20:54:23:02 - Horizontal piping

20:54:23:02. Horizontal piping. Horizontal piping shall be supported at sufficiently close intervals to keep it in alignment and prevent sagging. Horizontal piping shall conform to the following standards:

(1) Steel threaded pipe which is one-inch diameter or less shall be supported at eight-foot intervals, over one-inch diameter at ten-foot intervals;

(2) Copper tubing shall be supported at approximately six-foot intervals for piping one and one-fourth inches and smaller and ten-foot intervals for piping one and one-half inches and larger;

(3) Plastic pipe shall be supported at intervals not exceeding four feet.

Source: SL 1975, ch 16, ยง 1; 12 SDR 91, effective December 2, 1985; 12 SDR 151, 12 SDR 155, effective July 1, 1986.

General Authority:SDCL 36-25-14, 36-25-15.

Law Implemented:SDCL 36-25-15.

Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.