South Carolina Code of Regulations
Chapter 8 - BUILDING CODES COUNCIL
Article 12 - INTERNATIONAL RESIDENTIAL CODE
Section 8-1236 - IRC M1504.3 Exhaust Openings

Universal Citation: SC Code Regs 8-1236

Current through Register Vol. 48, No. 9, September 27, 2024

Air exhaust openings shall terminate as follows:

1. Not less than 3 feet (914 mm) from property lines.

2. Not less than 3 feet (914 mm) from gravity air intake openings, operable windows and doors.

3. Not less than 10 feet (3048 mm) from mechanical air intake openings except where the exhaust opening is located not less than 3 feet (914 mm) above the air intake opening. Openings shall comply with Sections R303.5.2 and R303.6.

Exception: Bathrooms, water closets shower spaces.

Disclaimer: These regulations may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.