South Carolina Code of Regulations
Chapter 8 - BUILDING CODES COUNCIL
Article 10 - INTERNATIONAL FUEL GAS CODE
Section 8-1007 - IFGC 505.1.1 Commercial cooking appliances vented by exhaust hoods

Universal Citation: SC Code Regs 8-1007
Current through Register Vol. 48, No. 3, March 22, 2024

Where commercial cooking appliances are vented by means of the Type I or Type II kitchen exhaust hood system that serves such appliances, the exhaust system shall be fan powered and the appliances shall be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating. Where a solenoid valve is installed in the gas piping as part of an interlock system, gas piping shall not be installed to bypass such valve. Dampers shall not be installed in the exhaust system.

Exception: An interlock between the cooking appliance and the exhaust hood system shall not be required for appliances that are of the manually operated type and are factory equipped with standing pilot burner ignition systems.

Disclaimer: These regulations may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.