South Carolina Code of Regulations
Chapter 71 - DEPARTMENT OF LABOR, LICENSING AND REGULATION-DIVISION OF LABOR
Article 9 - BOILER SAFETY PROGRAM
Subarticle 4 - GENERAL REQUIREMENTS
Section 71-9104 - General Requirements
Current through Register Vol. 48, No. 9, September 27, 2024
A. GR-1 Inspection of Boilers
All boilers not exempted by the Act or by rules and regulations promulgated under the Act and which are subject to regular inspections shall be prepared for such inspections as required in GR-2.
B. GR-2 Preparation for Inspection
The owner or user shall prepare each boiler for inspection, and shall prepare for and apply a hydrostatic or pressure test, whenever necessary, on the date arranged by the inspector which shall not be less than seven (7) days after the date of notification.
C. GR-3 Boilers Improperly Prepared for Inspection
If a boiler has not been properly prepared for an internal inspection, or if the owner or user fails to comply with the requirements for a pressure test as set forth in these rules, the inspector may decline to make the inspection or test.
D. GR-4 Removal of Covering to Permit Inspection
If, upon an external inspection, there is evidence of a leak or crack, sufficient covering of the boiler shall be removed to permit the inspector to satisfactorily determine the safety of the boiler.
E. GR-5 Lap Seam Crack
The shell or drum of a boiler (in which a lap seam crack is discovered along a longitudinal riveted joint) shall be immediately discontinued from use. Patching is prohibited. (Lap seam crack refers to a crack found in lap seams extending parallel to the longitudinal joint, and located either between or adjacent to rivet holes.)
F. GR-6 Pressure Test
G. GR-7 Automatic Low-Water Fuel Cutoff and/or Water Feeding Device
H. GR-8 Pressure Reducing Valves
I. GR-9 Boiler Blow Off Equipment
J. GR-10 Location of Discharge Piping Outlets
The discharge of safety valves, blow off pipes, and other outlets shall be located and supported as to prevent injury to personnel.
K. GR-11 Supports
Each boiler shall be supported by masonry or structural supports of sufficient strength and rigidity to safely support the boiler and its contents. There shall be no excessive vibration in either the boiler or its connecting piping.
L. GR-12 Boiler Door Latches
M. GR-13 Clearance
When boilers are replaced or new boilers are installed in either existing or new buildings, a minimum height of at least 3 ft. shall be provided between the top of the boiler proper and the ceiling, and at least 3 ft. between all sides of the boiler and adjacent walls or other structures. Boilers and pressure vessels having manholes shall have 5 ft. clearance from the manhole opening and any wall, ceiling or piping that will prevent a person from entering the boiler or vessel. All boilers shall be so located that adequate space will be provided for the proper operation of the boilers and their appurtenances, for the inspection of all surfaces, tubes, water walls, economizers, piping, valves and other equipment, and for their necessary maintenance and repair and replacement of tubes.
N. GR-14 Ladders and Runways
When necessary for safety, there shall be a steel runway or platform of standard construction installed across the tops of adjacent boilers or at some other convenient level for the purpose of affording safe access. All walkways shall have at least two means of exit, each to be remotely located from the other.
O. GR-15 Exit from Boiler Room
All boiler rooms exceeding a 500 sq. ft. floor area and containing one or more boilers having a fuel-burning capacity of 1,000,000 BTU, or equivalent electrical heat input, shall have at least two means of exit. Each exit shall be remotely located from the other. Each elevation in such boiler room shall have two means of exit, each remotely located from the other.
P. GR-16 Suggestions for Operations
It is suggested that the Recommended Rules for Care of Power Boilers, Section VII, and the Recommended Rules for Care and Operation of Heating Boilers, Section VI, of the ASME Code be used as a guide for proper and safe operating practices.
Q. GR-17 Air and Ventilation Requirements - Combustion Air Supply and Ventilation of Boiler Room
A permanent source of outside air shall be provided for each boiler room to permit satisfactory combustion of the fuel as well as proper ventilation of the boiler room under normal operating conditions.
INPUT BTU/HOUR |
REQUIRED AIR MIN. CU/FT/MIN. |
NET LOUVERED AREA, SQ. FT. |
500,000 |
T125 |
1.0 |
1,000,000 |
250 |
1.0 |
2,000,000 |
500 |
1.6 |
3,000,000 |
750 |
2.5 |
4,000,000 |
1,000 |
3.3 |
5,000,000 |
1,250 |
4.1 |
6,000,000 |
1,500 |
5.0 |
7,000,000 |
1,750 |
5.8 |
8,000,000 |
2,000 |
6.6 |
9,000,000 |
2,250 |
7.5 |
10,000,000 |
2,500 |
8.3 |
R. GR-18 Gas Burners
For installations, which are gas fired, the burners used shall conform to the applicable requirements of nationally recognized standards.
S. GR-19 Conditions Not Covered by These Rules and Regulations
For any conditions not covered by these requirements, the applicable provisions of the ASME Code, the National Board Inspection Code, or the American Petroleum Institute Pressure Vessel Inspection Code shall apply.