Sec2 61-93.2600 - PHYSICAL PLANT
Section 61-93.2600.2618 - Doors (II)
Current through Register Vol. 48, No. 9, September 27, 2024
A. All Patient rooms and bathrooms and restrooms shall have opaque doors for the purpose of privacy.
B. All glass doors, including sliding or patio type doors shall have a contrasting or other indicator that causes the glass to be observable.
C. Bathroom and restroom door widths shall be not less than thirty-six (36) inches.
D. Doors to Patient occupied rooms shall be at least thirty-six (36) inches wide.
E. Doors that have locks shall be unlockable and openable with one action.
F. If Patient room doors are lockable, there shall be provisions for emergency entry. There shall not be locks that cannot be unlocked and operated from inside the room.
G. All Patient room doors shall be solid-core.