Sec2 61-93.2600 - PHYSICAL PLANT
Section 61-93.2600.2607 - Cross-connections (I)

Universal Citation: SC Code Regs 61-93.2600.2607
Current through Register Vol. 48, No. 9, September 27, 2024

Facilities shall ensure that there are no cross-connections in plumbing between safe and potentially unsafe water supplies. Facilities shall ensure water is delivered at least two (2) delivery pipe diameters above the rim or points of overflow to each fixture, equipment, and service unless protected against back-siphonage by approved vacuum breakers or other approved back-flow preventers. Facilities shall ensure that all faucets and fixtures which may be attached to a hose have an approved vacuum breaker or other approved back-flow preventer.

Disclaimer: These regulations may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.