Section 61-92.280.C.32 - COMPATIBILITY
Current through Register Vol. 48, No. 9, September 27, 2024
(a) Owners and operators must use an UST system made of or lined with materials that are compatible with the substance stored in the UST system.
(b) Owners and operators must notify the Department at least 30 days prior to switching to a regulated substance containing greater than 10 percent ethanol, greater than 20 percent biodiesel, or any other regulated substance identified by the Department. In addition, owners and operators with UST systems storing these regulated substances must meet one of the following:
(c) Owners and operators must maintain records in accordance with Section 280.34(b) documenting compliance with paragraph (b) of this section for as long as the UST system is used to store the regulated substance.
[Note to Section 280.32. The following code of practice may be useful in complying with the requirements of this section:
American Petroleum Institute Recommended Practice 1626, "Storing and Handling Ethanol and Gasoline-Ethanol Blends at Distribution Terminals and Filling Stations"]