Part 280 - TECHNICAL STANDARDS AND CORRECTIVE ACTION REQUIREMENTS FOR OWNERS AND OPERATORS OF UNDERGROUND STORAGE TANKS (UST)
Subpart A - PROGRAM SCOPE AND INSTALLATION REQUIREMENTS FOR PARTIALLY EXCLUDED UST SYSTEMS
Section 61-92.280.A.11 - INSTALLATION REQUIREMENTS FOR PARTIALLY EXCLUDED UST SYSTEMS
Current through Register Vol. 48, No. 9, September 27, 2024
(a) Owners and operators must install an UST system listed in Section 280.10(c)(1),(3), or (4) storing regulated substances (whether of single or doublewall construction) that meets the following requirements:
(b) Notwithstanding paragraph (a) of this section, an UST system without corrosion protection may be installed at a site that is determined by a corrosion expert not to be corrosive enough to cause it to have a release due to corrosion during its operating life. Owners and operators must maintain records that demonstrate compliance with the requirements of this paragraph for the remaining life of the tank.
[Note to paragraphs (a) and (b). The following codes of practice may be used as guidance for complying with this section: