South Carolina Code of Regulations
Chapter 61 - DEPARTMENT OF HEALTH AND ENVIRONMENTAL CONTROL
Subchapter 61-79 - Hazardous Waste Management Regulations
Part 61-79.264 - STANDARDS FOR OWNERS AND OPERATORS OF HAZARDOUS WASTE TREATMENT, STORAGE, AND DISPOSAL FACILITIES
Subpart CC - AIR EMISSION STANDARDS FOR TANKS, SURFACE IMPOUNDMENTS, AND CONTAINERS (9/98)
Section 61-79.264.CC.1087 - Standards: Closed-vent systems and control devices
Universal Citation: SC Code Regs 61-79.264.CC.1087
Current through Register Vol. 48, No. 9, September 27, 2024
(a) This section applies to each closed-vent system and control device installed and operated by the owner or operator to control air emissions in accordance with standards of this subpart.
(b) The closed-vent system shall meet the following requirements:
(1) The closed-vent
system shall route the gases, vapors, and fumes emitted from the hazardous
waste in the waste management unit to a control device that meets the
requirements specified in paragraph (c) of this section.
(2) The closed-vent system shall be designed
and operated in accordance with the requirements specified in 264.1033(k) of
this part.
(3) In the case when the
closed-vent system includes bypass devices that could be used to divert the gas
or vapor stream to the atmosphere before entering the control device, each
bypass device shall be equipped with either a flow indicator as specified in
paragraph (b)(3)(i) of this section or a seal or locking device as specified in
paragraph (b)(3)(ii) of this section. For the purpose of complying with this
paragraph, low leg drains, high point bleeds, analyzer vents, open-ended valves
or lines, spring loaded pressure relief valves, and other fittings used for
safety purposes are not considered to be bypass devices.
(i) If a flow indicator is used to comply
with paragraph (b)(3) of this section, the indicator shall be installed at the
inlet to the bypass line used to divert gases and vapors from the closed-vent
system to the atmosphere at a point upstream of the control device inlet. For
this paragraph, a flow indicator means a device which indicates the presence of
either gas or vapor flow in the bypass line.
(ii) If a seal or locking device is used to
comply with paragraph (b)(3) of this section, the device shall be placed on the
mechanism by which the bypass device position is controlled (e.g., valve
handle, damper lever) when the bypass device is in the closed position such
that the bypass device cannot be opened without breaking the seal or removing
the lock. Examples of such devices include, but are not limited to, a car-seal
or a lock-and-key configuration valve. The owner or operator shall visually
inspect the seal or closure mechanism at least once every month to verify that
the bypass mechanism is maintained in the closed position.
(4) The closed-vent system shall be inspected
and monitored by the owner or operator in accordance with the procedure
specified in 264.1033(l).
(c) The control device shall meet the following requirements:
(1) The control device
shall be one of the following devices:
(i) A
control device designed and operated to reduce the total organic content of the
inlet vapor stream vented to the control device by at least 95 percent by
weight;
(ii) An enclosed combustion
device designed and operated in accordance with the requirements of 264.1033(c)
of this part; or
(iii) A flare
designed and operated in accordance with the requirements of 264.1033(d) of
this part.
(2) The owner
or operator who elects to use a closed-vent system and control device to comply
with the requirements of this section shall comply with the requirements
specified in paragraphs (c)(2)(i) through (c)(2)(vi) of this section.
(i) Periods of planned routine maintenance of
the control device, during which the control device does not meet the
specifications of paragraphs (c)(1)(i), (c)(1)(ii), or (c)(1)(iii) of this
section, as applicable, shall not exceed 240 hours per year.
(ii) The specifications and requirements in
paragraphs (c)(1)(i), (c)(1)(ii), and (c)(1)(iii) of this section for control
devices do not apply during periods of planned routine maintenance.
(iii) The specifications and requirements in
paragraphs (c)(1)(i), (c)(1)(ii), and (c)(1)(iii) of this section for control
devices do not apply during a control device system malfunction.
(iv) The owner or operator shall demonstrate
compliance with the requirements of paragraph (c)(2)(i) of this section (i.e.,
planned routine maintenance of a control device, during which the control
device does not meet the specifications of paragraphs (c)(1)(i), (c)(1)(ii), or
(c)(1)(iii) of this section, as applicable, shall not exceed 240 hours per
year) by recording the information specified in 264.1089(e)(1)(v) of this
subpart.
(v) The owner or operator
shall correct control device system malfunctions as soon as practicable after
their occurrence in order to minimize excess emissions of air
pollutants.
(vi) The owner or
operator shall operate the closed-vent system such that gases, vapors, or fumes
are not actively vented to the control device during periods of planned
maintenance or control device system malfunction (i.e., periods when the
control device is not operating or not operating normally) except in cases when
it is necessary to vent the gases, vapors, and/or fumes to avoid an unsafe
condition or to implement malfunction corrective actions or planned maintenance
actions.
(3) The owner
or operator using a carbon adsorption system to comply with paragraph (c)(1) of
this section shall operate and maintain the control device in accordance with
the following requirements:
(i) Following the
initial startup of the control device, all activated carbon in the control
device shall be replaced with fresh carbon on a regular basis in accordance
with the requirements of 264.1033(g) or 264.1033(h) of this part.
(ii) All carbon that is a hazardous waste and
that is removed from the control device shall be managed in accordance with the
requirements of 264.1033(n), regardless of the average volatile organic
concentration of the carbon.
(4) An owner or operator using a control
device other than a thermal vapor incinerator, flare, boiler, process heater,
condenser, or carbon adsorption system to comply with paragraph (c)(1) of this
section shall operate and maintain the control device in accordance with the
requirements of 264.1033(j) of this part.
(5) The owner or operator shall demonstrate
that a control device achieves the performance requirements of paragraph (c)(1)
of this section as follows:
(i) An owner or
operator shall demonstrate using either a performance test as specified in
paragraph (c)(5)(iii) of this section or a design analysis as specified in
paragraph (c)(5)(iv) of this section the performance of each control device
except for the following:
(A) A
flare;
(B) A boiler or process
heater with a design heat input capacity of 44 megawatts or greater;
(C) A boiler or process heater into which the
vent stream is introduced with the primary fuel;
(D) A boiler or industrial furnace burning
hazardous waste for which the owner or operator has been issued a final permit
under part 270 and has designed and operates the unit in accordance with the
requirements of part 266, subpart H; or
(E) A boiler or industrial furnace burning
hazardous waste for which the owner or operator has designed and operates in
accordance with the interim status requirements of part 266, subpart
H.
(ii) An owner or
operator shall demonstrate the performance of each flare in accordance with the
requirements specified in 264.1033(e).
(iii) For a performance test conducted to
meet the requirements of paragraph (c)(5)(i) of this section, the owner or
operator shall use the test methods and procedures specified in 264.1034(c)(1)
through (c)(4).
(iv) For a design
analysis conducted to meet the requirements of paragraph (c)(5)(i) of this
section, the design analysis shall meet the requirements specified in
264.1035(b)(4)(iii).
(v) The owner
or operator shall demonstrate that a carbon adsorption system achieves the
performance requirements of paragraph (c)(1) of this section based on the total
quantity of organics vented to the atmosphere from all carbon adsorption system
equipment that is used for organic adsorption, organic desorption or carbon
regeneration, organic recovery, and carbon disposal.
(6) If the owner or operator and the
Department do not agree on a demonstration of control device performance using
a design analysis then the disagreement shall be resolved using the results of
a performance test performed by the owner or operator in accordance with the
requirements of paragraph (c)(5)(iii) of this section. The Department may
choose to have an authorized representative observe the performance
test.
(7) The closed-vent system
and control device shall be inspected and monitored by the owner or operator in
accordance with the procedures specified in 264.1033(f)(2) and 264.1033(1). The
readings from each monitoring device required by 264.1033(f)(2) shall be
inspected at least once each operating day to check control device operation.
Any necessary corrective measures shall be immediately implemented to ensure
the control device is operated in compliance with the requirements of this
section.
Disclaimer: These regulations may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.