Sec2 61-78.2900 - PHYSICAL PLANT
Section 61-78.2900.2903 - Patient Room Floor Area

Universal Citation: SC Code Regs 61-78.2900.2903

Current through Register Vol. 48, No. 9, September 27, 2024

A. Each patient room shall be an outside room with an outside window. This window shall not open onto a common area screened porch. (I)

B. The patient room floor area is a usable or net area and does not include wardrobes (built-in or freestanding), closets, or the entry alcove to the room. The following is the minimum floor space allowed: (II)

1. Rooms for only one (1) patient: one hundred (100) square feet for the licensed bed (there shall be compliance with the minimum square footage requirements of Section 2903.B.2 in instances when family members or responsible party routinely utilize a separate bed for overnight stays with the patient);

2. Rooms for more than one (1) patient: eighty (80) square feet per licensed bed. C. There shall be at least three (3) feet between beds. (II)

Disclaimer: These regulations may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.