Current through Register Vol. 48, 12, December 27, 2024
(1) Presedimentation--Presedimentation
basins, where used, shall be designed such that:
(a) incoming water is dispersed across the
full width of the line of travel;
(b) short circuiting shall be prevented;
and,
(c) provisions for bypassing
presedimentation basins are included.
(2) Conventional Sedimentation
(a) Rapid Mix--The rapid mix shall be
designed so as to ensure the rapid dispersion of chemicals throughout the water
to be treated.
(i) Mechanical Mixer--The
mechanical mixer shall have sufficient horsepower to provide adequate
dispersion of treatment chemicals and be equipped with variable speed
drive.
(ii) Location--The rapid mix
and flocculation basins shall be as close together as possible.
(iii) In-line mixers must be specifically
approved by the Department, and shall be designed based on manufacturers
recommendation and studies using the raw water source. In-line mixers shall be
accessible without excavation.
(iv)
A by-pass around the rapid mix or in-line mixers is prohibited.
(b) Flocculation--A minimum of two
(2) parallel flocculation basins are required.
(i) Conventional Basin Design--Inlet and
outlet design shall prevent short circuiting and destruction of floc. A drain
or pumps shall be provided to handle de-watering and sludge removal.
(ii) Detention--The flow through velocity
shall not be less than five tenths (0.5) nor greater than one and one half
(1.5) feet per minute with detention time for floc formation of at least thirty
(30) minutes.
(iii)
Equipment--Multi-stage agitators shall be provided. The velocity gradient (G)
shall decrease with each stage. G values shall be in the range of five (5) to
one hundred (100) second 2-1.
(iv) Piping--Flocculation and sedimentation
basins shall be as close together as possible. The velocity of flocculated
water through pipes and conduits to settling basins shall not be less than five
tenths (0.5) nor greater than one and one half (1.5) feet per second.
Allowances shall be made to minimize turbulence at bends and changes in
direction
(v) Other
designs--Baffling may be used to provide flocculation in small plants only
after consultation with the Department. The design shall be such that the
velocities and flows noted above will be maintained.
(c) Sedimentation--A minimum of two (2)
sedimentation basins are required.
(i)
Detention time - Sedimentation basin design considerations and calculations
shall include basin overflow rate, weir loading rate, flow through velocity and
theoretical detention time. For conventional sedimentation basins with
detention times of less than four (4) hours, an acceptable alternate basis for
design must be provided and must be approved by the Department.
(ii) Inlet Devices--Inlets shall be designed
to distribute water equally and at uniform velocities. The structures shall be
designed so as to dissipate inlet velocities and provide uniform flows across
the basin.
(iii) Outlet
Devices--Outlet devices shall be designed to maintain velocities suitable for
settling in the basin and to minimize short circuiting.
(iv) Outlet Flow Rate--The approach velocity
at the outlet weir shall be such that the resuspension of floc is
minimized.
(v) Velocity--The
velocity through settling basins shall not exceed five tenths (0.5) of a foot
per minute, except as specifically approved by the Department. The basins shall
be designed to minimize short circuiting. Baffles shall be provided, as
necessary.
(vi) Overflow--An
overflow weir (or pipe) shall be installed which will establish the maximum
water level desired on top of the filters. It shall overflow at a location
observable to the operator.
(vii)
Drainage--Basins shall be provided with the means for draining, either by
gravity or pumps. The amount of time required to drain the basin shall not be
such that it interferes with plant operation.
(viii) Sludge handling--Facilities are
required by the Department for the disposal of sludge and shall be designed in
accordance with R.61-58.3(F)(F). Provisions shall be made for the operator to
observe and sample sludge being withdrawn from the basin.
(ix) Washdown Hydrants--Washdown hydrants
shall be provided and shall be equipped with backflow prevention devices
acceptable to the Department.
(3) Solids Contact Clarification--A minimum
of two (2) solids contact units are required unless continuous sludge
withdrawal is provided.
(a) Chemical
Feed--Chemicals shall be applied at such points and by such means as to ensure
satisfactory mixing of the chemicals with the water.
(b) Mixing--Rapid mix device or chamber ahead
of the solids contact unit may be required by the Department to assure proper
mixing of the chemicals applied. Mixing devices employed shall be so
constructed as to provide adequate mixing of the raw water with previously
formed sludge particles, and prevent deposition of solids in the mixing
zone.
(c)
Flocculation--Flocculation Equipment shall:
(i) have variable speed drive;
(ii) provide for coagulation to occur in a
separate chamber or baffled zone within the unit; and,
(iii) provide the flocculation and mixing
period to be not less than thirty (30) minutes, except as approved by the
Department.
(d) Sludge
removal--Sludge removal design shall provide that:
(i) sludge pipes shall not be less than three
(3) inches in diameter and shall be arranged so as to facilitate
cleaning;
(ii) entrance to sludge
withdrawal piping shall be designed to prevent clogging;
(iii) valves shall be located outside the
tank for accessibility;
(iv) the
operator may observe and sample sludge being withdrawn from the unit;
and,
(v) blowdown processes are
automated.
(e) Sludge
handling--Facilities are required by the Department for the disposal of sludge
and shall be designed in accordance with R.61-58.3(F)(F).
(f) Cross-connections
(i) Blow off outlets and drains shall
terminate with proper air gap discharge at a location satisfactory to the
Department.
(ii) Cross-connection
control shall be included for the potable water lines used to backflush sludge
lines.
(g) Detention
time--The detention time shall be established on the basis of raw water
characteristics and other local conditions that affect the operation of the
unit.
Design considerations and calculations shall include
theoretical detention time, weir loading rate, and surface loading rate.
(h) Weirs or orifices--The units
shall be equipped with either overflow weirs or orifices.
(i) Weirs shall be adjustable, and at least
equivalent in length to the perimeter of the tank. They shall be constructed so
that water at the surface does not travel over ten (10) feet horizontally to
the collection trough.
(ii) Weir
loading shall not exceed fifteen (15) gallons per minute per foot of weir
length for units used for softeners or clarifiers removing heavy alum floc
(high turbidity raw water), or ten (10) gallons per minute per foot of weir
length for units used for clarifiers removing light alum floc (low turbidity
raw water).
(iii) Weirs or orifices
shall produce uniform rising rates over the entire area of the tank.
(iv) Where orifices are used, the loading per
foot shall be equivalent to specified weir loadings.
(i) Overflow rates--Unless supporting data is
submitted to the Department the following rates shall not be exceeded:
(i) One and seventy-five hundredths (1.75)
gallons per minute per square foot of area at the slurry separation line, for
units used for softeners; and,
(ii)
One (1.0) gallon per minute per square foot of area at the sludge separation
line for units used for turbidity removal.
(4) Tube or Plate Settlers--Pilot test data
is required prior to approval of settler units. The pilot tests must
demonstrate that the unit is capable of treating the source water to comply
with all drinking water standards during the worst conditions of raw water
quality.
(a) Inlet and outlet
considerations--Inlet and outlet devices shall be designed such that proper
settling velocities are maintained and short circuiting is minimized.
(b) Drainage--Drain piping from the settler
units shall be sized to facilitate a quick flush of the settler units, and to
prevent flooding of the other portions of the plant.
(c) Application rate for tubes - A maximum
rate of two (2) gallons per minute per square foot of cross-sectional area is
allowed for tube settlers, unless pilot or full scale demonstration testing
indicate that higher rates do not adversely affect water quality.
(d) Application rates for plates - A maximum
plate loading rate of five tenths (0.5) gallons per minute per square foot,
based on eighty (80) percent of the projected horizontal plate area is allowed,
unless pilot or full scale demonstration testing indicate that higher rates do
not adversely affect water quality.
(e) Flushing lines - Flushing lines shall be
provided to facilitate maintenance, and shall be properly protected against
backflow and back siphonage.
(5) Filtration--The following criteria
applies to both conventional down-flow filters and to up-flow filters. All
filters treating surface water must meet the performance standards set forth in
R.61-58.10(E)(E).
The application of any one type of filtration must be supported
by water quality data representing a reasonable period of time to characterize
the variations in water quality. Experimental treatment studies may be required
to demonstrate the applicability of the method of filtration proposed. The
maximum loss of head should be designed to occur at the point of terminal
filter turbidity increase.
(a) Rapid
Rate Gravity Filters
(i) Pretreatment--The
use of rapid rate gravity filters shall require pretreatment.
(ii) Number--At least two (2) units shall be
provided. Provisions shall be made to assure continuity of service with a
filter unit temporarily removed from operation. The plant shall be designed so
that the design filtration rate is not exceeded during backwash operations. In
addition, provisions shall be made so that hydraulic surges through the filters
are minimized during flow rate changes and when filters are removed from
service for backwashing.
(iii) Rate
of Filtration--The rate of filtration shall be determined through
considerations of such factors as the quality of the raw water, the degree of
pretreatment provided, the filter media provided and other considerations
required by the Department. The nominal rate shall be four (4) gallons per
minute per square foot of filter area except as higher rates are justified by
the professional engineer to the satisfaction of the Department.
(iv) Structural Details and hydraulics--The
filter structure shall be designed to provide:
(A) vertical walls within the
filter;
(B) no protrusion of the
filter walls into the filter media;
(C) head room to permit normal inspection and
operation;
(D) access to at least
fifty (50) percent of the perimeter.
(E) minimum depth of filter of eight and one
half (8- 1/2) feet measured from the top of the underdrain to the top of the
filter bay;
(F) If a filter is
designed to operate to a specified loss of head then the filter shall be
designed with that water level or greater above the surface of the filter
media;
(G) trapped effluent to
prevent backflow of air to the bottom of the filters;
(H) prevention of floor drainage to the
filter with a minimum four (4) inch curb around the filters;
(I) maximum influent velocity of treated
water in pipes and conduits to filters of two (2) feet per second;
(J) cleanouts and straight alignment for
influent pipes or conduits where solids loading is heavy, or following
lime-soda softening;
(K) washwater
drain capacity to carry maximum backwash flow;
(L) walkways around filters, to be not less
than twenty-four (24) inches wide;
(M) safety handrails or walls around filter
areas adjacent to walkways; and,
(N) no roof drainage into the filter or
basins and conduits preceding the filters.
(v) Washwater Troughs--Washwater troughs
shall be designed to provide:
(A) the bottom
elevation of the trough must be above the maximum level of expanded media
during washing;
(B) a two (2) inch
freeboard at the maximum rate of wash;
(C) the top or edge to be level;
(D) spacing so that each trough serves the
same number of square feet of filter area; and,
(E) maximum horizontal travel of suspended
particles to reach trough not to exceed three (3) feet.
(vi) Filter Material--One or more of the
following filter media shall be used and shall have a depth of at least thirty
(30) inches.
(A) Anthracite-- Clean crushed
anthracite, or a combination of anthracite and other media may be considered.
If used alone, the anthracite shall have an effective size of 0.45 millimeters
to 0.7 millimeters and a uniformity coefficient of not less than 1.3 nor
greater than 1.65. If used in conjunction with sand or other media, the
anthracite shall have an effective size of 0.45 millimeters to 1.2 millimeters
and a uniformity coefficient of not less than 1.3 nor greater than
1.85.
(B) Sand Media--Sand media
shall have an effective size of 0.45 millimeters to 0.55 millimeters, and a
uniformity coefficient of not less than 1.3 nor greater than 1.65.
(C) Granular Activated Carbon--Use of
granular activated carbon media, if used alone, may be considered only with
approval of the Department, and must meet the requirements for anthracite
media. There shall be provision for a free chlorine residual in the water
following the filters and prior to distribution. There must be a means for
periodic treatment of filter material for control of bacteria and other
growths, and there must be provisions for testing, regeneration, and periodic
replacement of the carbon.
(D)
Torpedo Sand--A three (3) inch layer of torpedo sand shall be used as a
supporting media for the filter sand. Such torpedo sand shall have an effective
size of 0.8 millimeters to 2.0 millimeters, and a uniformity coefficient not
less than 1.3 nor greater than 1.7 millimeters.
(E) Gravel--Gravel, when used as the
supporting media, shall consist of hard, rounded particles and shall not
include flat or elongated particles. The coarsest gravel shall be 2.5 inches in
size when the gravel rests directly on the strainer system, and shall extend
above the top of the perforated laterals or strainer nozzles. The size and
depth of gravel required is dependent upon the type of underdrain used. Size
and depth of gravel required when using proprietary filter bottoms shall be in
accordance with the manufactures recommendations.
(F) Other Filter Media Design--Other filter
media design will be considered based on pilot test data and operating
experience.
(vii) Filter
Bottoms and Strainer Systems
(A) All filter
bottom and strainer systems shall be designed to ensure both an even
distribution of washwater with minimum head loss and a uniform rate of
filtration.
(B) The design of
manifold type collection systems shall be to provide the ratio of the area of
the final openings of the strainer system to the area of the filter of 0.003;
provide the total cross-sectional area of the laterals of twice the total area
of the final openings; and provide the cross-sectional area of the manifold at
one and one half (1.5) to two (2) times the total area of the
laterals.
(C) Proprietary bottoms
shall be permanently grouted or fastened in place.
(D) Porous plate bottoms shall not be used
where iron or manganese may clog them or with waters treated with lime prior to
filtration.
(viii)
Surface Wash or Subsurface Wash--Surface wash or subsurface wash facilities
shall be required for all filters treating surface water, unless an air
scouring system is provided, and may be accomplished by a system of fixed
nozzles or a revolving type apparatus. All surface wash or subsurface wash
devices shall be designed with:
(A)
provisions for water pressures of at least forty-five (45) pounds per square
inch;
(B) a properly installed
vacuum breaker or other approved device to prevent back siphonage;
and,
(C) a rate of flow of two (2)
gallons per minute per square foot of filter area with fixed nozzles or one
half (0.5) gallons per minute per square foot with revolving arms.
(ix) Air Scouring--Air scouring
may be used in lieu of or in conjunction with surface or subsurface wash, and
is recommended for filtration rates greater than four (4) gallons per minute
per square foot. The air scouring system shall be designed such that:
(A) air flow shall be three (3) to five (5)
standard cubic feet per minute per square foot of filter area when the air is
introduced in the underdrain; a lower rate must be used when the air scour
distribution system is placed above the underdrain;
(B) excessive loss of filter media during
backwashing is avoided;
(C) it is
followed by a fluidization wash which is sufficient to restatify the
media;
(D) the air supply remains
free from contamination;
(E)
clogging of the air scour nozzles and the entering of the media into the air
scour distribution system is avoided;
(F) air delivery piping does not pass down
through the filter media; and,
(G)
regular maintenance and/or replacement of the air delivery piping may be
performed.
(x)
Appurtenances--Each filter shall have:
(A)
sampling taps for filtered water, backwash water and rewash water;
(B) an indicating loss of head
gauge;
(C) indicating flow rate
control. Equipment that simply maintains a constant water level on the filters
is not acceptable, unless the rate of flow onto the filter is properly
controlled;
(D) provisions for
filtering water to waste with a properly installed vacuum breaker or other
approved device for backflow prevention;
(E) continuous recording device or computer
data for loss of head and rate of flow instrumentation; and,
(F) continuous turbidity monitoring equipment
for raw and settled water. Each filter shall be equipped with a continuous,
on-line turbidimeter. The filter effluent turbidimeters shall be nephelometric
type and equipped with alarms to be set to enunciate at five tenths (0.50)
nephelometric turbidity units. Continuous recorders or computer data which
record at no greater than fifteen (15) minute intervals are required for each
unit.
(xi)
Backwash--Provisions shall be made for washing filters as follows:
(A) A minimum rate of fifteen (15) gallons
per square foot per minute, consistent with water temperatures and specific
gravity of the filter media or a rate necessary to provide for a fifty (50)
percent expansion of the filter bed is required.
(B) Filtered water shall be provided at the
required rate by washwater tanks, a washwater pump, from the high service main,
a combination of these, or by other means acceptable to the
Department;
(C) Washwater pumps in
duplicate are required unless an alternate means of obtaining washwater is
available;
(D) Capacity for at
least twenty (20) minute wash of one filter is required at the design rate of
wash;
(E) A washwater regulator or
valve on the main washwater line to obtain the desired rate of filter wash with
the washwater valves on the individual filters open wide;
(F) A rate-of-flow indicator, preferably with
a totalizer, is required on the main washwater line, and shall be located so
that it can be easily read by the operator during the washing
process;
(G) The design shall
prevent rapid changes in backwash water flow; and,
(H) A treatment of filter backwash designed
in accordance with R.61-58.3 (F) shall be provided.
(b) High Rate Gravity Filters--No
rates above four (4) gallons per minute per square foot will be considered
without full scale pilot tests of at least twelve (12) month duration. High
rate approval will not be considered for a plant with a flashy raw water source
unless adequate off-stream storage is provided. High rate approval for existing
plants requires an engineering evaluation and will be approved only where a
sufficient number of experienced and qualified operators are employed. Where
high rate approval will not allow a plant to maintain minimum unit process
detention times specified in R.61-58.3.D(2), evaluations of those unit
processes must be included in the pilot test and high rate engineering
evaluation. The design of high rate gravity filters shall be in accordance with
all applicable requirements of R.61-58.3.D(5).
(c) Rapid Rate Pressure Filters--Pressure
filters will not be allowed as primary filtration on surface waters.
(d) Diatomaceous earth filtration will not be
allowed as primary filtration on surface waters.
(i) Conditions of use--Diatomaceous earth
filters are expressly excluded from consideration for bacteria removal, color
removal, or turbidity removal where either the gross quantity of turbidity is
high or the turbidity exhibits poor filterability characteristics, and
filtration of waters with high algae counts.
(ii) Pilot plant study--Installation of a
diatomaceous earth filtration system shall be preceded by a pilot plant study
on the water to be treated.
(A) Conditions of
the study such as duration, filter rates, head loss accumulation, slurry feed
rates, turbidity removal, bacteria removal, etc., shall be approved by the
Department prior to the study.
(B)
Satisfactory pilot plant results shall be obtained prior to preparation of
final construction plans and specifications.
(C) The pilot plant study shall demonstrate
the ability of the system to meet applicable drinking water standards at all
times.
(iii) Types of
filters--Pressure or vacuum diatomaceous earth filtration units will be
considered for approval.
(iv)
Treated water storage--Treated water storage capacity in excess of normal
requirements shall be provided to allow operation of the filters at a uniform
rate during all conditions of system demand at or below the approved filtration
rate, and guarantee continuity of service during adverse raw water conditions
without by-passing the system.
(v)
Number of filtration units--At least two (2) units shall be provided.
(vi) Precoat--A uniform precoat of at least
1/16 inch shall be applied hydraulically to each septum by introducing a slurry
to the tank influent line and employing either a filter-to-waste or
recirculation system.
(vii) Body
feed--A body feed system to apply additional amounts of diatomaceous earth
slurry during the filter run is required. Continuous mixing of the body feed
slurry shall be provided.
(viii)
Filtration
(A) Rate of filtration--The
filtration rate shall be controlled by a positive means and shall not exceed
one and a half (1.5) gallons per minute per square foot of filter.
(B) Head loss--The head loss shall not exceed
thirty (30) pounds per square inch for pressure diatomaceous earth filters, or
a vacuum of fifteen (15) inches of mercury for a vacuum system.
(C) Recirculation--A recirculation or holding
pump shall be employed to maintain differential pressure across the filter when
the unit is not in operation in order to prevent the filter cake from dropping
off the filter elements. A minimum recirculation rate of one tenth (0.1) gallon
per minute per square foot of filter area shall be provided.
(D) Septum or filter element--The filter
elements shall be structurally capable of withstanding maximum pressure and
velocity variations during filtration and backwash cycles, and shall be spaced
such that no less than one (1) inch is provided between elements or between any
element and a wall.
(E) Inlet
design--The filter influent shall be designed to prevent scour of the
diatomaceous earth from the filter element.
(ix) Backwash--A satisfactory method to
thoroughly remove and dispose of spent filter cake shall be provided. Treatment
is required for the backwash water and shall be designed in accordance with
applicable portions of R.61-58.3 (F).
(x) Appurtenances--The following shall be
provided for every filter:
(A) sampling taps
for raw and filtered water;
(B)
loss of head or differential pressure gauge;
(C) rate-of-flow indicator, with
totalizer;
(D) a throttling valve
used to reduce rates below normal during adverse raw water conditions;
and,
(E) an evaluation of the need
for body feed, recirculation, and any other pumps, in accordance with
R.61-58.4(B)(1)(d)(B)(1)(d).
(xi) Monitoring--A continuous monitoring
turbidimeter with recorder is required on the filter effluent.
(e) Direct Filtration--The use of
direct filtration technology will be considered only where sufficient raw water
quality and engineering data is submitted to justify such. No rates above four
(4) gallons per minute per square foot will be considered without full scale
pilot tests of at least twelve (12) month duration. The following shall be met
for direct filtration approval:
(i) Off
stream raw water storage must be provided, unless a consistent raw water
quality can be demonstrated to the satisfaction of the Department.
(ii) The flocculation chamber design shall be
based on pilot plant studies in conjunction with applicable portions of
R.61-58.3(D)(2)(D)(2).
(iii) Each
filter must meet the basic requirements of a rapid rate gravity filter as given
in R.61-58.3(D)(5)(D)(5).
(iv)
Filters shall be provided with either rapid rate dual or mixed media specified
for filtration rates of four (4) gallons per minute per square foot or
greater.
(v) Surface wash,
subsurface wash and/or air scour facilities designed in accordance with
R.61-58.3(D)(5)(a)(viii)(D)(5)(a)(viii) and R.61-58.3(D)(5)(a)(ix)for each
filter.
(vi) Each direct filtration
plant shall have continuous turbidity monitoring equipment for raw and settled
water. Each filter shall be equipped with a continuous, on-line turbidimeter.
The filter effluent turbidimeters shall be nephelometric type and equipped with
alarms set to enunciate at five tenths (0.50) nephelometric turbidity units.
Continuous recorders or computer data are required for each unit.
(vii) Continuous recording devices may be
required for loss of head and rate of flow instrumentation.
(viii) Provisions for filtration to waste
with appropriate measures for backflow prevention are required.
(6)
Disinfection--Disinfection may be accomplished with gas chlorine, chlorine
dioxide, ozone or chloramines. Other agents will be considered by the
Department provided that reliable feed equipment is available and test
procedures for a residual are recognized, and the agent meets the requirements
of an acceptable drinking water additive. Continuous disinfection will be
required at all surface water supplies. Due consideration shall be given to the
contact time of the disinfectant in water with relation to pH, ammonia,
taste-producing substances, temperature, bacterial quality, and other pertinent
factors. Consideration also must be given to the formation of disinfection
by-products and meeting the contact times prescribed in R.61-58.10.
(a) Chlorination--Where chlorine is used the
following shall apply:
(i) Type--Only vacuum
type gas chlorinators are acceptable.
(ii) Capacity--The chlorinator capacity shall
be such that a free chlorine residual of at least five (5) milligram per liter
can be attained in the water after a contact time of at least thirty (30)
minutes at maximum flow rates. The equipment shall be of such design that it
will operate accurately over the desired feeding range.
(iii) Number of units--at least one (1)
backup chlorinator shall be provided in addition to the number required for
each primary feed point. The backup chlorinator shall be equal to the capacity
of the largest chlorinator in use.
(iv) Automatic Proportioning--Automatic
proportioning chlorinators will be required where the rate of flow or chlorine
demand is not reasonably constant or where the rate of flow of the water is not
manually controlled.
(v) Residual
Chlorine--Where alternate disinfectants are used in the treatment process, the
capability for the addition of either free or combined chlorine in the finished
water shall be provided. Residual chlorine must be sufficient to meet the
applicable requirements of R.61-58.10.
(b) Cross connection protection--The
chlorinator water supply piping shall be designed to prevent contamination of
the treated water supply by sources of questionable quality.
(c) Chlorine gas--Consideration shall be
given to the location of gas chlorine facilities and the safety of the public
in the surrounding area. Consideration may be given for facilities that propose
the use of chlorine gas in inhabited areas when the use of safety devices which
will not allow the release of chlorine gas (e.g. chlorine scrubbers) are
provided. Only vacuum gas chlorinator systems will be approved.
(i) Chlorine gas feed shall be enclosed and
separated from other operating areas. Concrete, wood, and other construction
materials shall be sealed to prevent the escape of chlorine gas from the
chlorine building. The chlorine room shall be provided with a shatter resistant
inspection window installed in an interior wall or an inspection window in the
door. It shall be constructed in such a manner that all openings between the
chlorine room and the remainder of the plant are sealed, and shall be provided
with doors ensuring ready means of exit and opening only to the building
exterior.
(ii) Full and empty
cylinders of chlorine gas shall be isolated from operating areas, restrained in
position to prevent upset, stored in rooms separate from ammonia storage, and
stored in areas not in direct sunlight or exposed to excessive heat.
(iii) If the chlorine room is large enough
for a person to enter, the room shall be constructed such that:
(A) It has a ventilating fan with a capacity
which provides one complete air change per minute;
(B) The ventilating fan shall be located near
the ceiling and pull suction through a duct extending to within twelve (12)
inches of the floor and discharge as far as practical from the door and air
inlet. The point of discharge shall be located so as not to contaminate air
inlets to any rooms or structures. A sealed motor or other means shall be used
to ensure the reliability of the fan;
(C) Air inlets shall be located near the
ceiling;
(D) Air inlets and outlets
shall have mechanical louvers;
(E)
Switches for fans and lights are outside of the room, at the
entrance;
(F) Vents from feeders
and storage areas discharge to the outside atmosphere, above grade and away
from inlet vent; and,
(G)
Ventilation shall not be automatically controlled.
(iv) If the room is too small for a person to
enter, the room must meet only R.61-58.3(D)(2)(c)(iii)(E) and
(F)(D)(2)(c)(iii)(E) and (F).
(v)
Chlorine feed lines shall meet the following requirements:
(A) Chlorine gas under pressure shall be
piped with schedule eighty (80) stainless steel or schedule eighty (80)
seamless carbon steel. No chlorine gas under pressure will be piped beyond the
chlorinator room.
(B) Chlorine gas
under vacuum shall be piped with schedule eighty (80) PVC or reinforced
fiberglass.
(C) Chlorine solution
shall be piped with schedule eighty (80) PVC.
(vi) Heaters shall be provided to maintain
proper temperature for operation.
(vii) There shall be no equipment housed in
the chlorine room except chlorinators, chlorine cylinders, weighing scales,
heater, ventilation fan, and light(s).
(viii) Weighing scales shall be provided for
weighing cylinders, at all installations utilizing chlorine gas unless
provisions for automatic switchover of cylinders and an acceptable alternate
means to determine daily dosage are provided.
(ix) Chlorine feed systems shall be designed
to ensure continuous feed of chlorine.
(x) If a floor drain is provided, it shall be
equipped with a water seal or trap to prevent escaped gases from exiting
through the building sewer.
(xi) A
chlorine leak detection and alarm system shall be provided.
(d) Ozone--Ozone is a suitable
disinfectant for surface water. When used as a pre-treatment chemical for
surface water, provisions shall be made for post chlorination or
chloramination. Consideration shall be given to potential algae growth, removal
of assimilated carbon from treated waters, and the formation of oxidized
organics. On-site generation facilities shall be constructed in accordance with
manufacturer's standards.
(i) Pilot plant
tests--Pilot plant tests shall be performed with the water to be treated to
establish the optimum dosage, contact time, depth of conductor and the need for
multiple application points.
(ii)
Number of Units--At least two (2) generators shall be provided. The facility
shall be adequately sized to provide the maximum treatment capacity with one
generator out of service.
(iii)
Building Design--Ozone generators shall be housed in a separate room with
separate heating and ventilation. The building layout must provide for easy
access to the equipment. Ventilation equipment shall be two (2) speed with the
normal speed providing the normal distribution of heat or air movement. The
second speed must be capable of providing a complete turnover of the air in the
room every two (2) minutes to exhaust any ozone leakage in an
emergency.
(iv) Piping Materials
(A) All dry ozone gas piping shall be
mechanical jointed number 304 or 316 stainless steel or welded 304L or 316L
stainless steel. All wet ozone gas piping shall be number 316 or 316L stainless
steel. All flexible couplings shall be stainless steel.
(B) Valves shall be stainless steel face and
body.
(C) Gasket materials shall be
resistant to deterioration by the ozone.
(v) Reinforced concrete or stainless steel
are acceptable materials. All concrete joints shall be sealed using a synthetic
rubber material resistant to deterioration by ozone.
(e) Other disinfection agents--Any proposal
for the use of other disinfecting agents shall be approved by the Department
prior to preparation of final plans and specifications.
(f) Ammonia Gas--Consideration shall be given
to the location of ammonia gas facilities and the safety of the public in the
surrounding area. Only vacuum ammonia systems will be approved.
(i) Ammonia gas feed shall be enclosed and
separated from other operating areas. Concrete, wood, and other construction
materials shall be sealed to prevent the escape of ammonia gas from the room.
The ammonia room shall be provided with a shatter resistant inspection window
installed in an interior wall or an inspection window in the door. It shall be
constructed in such a manner that all openings between the ammonia room and the
remainder of the plant are sealed, and shall be provided with doors ensuring
ready means of exit and opening only to the building exterior.
(ii) Full and empty cylinders of ammonia gas
shall be isolated from operating areas, restrained in position to prevent
upset, stored in rooms separate from chlorine storage, and stored in areas not
in direct sunlight or exposed to excessive heat.
(iii) If the ammonia room is large enough for
a person to enter, the room shall be constructed such that:
(A) It has a ventilating fan with a capacity
which provides one complete air change per minute;
(B) The ventilating fan shall be located and
pull suction near the ceiling and discharge as far as practical from the door
and air inlet. The point of discharge shall be located so as not to contaminate
air inlets to any rooms or structures. A sealed motor or other means shall be
used to ensure the reliability of the fan;
(C) Air inlets shall be located near the
floor;
(D) Air inlets and outlets
shall have mechanical louvers;
(E)
Switches for fans and lights are outside of the room, at the
entrance;
(F) Vents from feeders
and storage areas discharge to the outside atmosphere, above grade and away
from inlet vent; and,
(G)
Ventilation shall be automatically controlled.
(iv) If the room is too small for a person to
enter, the room must meet only R.61-58.3(D)(2)(f)(iii)(E), and
(F)(D)(2)(f)(iii)(E), and (F).
(v)
Ammonia feed lines shall not carry ammonia gas beyond the ammonia
room.
(vi) There shall be no
equipment housed in the ammonia room except ammoniators, ammonia cylinders,
weighing scales, heater, ventilation fan, and light(s).
(vii) Weighing scales shall be provided for
weighing cylinders, at all plants utilizing ammonia gas from cylinders. Where
bulk storage tanks are installed, they shall be equipped with a pressure
gauge.
(viii) Ammonia leak
detectors with alarms shall be provided.
(g) Chlorine Dioxide - Chlorine Dioxide is a
suitable disinfectant for surface water. Chlorine dioxide shall be generated on
site. The unit shall be flow paced and not have a holding tank for the chlorine
dioxide solution generated. All applicable EPA disinfectant by-product rules
shall be observed.
(i) Sizing of the chlorine
dioxide generator - Chlorine dioxide demand studies shall be conducted to
determine estimated feed rates and points of feed.
(ii) Building Design -
(A) Chlorine dioxide generators shall be
located in a room separate from chlorine cylinders.
(B) Number of Units: Where chlorine dioxide
is used as the primary disinfectant, at least two (2) flow pacing chlorine
dioxide generators shall be provided. The facility shall be adequately sized to
supply the maximum treatment capacity with any one generator out of service. If
chlorine dioxide is not used as a primary disinfectant (i.e. an oxidant only),
a second generator is not required.
(iii) Piping Materials -
(A) All piping from the chlorine dioxide
generator shall be schedule 80 PVC.
(B) Gasket materials shall be kynar or other
compatible material.
(C) All tubing
connector fittings shall be kynar or other compatible material.
(7)
Aeration--Aeration treatment devices, as described herein, may be used for
oxidation, separation of gases or for taste and odor control.
(a) General Requirements
(i) Sample taps must be provided following
aeration equipment.
(ii) Where
aeration equipment discharges directly to the distribution system, air release
valves must be provided.
(b) Natural Draft Aeration--Design shall
provide that:
(i) Water is distributed
uniformly over the top tray;
(ii)
Water is discharged through a series of three (3) or more trays with the
separation of trays not less than twelve (12) inches;
(iii) Trays are loaded at a rate of one (1)
gallon per minute to five (5) gallons per minutes for each square foot of total
tray area;
(iv) Trays have slotted,
woven wire cloth or perforated bottoms;
(v) Perforation are three sixteenth ( 3/16)
to one-half ( 1/2) inches in diameter, spaced one (1) to three (3) inches on
centers, when perforations are used in the distribution pan;
(vi) Construction of durable material
resistant to the aggressiveness of the water and dissolved gases;
(vii) Protection of aerators from loss of
spray water by wind carriage by enclosure with louvers sloped to the inside at
an angle of approximately forty-five (45) degrees;
(viii) Protection from insects by number
twenty-four (24) mesh screen; and,
(ix) Aerated water receives disinfection
treatment.
(c) Forced or
Induced Draft Aeration--Devices shall be designed to:
(i) Provide an adequate countercurrent of air
through the enclosed aeration column;
(ii) Include a blower in a screened enclosure
and with a watertight motor;
(iii)
Exhaust air directly to the outside atmosphere;
(iv) Include a down-turned, number
twenty-four (24) mesh screened air outlet and inlet;
(v) Be such that air introduced in the column
shall be as free from noxious fumes, dust, and dirt as possible;
(vi) Be such that sections of the aerator can
be easily reached or removed for maintenance of the interior;
(vii) Provide loading at a rate of one (1) to
five (5) gallons per minute for each square foot of total tray area;
(viii) Ensure that the water outlet is
adequately sealed to prevent the unwarranted loss of air;
(ix) Discharge through a series of five (5)
or more trays, with separation of trays not less than six (6) inches;
(x) Provide distribution of water uniformly
over the top tray; and,
(xi) Be of
a durable corrosive resistant material.
(d) Pressure Aeration--This method may be
used for oxidation purposes if pilot plant study indicates method is
applicable. It is not acceptable for removal of dissolved gases. Filters
following pressure aeration shall have adequate exhaust devices for release of
air. Pressure aeration devices shall be designed to give thorough mixing of
compressed air with water being treated. Screened and filtered air, free of
noxious fumes, dust, dirt and other contaminants shall be provided.
(e) Other Methods of Aeration--Other methods
of aeration may be used if applicable to the treatment needs. Such methods may
include, but are not restricted to, spraying, diffused air, cascades, and
mechanical aeration. The treatment processes shall be designed to meet the
particular needs of the water to be treated and shall be subject to Department
approval.
(8)
Fluoridation--Commercial sodium fluoride, sodium silicofluoride and
hydrofluorosilic acid shall be NSF approved and shall conform to American
Waterworks Association Standards B701, B702 and B703, respectively. Fluoride
chemicals shall meet the requirements of chemical additives in
R.61-58.2(E)(3)(E)(3). The proposed method of fluoride feed shall be approved
by the Department prior to preparation of final plans and specifications.
(a) Fluoride Compound Storage - Dry chemical
storage shall be designed in accordance with R.61-58.3.E(2)(e).
Storage units for hydrofluorosilic acid shall be isolated from operating areas
and shall be vented to the atmosphere at a point outside any
building.
(b) Dry
Conveyors--Provisions shall be made for the proper transfer of dry fluoride
compounds from shipping containers to storage bins or hoppers, in such a way as
to minimize the quantity of fluoride dust.
(c) Injection Point--The fluoride compound
shall not be added before lime addition, to avoid precipitation of
fluoride.
(d) Chemical Feed
Installations--Fluoride feed systems shall meet the following criteria:
(i) Scales or loss-of-weight recorders for
weighing the quantity of chemicals added shall be provided;
(ii) Feed equipment shall have an accuracy to
within five (5) percent of any desired feed rate;
(iii) The point of application of
hydrofluorosilic acid, if into a pipe, shall be in the lower half of the pipe
and project upward at an angle approximately forty (40) degrees and extend into
the pipe one-third of diameter; and,
(iv) All fluoride feed lines shall be
provided with adequate antisiphon devices.
(v) All fluoride feed systems shall be
equipped with a fail-safe system to prevent the continued feed of fluoride at
times when there is no flow of water through the fluoride feed point.
(e) Protective equipment--At least
one (1) pair of rubber gloves, a respirator of a type certified by the National
Institute for Occupational Safety and Health for toxic dusts or acid gas (as
necessary), an apron or other protective clothing, and goggles or face masks
shall be provided for use by the operator. Other protective equipment may be
required, as deemed necessary by the Department.
(f) Dust Control
(i) Provisions shall be made for the transfer
of dry fluoride compounds from shipping containers to storage bins or hoppers
in such a way as to minimize the quantity of fluoride dust which may enter the
room in which the equipment is installed. The enclosure shall be provided with
an exhaust fan and dust filter to the outside atmosphere of the
building.
(ii) Provisions shall be
made for disposing of empty bags, drums and barrels in a manner which will
minimize exposure to fluoride dusts. A floor drain shall be provided to
facilitate the washing of floors.
(9) Corrosion Control--Water that is
corrosive due either to natural causes or to treatment given the water shall be
rendered non-corrosive, and nonaggressive before being pumped to the
distribution system.
(a) Alkali
Feed--Corrosive water due to natural occurrence, created by the addition of
alum or other coagulant, shall be treated by an alkali feed. Alkali feed can
consist of lime, soda ash, bicarbonate, caustic soda, or a combination of any
of the above. Lime feed systems shall include a mechanism for flushing the feed
lines, including suction and pumping equipment, if used.
(b) Phosphates--The feeding of phosphates may
be applicable for corrosion control. Phosphate chemicals shall meet the
requirements of chemical additives in R.61-58.3(E)(3)(E)(3).
(c) Carbon dioxide addition
(i) Recarbonation basin design shall provide:
(A) a total detention time of at least twenty
(20) minutes.
(B) two (2)
compartments, each with a depth of eight (8) feet, consisting of a mixing
compartment having a detention time of at least three (3) minutes, and a
reaction compartment.
(ii) Adequate precautions shall be taken to
prevent the possibility of carbon monoxide entering the plant from
recarbonation compartments.
(iii)
Provisions shall be made for draining the recarbonation basin and removing
sludge.
(d) Other
Treatment--Other treatment for controlling corrosive waters will be considered
on a case by case basis. All chemicals must meet the requirements in
R.61-58.3(E)(3)(E)(3). Any proprietary compound must receive the specific
approval of the Department before use.
(e) Control--Laboratory equipment, acceptable
to the Department, shall be provided to test for the compounds being
fed.
(10) Taste and Odor
Control--Provision shall be made for the addition of taste and odor control
chemicals at all surface water treatment plants. These chemicals shall be added
sufficiently ahead of other treatment processes to ensure adequate contact time
for an effective and economical use of the chemicals.
(a) Flexibility--Plants treating water that
is known to have taste and odor problems shall be provided with equipment that
makes several of the control processes available to allow the operator
flexibility in operation.
(b)
Chlorination--Chlorination can be used for the removal of some objectionable
odors. Adequate contact time must be provided to complete the chemical
reactions involved. Consideration shall be given to disinfection by-products if
this method is used.
(c) Chlorine
Dioxide--Chlorine dioxide may be used in the treatment of taste or odor.
Provision shall be made for the proper storing and handling of sodium chlorite,
so as to eliminate any danger of explosion. Consideration shall be given to
disinfection by-products if this method is used.
(d) Powdered Activated Carbon--Where added,
powder activated carbon feed systems shall meet the following criteria:
(i) Powdered activated carbon may be added
prior to coagulation to provide maximum contact time, but shall not be added
near the point of chlorine application.
(ii) Provisions shall be made for adequate
dust control.
(iii) Provision shall
be made for adding at least forty (40) milligrams per liter.
(e) Granular Activated Carbon
Absorption Units--Rates of flow shall be consistent with the type and intensity
of the problem. The rate used shall be supported by the results of pilot plant
studies and shall be accordance with the requirements of
R.61-58.3(D)(5)(D)(5).
(f) Copper
Sulfate and Other Copper Compounds--Continuous or periodic treatment of water
with copper compounds to kill algae or other growths shall be controlled to
prevent copper in excess of one (1) milligrams per liter as copper in the plant
effluent or distribution system. Care shall be taken in obtaining a uniform
distribution. Department approval shall be obtained prior to the use of any
such compound.
(g)
Aeration--Aeration units used for taste and odor removal shall be designed in
accordance with R.61-58.3(D)(7)(D)(7).
(h) Potassium Permanganate--The application
of potassium permanganate may be considered, provided that dosages are
determined by permanganate demand testing.
(11) Membrane Technology - All applications
for projects involving membrane technology must be preceded by an engineering
report and may require a pilot study. The engineering report must meet the
requirements of R.61-58.1.C.
(a) General
Requirements
(i) Membrane material - No
membrane material shall be used in a public water system unless the material or
product has been tested and certified as meeting the specifications of the
American National Standard Institute/National Sanitation Foundation Standard
61, Drinking Water System Components - Health Effects. This requirement shall
be met under testing conducted by a third party product certification
organization accredited for this purpose by the American National Standards
Institute.
(ii) Loading rates must
be determined by pilot testing and/or manufacturers recommendations.
(iii) Scale Inhibitors and Cleaning Solutions
- Where required, scale inhibitors and cleaning solutions must meet the
requirements of chemical additives R.61-58.3.E(3).
(b) Electrodialysis
Reversal--Electrodialysis reversal treatment shall not be used on surface water
or groundwater under the direct influence of surface water.