Current through Register Vol. 48, No. 9, September 27, 2024
(1)
Filtration--All filters treating groundwater under the direct influence of
surface water must meet the performance standards set forth in R.61-58.10(E)(E).
The application of any one type of filtration must be supported
by water quality data. Experimental treatment studies may be required to
demonstrate the applicability of the method of filtration proposed.
(a) Pressure Filters--The use of these
filters may be considered for iron and manganese removal and other
clarification processes.
(i) Rate of
Filtration--The nominal rate shall be three (3) gallons per minute per square
foot of filter area and shall not exceed five (5) gallons per minute per square
foot without adequate justification.
(ii) Details of Design--The filter design
shall address the following:
(A) Pressure
gauges on the inlet and outlet pipes of each filter shall be
provided.
(B) Provisions shall be
made for filtration and backwashing of each filter individually with an
arrangement of piping as simple as possible to accomplish these
purposes.
(C) The backwash water
collection system shall be designed to allow for adequate bed expansion without
loss of media.
(D) The underdrain
system shall efficiently collect the filtered water and shall distribute the
backwash water uniformly at a rate not less than fifteen (15) gallons per
minute per square foot of filter area.
(E) Backwash flow indicators and controls
shall be located such that they are easily readable while operating the control
valves.
(F) An air release valve on
the highest point of each filter shall be provided.
(G) An accessible manhole to facilitate
inspections and repairs (above level of media) shall be provided.
(H) A means to observe the wastewater during
backwashing shall be provided.
(I)
No unprotected cross connections shall exist.
(J) Filter material must be in accordance
with R.61-58.3(D)(5)(a)(vi)(D)(5)(a)(vi).
(K) A sufficient number of filter units so as
to ensure continuity of service with one unit temporarily removed from
operation. The facility shall be designed so that the design filtration rate is
not exceeded during backwash operation.
(L) Filter material shall have a total depth
of not less than twenty-four (24) inches and generally not more than thirty
(30) inches.
(M) Only finished
water from the treatment process shall be used to backwash the
filter(s).
(b) Gravity Filters--Gravity filters shall be
designed in accordance with applicable portions of R.61-58.3(D)(5)(D)(5).
(c) Diatomaceous earth filtration
(i) Conditions of use--Diatomaceous earth
filters are expressly excluded from consideration for bacteria removal, color
removal, or turbidity removal where either the gross quantity of turbidity is
high or the turbidity exhibits poor filterability characteristics.
(ii) Pilot plant study--Installation of a
diatomaceous earth filtration system shall be preceded by a pilot plant study
on the water to be treated.
(A) Conditions of
the study such as duration, filter rates, head loss accumulation, slurry feed
rates, turbidity removal, bacteria removal, etc., shall be approved by the
Department prior to the study.
(B)
Satisfactory pilot plant results shall be obtained prior to preparation of
final construction plans and specifications.
(C) The pilot plant study shall demonstrate
the ability of the system to meet applicable drinking water standards at all
times.
(iii) Types of
filters--Pressure or vacuum diatomaceous earth filtration units will be
considered for approval.
(iv)
Treated water storage--Treated water storage capacity in excess of normal
requirements shall be provided to allow operation of the filters at a uniform
rate during all conditions of system demand at or below the approved filtration
rate, and guarantee continuity of service during adverse raw water conditions
without by-passing the system.
(v)
Precoat Application--A uniform precoat of at least 1/16 inch shall be applied
hydraulically to each septum by introducing a slurry to the tank influent line
and employing either a filter-to-waste or recirculation system.
(vi) Body feed--A body feed system to apply
additional amounts of diatomaceous earth slurry during the filter run is
required. Continuous mixing of the body feed slurry shall be
provided.
(vii) Filtration
(A) Rate of filtration--The filtration rate
shall be controlled by a positive means and shall not exceed one and a half
(1.5) gallons per minute per square foot of filter.
(B) Head loss--The head loss shall not exceed
thirty (30) pounds per square inch for pressure diatomaceous earth filters, or
a vacuum of fifteen (15) inches of mercury for a vacuum system.
(C) Recirculation--A recirculation or holding
pump shall be employed to maintain differential pressure across the filter when
the unit is not in operation in order to prevent the filter cake from dropping
off the filter elements. A minimum recirculation rate of one tenth (0.1) gallon
per minute per square foot of filter area shall be provided.
(D) Septum or filter element--The filter
elements shall be structurally capable of withstanding maximum pressure and
velocity variations during filtration and backwash cycles, and shall be spaced
such that no less than one (1) inch is provided between elements or between any
element and a wall.
(E) Inlet
design--The filter influent shall be designed to prevent scour of the
diatomaceous earth from the filter element.
(viii) Backwash--A satisfactory method to
thoroughly remove and dispose of spent filter cake shall be provided.
(ix) Appurtenances--The following shall be
provided for every filter:
(A) sampling taps
for raw and filtered water;
(B)
loss of head or differential pressure gauge;
(C) rate-of-flow indicator, with
totalizer;
(D) a throttling valve
used to reduce rates below normal during adverse raw water conditions;
and,
(E) an evaluation of the need
for body feed, recirculation, and any other pumps, in accordance with
R.61-58.4(B)(1)(d)(B)(1)(d).
(2)
Disinfection--Disinfection may be accomplished with liquid chlorine, calcium or
sodium hypochlorite, chlorine dioxide, ozone or chloramines. Other agents will
be considered by the Department provided that reliable feed equipment is
available and test procedures for a residual are recognized, and the agent
meets the requirements of an acceptable drinking water additive. Continuous
disinfection will be required at groundwater supplies which are of questionable
sanitary quality or where any other treatment is provided. Due consideration
shall be given to the contact time of the disinfectant in water with relation
to pH, ammonia, taste-producing substances, temperature, bacterial quality, and
other pertinent factors. Consideration also must be given to the formation of
disinfection by-products.
(a)
Chlorination--Where chlorine is used the following shall apply:
(i) Type--Only vacuum type gas chlorinators
or hypochlorite feeders of the positive displacement type are
acceptable.
(ii) Capacity--The
chlorinator capacity shall be such that a free chlorine residual of at least
five (5) milligram per liter can be attained in the water after a contact time
of at least thirty (30) minutes at maximum flow rates. The equipment shall be
of such design that it will operate accurately over the desired feeding
range.
(iii) Automatic
Proportioning--Automatic proportioning chlorinators will be required where the
rate of flow or chlorine demand is not reasonably constant or where the rate of
flow of the water is not manually controlled.
(iv) Residual chlorine--Where alternate
disinfectants are used in the treatment process, the capability for the
addition of either free or combined chlorine in the finished water shall be
provided.
(b) Cross
connection protection--The chlorinator water supply piping shall be designed to
prevent contamination of the treated water supply by sources of questionable
quality.
(c) Chlorine gas -
Consideration shall be given to the location of gas chlorine facilities and the
safety of the public in the surrounding area. The Department reserves the right
to deny approval of chlorine gas on the basis of hazards to the public health..
Consideration may be given for facilities that propose the use of chlorine gas
in inhabited areas when the use of safety devices which will not allow the
release of chlorine gas (e.g. chlorine scrubbers) are provided. Only vacuum gas
chlorinator systems will be approved.
(i)
Chlorine gas feed equipment shall be enclosed and separated from other
operating areas. Concrete, wood, and other construction materials shall be
sealed to prevent the escape of chlorine gas from the chlorine building. The
chlorine room shall be provided with a shatter resistant inspection window
installed in an interior wall or an inspection window in the door. It shall be
constructed in such a manner that all openings between the chlorine room and
the remainder of the plant are sealed, and shall be provided with doors
ensuring ready means of exit and opening only to the building
exterior.
(ii) Full and empty
cylinders of chlorine gas shall be isolated from operating areas, restrained in
position to prevent upset, stored in rooms separate from ammonia storage, and
stored in areas not in direct sunlight or exposed to excessive heat.
(iii) If the chlorine room is large enough
for a person to enter, the room shall be constructed such that:
(A) It has a ventilating fan with a capacity
which provides one complete air change per minute;
(B) The ventilating fan shall be located near
the ceiling and pull suction through a duct extending to within twelve (12)
inches of the floor and discharge as far as practical from the door and air
inlet. The point of discharge shall be located so as not to contaminate air
inlets to any rooms or structures. A sealed motor or other means shall be used
to ensure the reliability of the fan;
(C) Air inlets shall be located near the
ceiling;
(D) Air inlets and outlets
shall have mechanical louvers;
(E)
Switches for fans and lights are outside of the room, at the
entrance;
(F) Vents from feeders
and storage areas discharge to the outside atmosphere, above grade and away
from inlet vent; and,
(G)
Ventilation shall not be automatically controlled.
(iv) If the room is too small for a person to
enter, the room must meet the requirements of R.61-58.2(D)(2)(c)(iii)(E) and
(F)(D)(2)(c)(iii)(E) and (F).
(v) Chlorine feed lines shall meet the
following requirements:
(A) Chlorine gas
under pressure shall be piped with schedule eighty (80) stainless steel or
schedule eighty (80) seamless carbon steel. No chlorine gas under pressure will
be piped beyond the chlorinator room.
(B) Chlorine gas under vacuum shall be piped
with schedule eighty (80) PVC or reinforced fiberglass.
(C) Chlorine solution shall be piped with
schedule eighty (80) PVC.
(vi) Heaters shall be provided to maintain
proper temperature for operation.
(vii) There shall be no equipment housed in
the chlorine room except chlorinators, chlorine cylinders, weighing scales,
heater, ventilation fan, and light(s).
(viii) Weighing scales shall be provided for
weighing cylinders, at all installations utilizing chlorine gas unless
provisions for automatic switchover of cylinders and an acceptable alternate
means to determine daily dosage are provided.
(ix) Chlorine feed systems shall be designed
to ensure continuous feed of chlorine.
(x) If a floor drain is provided, it shall be
equipped with a water seal or trap to prevent escaped gases from exiting
through the building sewer.
(xi) A
chlorine leak detection and alarm system shall be provided.
(xii) An air pack approved by the National
Institute for Occupational Safety and Health shall be available for each gas
chlorination installation.
(xiii) A
chlorine cylinder repair kit for plugging the type of chlorine cylinders used
shall be available for each gas chlorination installation.
(d) Ozone--Ozone is a suitable disinfectant
for groundwater. On-site generation facilities shall be constructed in
accordance with manufacturer's standards.
(i)
Pilot plant tests--Pilot plant tests shall be performed with the water to be
treated to establish the optimum dosage, contact time, depth of conductor and
the need for multiple application points.
(ii) Building Design--Ozone generators shall
be housed in a separate room with separate heating and ventilation. The
building layout must provide for easy access to the equipment. Ventilation
equipment shall be two (2) speed with the normal speed providing the normal
distribution of heat or air movement. The second speed must be capable of
providing a complete turnover of the air in the room every two (2) minutes to
exhaust any ozone leakage in an emergency.
(iii) Piping Materials
(A) All dry ozone gas piping shall be
mechanical jointed number 304 or 316 stainless steel or welded 304L or 316L
stainless steel. All wet ozone gas piping shall be number 316 or 316L stainless
steel. All flexible couplings shall be stainless steel.
(B) Valves shall be stainless steel face and
body.
(C) Gasket materials shall be
resistant to deterioration by the ozone.
(iv) Reinforced concrete or stainless steel
are acceptable materials. All concrete joints shall be sealed using a synthetic
rubber material resistant to deterioration by the ozone.
(e) Other disinfection agents--Any proposal
for the use of other disinfecting agents shall be approved by the Department
prior to preparation of final plans and specifications.
(f) Ammonia Gas--Consideration shall be given
to the location of ammonia gas facilities and the safety of the public in the
surrounding area. The Department reserves the right to deny approval of ammonia
gas on the basis of hazards to the public health. Only vacuum ammonia systems
will be approved.
(i) Ammonia gas feed
equipment shall be enclosed and separated from other operating areas. Concrete,
wood, and other construction materials shall be sealed to prevent the escape of
ammonia gas from the ammonia room. The ammonia room shall be provided with a
shatter resistant inspection window installed in an interior wall or an
inspection window in the door. It shall be constructed in such a manner that
all openings between the ammonia room and the remainder of the plant are
sealed, and shall be provided with doors ensuring ready means of exit and
opening only to the building exterior.
(ii) Full and empty cylinders of ammonia gas
shall be isolated from operating areas, restrained in position to prevent
upset, stored in rooms separate from chlorine storage, and stored in areas not
in direct sunlight or exposed to excessive heat.
(iii) If the ammonia room is large enough for
a person to enter, the room shall be constructed such that:
(A) It has a ventilating fan with a capacity
which provides one complete air change per minute;
(B) The ventilating fan shall be located and
pull suction near the ceiling and discharge as far as practical from the door
and air inlet. The point of discharge shall be located so as not to contaminate
air inlets to any rooms or structures. A sealed motor or other means shall be
used to ensure the reliability of the fan;
(C) Air inlets shall be located near the
floor;
(D) Air inlets and outlets
shall have mechanical louvers;
(E)
Switches for fans and lights are outside of the room, at the
entrance;
(F) Vents from feeders
and storage areas discharge to the outside atmosphere, above grade and away
from inlet vent; and,
(G)
Ventilation shall not be automatically controlled.
(iv) If the room is too small for a person to
enter, the room must meet the requirements of R.61-58.2(D)(2)(f)(iii)(E) and
(F)(D)(2)(f)(iii)(E) and (F).
(v) Ammonia feed lines shall not carry
ammonia gas beyond the ammonia room.
(vi) There shall be no equipment housed in
the ammonia room except ammoniators, ammonia cylinders, weighing scales,
heater, ventilation fan, and light(s).
(vii) Weighing scales shall be provided for
weighing cylinders, at all installations utilizing ammonia gas from cylinders.
Where bulk storage tanks are installed, they shall be equipped with a pressure
gauge.
(viii) An ammonia leak
detection and alarm system shall be provided.
(g) Chlorine Dioxide - Chlorine dioxide is a
suitable disinfectant for groundwater. Chlorine dioxide shall be generated on
site. The unit shall be flow paced and not have a holding tank for the chlorine
dioxide solution generated. All applicable EPA disinfectant by-product rules
shall be observed.
(i) Sizing of the chlorine
dioxide generator - Chlorine dioxide demand studies shall be conducted to
determine estimated feed rates and points of feed.
(ii) Building Design -
(A) Chlorine dioxide generators shall be
located in a room separate from chlorine cylinders.
(B) Number of Units: Where chlorine dioxide
is used as the primary disinfectant, at least two (2) flow pacing chlorine
dioxide generators shall be provided. The facility shall be adequately sized to
supply the maximum treatment capacity with any one generator out of service. If
chlorine dioxide is not used as a primary disinfectant (i.e. an oxidant only),
a second generator is not required.
(iii) Piping Materials -
(A) All piping from the chlorine dioxide
generator shall be schedule 80 PVC
(B) Gasket materials shall be kynar or other
compatible material.
(C) All tubing
connector fittings shall be kynar or other compatible material.
(3)
Softening--The softening process selected shall be based upon the mineral
qualities of the raw water and the desired finished water quality in
conjunction with requirements for the disposal of brine waste, the plant
location. Applicability of the process chosen shall be demonstrated. Ion
exchange units used for softening shall be designed in accordance with
R.61-58.2.D(4).
(4) Ion Exchange
Process--The total iron and manganese concentration shall not exceed three
tenth (0.30) milligrams per liter in the water as applied to the ion exchange
material. Pretreatment is required when the total iron and manganese
concentration exceeds is three tenth (0.3) milligram per liter or more.
(a) Design--The units may be of pressure or
gravity type, of either an upflow or downflow design. A manual override shall
be provided on all automatic controls.
(b) Exchange Capacity--The design capacity
for hardness removal shall not exceed twenty thousand (20,000) grains per cubic
foot when resin is regenerated with three tenth (0.3) pounds of salt per
kilograin of hardness removed.
(c)
Depth of Media--Exchange resin shall have a total depth of not less than
twenty-four (24) inches and generally not more than thirty (30) inches unless
otherwise approved by the Department.
(d) Flow Rates--The rate of softening shall
be based on an actual bench scale test of the water to be treated. The backwash
rate shall be sufficient to clean the bed. The flow rate will be dependent on
the grain size and specific gravity of the exchange resin.
(e) Bypass--A bypass may be provided around
softening units to produce a blended water of desirable hardness. Meters shall
be installed on the bypass line and on each softener unit.
(f) Additional limitations--Waters having
five (5) units or more turbidity shall not be applied directly to the cation
exchange softener. Silica gel resins shall not be used for waters having a pH
above 8.4 and shall not be used when iron is present. When the applied water
contains a chlorine residual, the cation exchange resin shall be a type that is
not damaged by residual chlorine. Phenolic resin shall not be used.
(g) Sampling Taps--Smooth-nose sampling taps
shall be provided for the collection of representative samples for both
bacteriological and chemical analyses. The taps shall be located to allow
sampling of the softener influent, the softener effluent, and the blended
water. The sampling taps for the blended water shall be at least twenty (20)
feet downstream from the point of blending. Petcocks are not acceptable as
sampling taps.
(h) Brine and Salt
Storage Tanks--Brine measuring or salt dissolving tanks and wet salt storage
facilities shall be covered and shall be constructed of corrosion-resistant
material. The make-up water inlet shall have a free fall discharge of two (2)
pipe diameters above the maximum liquid level of the unit, or shall be
protected from back-siphonage by use of a vacuum breaker. The salt shall be
supported on graduated layers of gravel under which is a suitable means of
collecting the brine. Wet salt storage basins shall be equipped with manhole or
hatchway openings having raised curbs and watertight covers having overhanging
edges. Overflows, where provided, must be angled downward, have a proper free
fall discharge and be protected with noncorrodible screens or self-closing flap
valves.
(i) Storage Capacity--Wet
salt storage basins shall have sufficient capacity to provide for at least
three (3) days of operation.
(j)
Corrosion Control--Corrosion control shall be provided.
(k) Waste Disposal--A suitable means of
handling and disposal shall be provided for brine waste designed in accordance
with
61-58.2(F).
(l) Construction Material--Pipes and contact
materials shall be corrosion resistant.
(m) Housing--Salt storage tanks and feed
equipment shall be enclosed.
(5) Aeration--Aeration treatment devices, as
described herein, may be used for oxidation, separation of gases or for taste
and odor control. A separate air quality permit for the separation of gases
from water by aeration may be necessary.
(a)
General Requirements
(i) Sample taps must be
provided following aeration equipment.
(ii) Where aeration equipment discharges
directly to the distribution system, air release valves must be
provided.
(b) Natural
Draft Aeration--Design shall provide that:
(i) Water is distributed uniformly over the
top tray;
(ii) Water is discharged
through a series of three (3) or more trays with the separation of trays not
less than twelve (12) inches;
(iii)
Trays are loaded at a rate of one (1) gallon per minute to five (5) gallons per
minutes for each square foot of total tray area;
(iv) Trays have slotted, woven wire cloth or
perforated bottoms;
(v) Perforation
are three sixteenth ( 3/16) to one-half ( 1/2) inches in diameter, spaced one
(1) to three (3) inches on centers, when perforations are used in the
distribution pan;
(vi) Construction
of durable material resistant to the aggressiveness of the water and dissolved
gases;
(vii) Protection of aerators
from loss of spray water by wind carriage by enclosure with louvers sloped to
the inside at an angle of approximately forty-five (45) degrees;
(viii) Protection from insects by number
twenty-four (24) mesh screen; and,
(ix) Aerated water receives disinfection
treatment.
(c) Forced or
Induced Draft Aeration--Devices shall be designed to:
(i) Provide an adequate countercurrent of air
through the enclosed aeration column;
(ii) Include a blower in a screened enclosure
and with a watertight motor;
(iii)
Exhaust air directly to the outside atmosphere;
(iv) Include a down-turned, number
twenty-four (24) mesh screened air outlet and inlet;
(v) Be such that air introduced in the column
shall be as free from noxious fumes, dust, and dirt as possible;
(vi) Be such that sections of the aerator can
be easily reached or removed for maintenance of the interior;
(vii) Provide loading at a rate of one (1) to
five (5) gallons per minute for each square foot of total tray area;
(viii) Ensure that the water outlet is
adequately sealed to prevent the unwarranted loss of air;
(ix) Discharge through a series of five (5)
or more trays, with separation of trays not less than six (6) inches;
(x) Provide distribution of water uniformly
over the top tray; and,
(xi) Be of
a durable corrosion resistant material.
(d) Pressure Aeration--This method may be
used for oxidation purposes if pilot plant study indicates method is
applicable. It is not acceptable for removal of dissolved gases. Filters
following pressure aeration shall have adequate exhaust devices for release of
air. Pressure aeration devices shall be designed to give thorough mixing of
compressed air with water being treated. Screened and filtered air, free of
noxious fumes, dust, dirt and other contaminants shall be provided.
(e) Other Methods of Aeration--Other methods
of aeration may be used if applicable to the treatment needs. Such methods may
include, but are not restricted to, spraying, diffused air, cascades, and
mechanical aeration. The treatment processes shall be designed to meet the
particular needs of the water to be treated and shall be subject to Department
approval.
(f) Protection from
Contamination--Aerators that are used for oxidation or removal of dissolved
gases from waters that will be given no further treatment other than
chlorination shall be protected from contamination from insects and birds by a
roof or similar structure.
(g)
Disinfection--Groundwater supplies exposed to the atmosphere by aeration must
receive chlorination as a minimum additional treatment.
(6) Iron and Manganese Control--Iron and
manganese control, as used herein, refers solely to treatment processes
designed specifically for this purpose.
(a)
Removal by Oxidation, Detention and Filtration.
(i) Oxidation--Oxidation shall be by aeration
or by chemical oxidation with chlorine, potassium permanganate, chlorine
dioxide, ozone or other oxidant approved by the Department.
(ii) A minimum detention of twenty (20)
minutes shall be provided following oxidation by aeration to ensure that the
oxidation reactions are as complete as possible. This minimum detention shall
be omitted only where a pilot plant study or an analogous system indicates no
need for detention.
(iii)
Sedimentation basins shall be provided when treating water with high iron
and/or manganese content or where chemical coagulation is used to reduce the
load on the filters.
(A) Detention
time--Sedimentation basin design considerations and calculations shall include
basin overflow rate, weir loading rate, flow through velocity and theoretical
detention time.
(B) Inlet
Devices--Inlets shall be designed to distribute water equally and at uniform
velocities. The structures shall be designed so as to dissipate inlet
velocities and provide uniform flows across the basin.
(C) Outlet Devices--Outlet devices shall be
designed to maintain velocities suitable for settling in the basin and to
minimize short circuiting.
(D)
Velocity--The velocity through settling basins shall not exceed five tenths
(0.5) of a foot per minute. The basins shall be designed to minimize short
circuiting. Baffles shall be provided, as necessary.
(E) Overflow--An overflow weir (or pipe)
shall be installed to establish water level in the basin.
(F) Sludge handling--Facilities are required
by the Department for the disposal of sludge and shall be designed in
accordance with R.61-58.2F. Provisions shall be made for the operator to
observe and sample sludge being withdrawn from the unit.
(G) Washdown Hydrants--Washdown hydrants
shall be provided and shall be equipped with backflow prevention devices
acceptable to the Department.
(iv) Filtration--Filters shall conform to
R.61-58.2(D)(1)(D)(1).
(b) Removal by Manganese Green
Sand Filtration
(i) An anthracite media cap
of at least six (6) inches shall be provided over manganese green
sand.
(ii) The filtration rate will
be dependent on the raw water quality and the type of filter used. It shall not
exceed three (3) gallons per minute per square foot.
(iii) The backwash rate shall be sufficient
to clean the bed.
(iv) Sample taps
shall be provided prior to the application of permanganate; immediately ahead
of filtration; at a point between the anthracite coal media and the manganese
treated greensand; halfway down the manganese treated greensand; and at the
effluent for each filter.
(v) A
differential pressure gauge or separate inlet and outlet pressure gauges shall
be provided to measure the loss of head through the unit.
(c) Removal by Ion Exchange--Iron removal
with sodium zeolite ion exchange units shall not be approved without a pilot
study addressing the efficiency of removal, an evaluation of the potential for
bed fouling, and consideration of the corrosiveness of the treated water. The
Ion Exchange process treatment shall be designed in accordance with
R.61-58.2(D)(4)(D)(4).
(d) Sequestration by phosphates--Where
phosphate treatment is used, sufficient disinfectant residuals shall be
maintained in the distribution system.
(i)
Phosphates shall not be applied ahead of the filters in iron and manganese
removal treatment. Where there is no removal treatment, the phosphate shall be
added prior to any disinfection.
(ii) Phosphate chemicals shall meet the
requirements of chemical additives in R.61-58.2(E)(3)(E)(3), including maximum
feed rates.
(e) Sampling
Taps--Smooth-nosed sampling taps shall be located on each source, each
treatment unit influent and each treatment unit effluent.
(7) Fluoridation--Commercial sodium fluoride,
sodium silicofluoride and hydrofluorosilic acid shall be NSF approved and shall
conform to American Waterworks Association Standards B701, B702 and B703
respectively. Fluoride chemicals shall meet the requirements of chemical
additives in R.61-58.2(E)(3)(E)(3).
The proposed method of fluoride feed shall be approved by the Department prior
to preparation of final plans and specifications.
(a) Fluoride Compound Storage--Dry chemical
storage shall be designed in accordance with R.61-58.2(E)(2)(e)(E)(2)(e).
Storage units for hydrofluorosilic acid shall be isolated from operating areas
and shall be vented to the atmosphere at a point outside any
building.
(b) Injection Point--The
fluoride compound shall not be added before ion exchange softening or before
lime addition, to avoid precipitation of fluoride.
(c) Chemical Feed Installations--Fluoride
feed systems shall meet the following criteria:
(i) Scales or loss-of-weight recorders for
weighing the quantity of chemicals added shall be provided;
(ii) Feed equipment shall have an accuracy to
within five (5) percent of any desired feed rate;
(iii) The point of application of
hydrofluorosilic acid, if into a pipe, shall be in the lower half of the pipe
and project upward at an angle approximately forty (40) degrees and extend into
the pipe one-third of diameter; and,
(iv) All fluoride feed lines shall be
provided with adequate antisiphon devices.
(v) All fluoride feed systems shall be
equipped with a fail-safe system to prevent the continued feed of fluoride at
times when there is no flow of water through the fluoride feed point.
(d) Protective equipment--At least
one (1) pair of rubber gloves, a respirator of a type certified by the National
Institute for Occupational Safety and Health for toxic dusts or acid gas (as
necessary), an apron or other protective clothing, and goggles or face masks
shall be provided for use by the operator. Other protective equipment may be
required, as deemed necessary by the Department.
(e) Dust Control
(i) Provisions shall be made for the transfer
of dry fluoride compounds from shipping containers to storage bins or hoppers
in such a way as to minimize the quantity of fluoride dust which may enter the
room in which the equipment is installed. The enclosure shall be provided with
an exhaust fan and dust filter to the outside atmosphere of the
building.
(ii) Provisions shall be
made for disposing of empty bags, drums and barrels in a manner which will
minimize exposure to fluoride dusts. A floor drain shall be provided to
facilitate the washing of floors.
(8) Corrosion Control--Water that is
corrosive due either to natural causes or to treatment given the water shall be
rendered non-corrosive, and nonaggressive before being pumped to the
distribution system.
(a) Alkali
Feed--Corrosive water due to natural occurrence, or chemical exchange process
shall be treated by an alkali feed. Alkali feed can consist of lime, soda ash,
bicarbonate, caustic soda, or a combination of any of the above. Lime feed
systems shall include a mechanism for flushing the feed lines, including
suction and pumping equipment, if used.
(b) Phosphates--The feeding of phosphates may
be applicable for corrosion control. Phosphate chemicals shall meet the
requirements of chemical additives in R.61-58.2(E)(3)(E)(3).
(c) Carbon dioxide addition
(i) Recarbonation basin design shall provide:
(A) A total detention time of at least twenty
(20) minutes.
(B) A minimum of two
(2) compartments, consisting of a mixing compartment having a detention time of
at least three (3) minutes, and a reaction compartment.
(ii) Carbon dioxide feed systems shall be
isolated from the operating area and adequate precautions shall be taken to
prevent the possibility of carbon monoxide entering the plant from
recarbonation compartments.
(iii)
Provisions shall be made for draining the recarbonation basin and removing
sludge.
(d) Other
Treatment--Other treatment for controlling corrosive waters will be considered
on a case by case basis. All chemicals must meet the requirements in
R.61-58.2(E)(3)(E)(3). Any proprietary compound must receive the specific
approval of the Department before use.
(e) Control--Laboratory equipment, acceptable
to the Department, shall be provided to test the compounds being fed.
(9) Taste and Odor Control--When
necessary, provision shall be made for the addition of taste and odor control
chemicals. These chemicals shall be added sufficiently ahead of other treatment
processes to ensure adequate contact time for an effective and economical use
of the chemicals.
(a) Flexibility--Plants
treating water that is known to have taste and odor problems shall be provided
with equipment that makes several of the control processes available to allow
the operator flexibility in operation.
(b) Chlorination--Chlorination can be used
for the removal of some objectionable odors. Adequate contact time must be
provided to complete the chemical reactions involved. Consideration shall be
given to the formation of disinfection by-products if this method is
used.
(c) Chlorine
Dioxide--Chlorine dioxide may be used in the treatment of taste or odor.
Provision shall be made for the proper storing and handling of sodium chlorite,
so as to eliminate any danger of explosion. Consideration shall be given to the
formation of disinfection by-products if this method is used.
(d) Granular Activated Carbon Absorption
Units--Rates of flow shall be consistent with the type and intensity of the
problem. The rate used shall be supported by the results of pilot plant studies
and shall be in accordance with the requirements of
R.61-58.2(D)(1)(D)(1).
(e)
Aeration--Aeration units used for taste and odor removal shall be designed in
accordance with R.61-58.2(D)(5)(D)(5).
(f) Potassium Permanganate--The application
of potassium permanganate may be considered, provided that dosages are
determined by permanganate demand testing.
(10) Membrane Technology--All applications
for projects involving membrane technology must be preceded by an engineering
report and may require a pilot study.
(a)
Reverse Osmosis
(i) Pilot Study--The pilot
study, where required, must determine or address the following items:
(A) Membrane loading rates including the most
efficient percentage of recovery;
(B) What pre-treatment is needed including
feed rates of any chemicals;
(C)
Whether by-pass blending can be used and what the blending rate will
be;
(D) The post treatment needs
including what chemical additions will be necessary to make the finished water
non-corrosive; and,
(E) The best
type of membrane for the source water application.
(ii) General Design Requirements--
(A) A flow meter with totalizer must be
provided for the permeate and the blend lines in each treatment
train.
(B) Valves must be provided
on the influent, permeate, reject, and cleaning lines for each unit.
(C) Pressure gauges must be provided on the
influent and permeate lines for each unit for measurement of head
loss.
(D) Sample taps must be
provided for the permeate, blended product, and finished water.
(E) Monitoring equipment must be provided to
measure pH, conductivity, temperature, turbidity, and any specific contaminants
for which treatment is being provided.
(F) Disposal of concentrate and cleaning
solutions must be approved by the Department.
(iii) Reverse Osmosis Membrane Material -
(A) Membrane material used in public water
systems shall be certified as meeting the specification of the American
National Standards Institute/National Sanitation Foundation Standard 61,
Drinking Water System Components - Health Effects. The certifying party shall
be accredited by the American National Standards Institute.
(B) Loading rates must be determined by pilot
testing and manufacturers recommendations.
(iv) Scale Inhibitors and Cleaning
Solutions--Scale inhibitors and cleaning solutions must meet the requirements
of chemical additives in R.61-58.2(E)(3)(E)(3).
(v) Post-Treatment--
(A) Continuous disinfection must be employed
on the permeate or on the blended effluent from the treatment units.
(B) Treatment shall be employed to render the
finished water non-corrosive.
(b) Electrodialysis Reversal--Electrodialysis
reversal treatment shall not be used on surface water or groundwater under the
direct influence of surface water unless the requirements of R.61-58.10 are otherwise met.
(i) Pretreatment--Pretreatment must be used
to protect the membrane from fouling. Media filtration used in pretreatment
must be designed in accordance with R.661-58.2(D)(1)-58.2(D)(1).
Degassification must be designed in accordance with R.61-58.2(D)(1)(D)(5).
(ii) Pilot Study--The pilot study must
determine or address the following items:
(A)
Membrane loading rates including the most efficient percentage of
recovery;
(B) What pre-treatment is
needed including feed rates of any chemicals;
(C) Whether by-pass blending can be used and
what the blending rate will be;
(D)
The post treatment needs, including what chemical additions will be necessary
to make the finished water non-corrosive; and,
(E) The best type of membrane for the source
water application.
(iii)
General Design Requirements--
(A) A gallon
meter with totalizer must be provided for the product water and the blend lines
in each treatment train.
(B) Valves
must be provided on the influent, product water, reject, and cleaning lines for
each unit.
(C) Electric volt and
current meters must be provided to measure the electric potential across each
unit.
(D) Pressure gauges must be
provided on the influent and product lines for each unit for measurement of
head loss.
(E) Sample taps must be
provided for the product, blended water, and finished water.
(F) Monitoring equipment must be provided to
measure pH, conductivity, temperature, turbidity, and any specific contaminants
for which treatment is being provided.
(G) Disposal of concentrate and cleaning
solutions must be approved by the Department.
(iv) Electrodialysis Reversal Membrane
Material -
(A) Membrane material used in
public water systems shall be certified as meeting the specification of the
American National Standard Institute/National Sanitation Foundation Standard
61, Drinking Water System Components - Health Effects. The certifying party
shall be accredited by the American National Standards Institute.
(B) Loading rates must be determined by pilot
testing and manufacturers recommendations.
(v) Scale Inhibitors and Cleaning
Solutions--Scale inhibitors and cleaning solutions must meet the requirements
of chemical additives in R.61-58.2(E)(3)(E)(3).
(vi) Post-Treatment--
(A) Continuous disinfection must be employed
on the product water or on the blended effluent from the treatment
units.
(B) Treatment shall be
employed to render the finished water non-corrosive.