(2) Monitoring Requirements for Disinfection
Byproducts.
(a) TTHMs and HAA5--At least
twenty-five (25) percent of all samples collected each quarter shall be at
locations representing maximum residence time in the distribution system.
Remaining samples shall be collected from locations representative of at least
average residence time in the distribution systems and representing the entire
distribution system, taking into account number of persons served, different
sources of water and different treatment methods. The minimum number of samples
required shall be determined based on the source of supply and the populations
served by a public water system.
(i) CWSs and
NTNCWSs that use a surface water source or a ground water source under the
influence of surface water which serve 10,000 or more persons must collect
samples as follows:
(A) Routine Monitoring--A
minimum of four (4) water samples per treatment plant per quarter in accordance
with paragraph (2)(a) of this section.
(B) Reduced Monitoring--If the system has a
source water annual average TOC level, before any treatment, less than 4.0 mg/l
and a TTHM annual average less than 0.040 mg/l and HAA5 annual average less
than 0.030 mg/l, then the minimum number of samples required may be reduced to
one (1) sample per treatment plant per quarter at a distribution system
location reflecting maximum residence time.
(C) Systems on a reduced monitoring schedule
may remain on that reduced schedule as long as the average of all samples taken
in the year (for systems which must monitor quarterly) or the result of the
sample (for systems which must monitor no more frequently than annually) is no
more than 0.060 mg/L and 0.045 mg/L for TTHMs and HAA5, respectively. Systems
that do not meet these levels must resume monitoring at the frequency
identified in paragraph (2)(a)(i)(A) of this section in the quarter immediately
following the monitoring period in which the system exceeds 0.060 mg/L and
0.045 mg/L for TTHMs and HAA5, respectively.
(D) The system may be returned to routine
monitoring at any time at the Department's discretion.
(ii) CWSs and NTNCWSs that use a surface
water source or a ground water source under the influence of surface water
which serve from 500 to 9,999 persons must collect samples as follows:
(A) Routine Monitoring--A minimum of one (1)
water sample per treatment plant per quarter at a location representing maximum
residence time in the distribution system.
(B) Reduced Monitoring--If the system has a
source water annual average TOC level, before any treatment, less than 4.0 mg/l
and a TTHM annual average less than 0.040 mg/l and HAA5 annual average less
than 0.030 mg/l, then the minimum number of samples required may be reduced to
one (1) sample per treatment plant per year during a month of warmest water
temperature at a distribution system location reflecting maximum residence
time.
(C) Systems on a reduced
monitoring schedule may remain on that reduced schedule as long as the average
of all samples taken in the year (for systems which must monitor quarterly) or
the result of the sample (for systems which must monitor no more frequently
than annually) is no more than 0.060 mg/L and 0.045 mg/L for TTHMs and HAA5,
respectively. Systems that do not meet these levels must resume monitoring at
the frequency identified in paragraph (2)(a)(ii)(A) of this section in the
quarter immediately following the monitoring period in which the system exceeds
0.060 mg/L and 0.045 mg/L for TTHMs and HAA5, respectively.
(D) The system may be returned to routine
monitoring at any time at the Department's discretion.
(iii) CWSs and NTNCWSs that use a surface
water source or a ground water source under the influence of surface water
which serve less than 500 persons must collect samples as follows:
(A) Routine Monitoring--A minimum of one
water sample per treatment plant per year during a month of warmest water
temperature at a location representing maximum residence time in the
distribution system.
(B) Reduced
Monitoring--There is no reduced monitoring allowed for these systems
(C) Increased Monitoring--If the sample (or
average of annual samples, if more than one is taken) exceeds the MCL, the
system must increase monitoring to one sample per treatment plant per quarter,
taken at a point reflecting the maximum residence time in the distribution
system, until the system meets criteria in paragraph (2)(a)(iii)(D) of this
section.
(D) Systems on increased
monitoring may return to routine monitoring if, after at least one year of
monitoring their TTHM annual average is less than or equal to 0.060 mg/L and
their HAA5 annual average is less than or equal to 0.045 mg/L.
(iv) CWSs and NTNCWSs that use
only ground water not under the influence of surface water which serve 10,000
or more persons and use a chemical disinfectant must collect samples as
follows:
(A) Routine Monitoring--A minimum of
one water sample per treatment plant per quarter at a location representing
maximum residence time in the distribution system.
(B) Reduced Monitoring--If the system has a
TTHM annual average less than 0.040 mg/l and HAA5 annual average less than
0.030 mg/l, then the minimum number of samples required may be reduced to one
(1) sample per treatment plant per year during a month of warmest water
temperature at a distribution system location reflecting maximum residence
time.
(C) Systems on a reduced
monitoring schedule may remain on that reduced schedule as long as the average
of all samples taken in the year (for systems which must monitor quarterly) or
the result of the sample (for systems which must monitor no more frequently
than annually) is no more than 0.060 mg/L and 0.045 mg/L for TTHMs and HAA5,
respectively. Systems that do not meet these levels must resume monitoring at
the frequency identified in paragraph (2)(a)(iv)(A) of this section in the
quarter immediately following the monitoring period in which the system exceeds
0.060 mg/L and 0.045 mg/L for TTHMs and HAA5, respectively.
(D) The system may be returned to routine
monitoring at any time at the Department's discretion.
(v) CWSs and NTNCWSs that use only ground
water not under the influence of surface water which serve less than 10,000
persons and use a chemical disinfectant must collect samples as follows:
(A) Routine Monitoring--A minimum of one (1)
water sample per treatment plant per year during a month of warmest water
temperature at a location representing maximum residence time in the
distribution system.
(B) Increased
Monitoring--If the sample taken, or average of annual samples if more than one
(1) sample is taken, exceeds the MCL, the system must increase monitoring to
one sample per treatment plant per quarter, taken at a location representing
the maximum residence time in the distribution system, until the system meets
the criteria in paragraph (2)(a)(v)(F) of this section for reduced
monitoring.
(C) Reduced
Monitoring--If the system has a TTHM annual average less than 0.040 mg/l and
HAA5 annual average less than 0.030 mg/l for two (2) consecutive years, or a
TTHM annual average less than 0.020 mg/l and HAA5 annual average less than
0.015 mg/l for one (1) year, then the minimum number of samples required may be
reduced to one sample per treatment plant per three (3) year cycle taken during
a month of warmest water temperature at a distribution system location
reflecting maximum residence time, with the three (3) year cycle beginning on
January 1 following the quarter in which the system qualifies for reduced
monitoring.
(D) Systems on a
reduced monitoring schedule may remain on that reduced schedule as long as the
average of all samples taken in the year is no more than 0.060 mg/L and 0.045
mg/L for TTHMs and HAA5, respectively. Systems that do not meet these levels
must resume monitoring at the frequency identified in paragraph (v)(A) of this
section in the quarter immediately following the monitoring period in which the
system exceeds 0.060 mg/L and 0.045 mg/L for TTHMs and HAA5, respectively. If
either the TTHM annual average is greater than 0.080 mg/L or the HAA5 annual
average is greater than 0.060 mg/L, the system must go to the increased
monitoring identified in paragraph (v)(B) of this section in the quarter
immediately following the monitoring period in which the system exceeds the
0.080 mg/L or 0.060 mg/L for TTHMs or HAA5 respectively.
(E) The system may be returned to routine
monitoring at any time at the Department's discretion.
(F) Systems on increased monitoring may
return to routine monitoring if, after at least one (1) year of monitoring
their TTHM annual average is less than or equal to 0.060 mg/L and their HAA5
annual average is less than or equal to 0.045 mg/L.
(vi) Monitoring requirements for source water
TOC.
In order to qualify for reduced monitoring for TTHM and HAA5
under paragraph C(2)(a)(i)(B) or C(2)(a)(ii)(B) of this section, Subpart H
systems not monitoring under the provisions of paragraph C(4) of this section
must take monthly TOC samples every 30 days at a location prior to any
treatment, beginning April 1, 2008 or earlier, if specified by the Department.
In addition to meeting other criteria for reduced monitoring in paragraph
C(2)(a)(i)(B) or C(2)(a)(ii)(B) of this section, the source water TOC running
annual average must be less than or equal to 4.0 mg/L (based on the most recent
four quarters of monitoring) on a continuing basis at each treatment plant to
reduce or remain on reduced monitoring for TTHM and HAA5. Once qualified for
reduced monitoring for TTHM and HAA5 under paragraph C(2)(a)(i)(B) or
C(2)(a)(ii)(B) of this section, a system may reduce source water TOC monitoring
to quarterly TOC samples taken every 90 days at a location prior to any
treatment.
(b)
Chlorite. Community and non-transient, non-community water systems using
chlorine dioxide, for disinfection or oxidation, must conduct monitoring for
chlorite.
(i) Routine Monitoring.
(A) Daily monitoring. Systems must take daily
samples at the entrance to the distribution system. For any daily sample that
exceeds the chlorite MCL, the system must take additional samples in the
distribution system the following day at the locations required by
R.61-58.13.C(2)(b)(ii) in addition to the sample required at the entrance to
the distribution system.
(B)
Monthly monitoring. Systems must take a three-sample set each month in the
distribution system. The system must take one sample at each of the following
locations: near the first customer, at a location representative of average
residence time, and at a location reflecting the maximum residence time in the
distribution system. Any additional routine sampling must be conducted in the
same manner (as three-sample sets, at the specified locations). The system may
use the results of additional monitoring conducted under R.61-58.13.C(2)(b)(ii)
to meet the requirement for this monitoring.
(ii) Additional monitoring. On each day
following a routine sample monitoring result that exceeds the chlorite MCL at
the entrance to the distribution system, the system is required to take three
chlorite distribution system samples at the following locations: as close to
the first customer as possible, in a location representative of average
residence time, and as close to the end of the distribution system as possible
(reflecting maximum residence time in the distribution system).
(iii) Reduced monitoring.
(A) Chlorite monitoring at the entrance to
the distribution system required by R.61-58.13.C(2)(b)(i)(A) may not be
reduced.
(B) Chlorite monitoring in
the distribution system required by R.61-58.13.C(2)(b)(i)(B) may be reduced to
one three-sample set per quarter after one year of monitoring where no
individual chlorite sample taken in the distribution system under
R.61-58.13.C(2)(b)(i)(B) has exceeded the chlorite MCL and the system has not
been required to conduct monitoring under R.61-58.13.C(2)(b)(ii). The system
may remain on the reduced monitoring schedule until either of the three
individual chlorite samples taken quarterly in the distribution system under
R.61-58.13.C(2)(b)(i)(B) exceeds the chlorite MCL or the system is required to
conduct monitoring under R.61-58.13.C(2)(b)(ii), at which time, the system must
revert to routine monitoring.
(c) Bromate
(i) Routine monitoring. Community and
non-transient, non-community systems using ozone, for disinfection or
oxidation, must take one sample per month for each treatment plant in the
system using ozone. Systems must take samples monthly at the entrance to the
distribution system while the ozonation system is operating under normal
conditions.
(ii) Reduced Monitoring
(A) Until March 31, 2009, Systems required to
analyze for bromate may reduce monitoring from monthly to once per quarter, if
the system demonstrates that the average source water bromide concentration is
less than 0.05 mg/L based upon representative monthly bromide measurements for
one year. The system may remain on reduced bromate monitoring until the running
annual average source water bromide concentration, computed quarterly, is equal
to or greater than 0.05 mg/L based upon representative monthly measurements. If
the running annual average source water bromide concentration is greater than
or equal to 0.05 mg/L, the system must resume routine monitoring required by
R.61-58.13.C(2)(c)(i).
(B)
Beginning April 1, 2009, systems may no longer use the provisions of
R.61-58.C(2)(c)(ii)(A)
to qualify for reduced monitoring. A system required to analyze for bromate may
reduce monitoring from monthly to quarterly, if the system's running annual
average bromate concentration is less than or equal to 0.0025 mg/L based on
monthly bromate measurements under R.61-58.13.C(2)(c)(i) for the most recent
four quarters, with samples analyzed using analytical methods identified in
40 CFR
141.132(b)(3)(ii)(B)
(1-04-06 edition). If a system has qualified for reduced bromate monitoring
under R.61-58.13.C(2)(c)(ii)(A), that system may remain on reduced monitoring
as long as the running annual average of quarterly bromate samples is less than
or equal to 0.0025 mg/L based on samples analyzed using analytical methods
identified in
40 CFR
141.132(b)(3)(ii)(B)
(1-04-06 edition). If the running annual average bromate concentration is
greater than 0.0025 mg/L, the system must resume routine monitoring required by
R.61-58.13.C(2)(c)(i).