(3) Disinfection profiling and benchmarking.
(a) Using data gathered from monitoring
conducted by the Department during the time period of January 1, 1999 through
March 1, 2000, any system having either a TTHM annual average greater than or
equal to 0.064 mg/L or an HAA5 annual average greater than or equal to 0.048
mg/L during this period must comply with paragraph (3)(b) of this
section.
(b) Disinfection
profiling.
(i) Any system that meets the
criteria in paragraph (3)(a) of this section must develop a disinfection
profile of its disinfection practice for a period of up to three
years.
(ii) The system must monitor
daily for a period of twelve (12) consecutive calendar months to determine the
total logs of inactivation for each day of operation, based on the
CT99.9 values in Tables 1.1--1.6, 2.1, and 3.1 of
R.61-58.10.F(2),
as appropriate, through the entire treatment plant. This system must begin this
monitoring not later than March 16, 2000. As a minimum, the system with a
single point of disinfectant application prior to entrance to the distribution
system must conduct the monitoring in paragraphs (3)(b)(ii) (A) through (D) of
this section. A system with more than one point of disinfectant application
must conduct the monitoring in paragraphs (3)(b)(i) through (iv) of this
section for each disinfection segment. The system must monitor the parameters
necessary to determine the total inactivation ratio, using EPA approved
analytical methods specified in 40 CFR 141, as follows:
(A) The temperature of the disinfected water
must be measured once per day at each residual disinfectant concentration
sampling point during peak hourly flow.
(B) If the system uses chlorine, the pH of
the disinfected water must be measured once per day at each chlorine residual
disinfectant concentration sampling point during peak hourly flow.
(C) The disinfectant contact time(s) ("T")
must be determined for each day during peak hourly flow.
(D) The residual disinfectant
concentration(s) ("C") of the water before or at the first customer and prior
to each additional point of disinfection must be measured each day during peak
hourly flow.
(iii) In
lieu of the monitoring conducted under the provisions of paragraph (b)(ii) of
this section to develop the disinfection profile, the system may elect to meet
the requirements of paragraph (b)(iii)(A) of this section. In addition to the
monitoring conducted under the provisions of paragraph (b)(ii) of this section
to develop the disinfection profile, the system may elect to meet the
requirements of paragraph (b)(iii)(B) of this section.
(A) A PWS that has three years of existing
operational data may submit those data, a profile generated using those data,
and a request that the State approve use of those data in lieu of monitoring
under the provisions of paragraph (b)(2) of this section not later than March
16, 2000. The State must determine whether these operational data are
substantially equivalent to data collected under the provisions of paragraph
(b)(ii) of this section. These data must also be representative of Giardia
lamblia inactivation through the entire treatment plant and not just of certain
treatment segments. Until the State approves this request, the system is
required to conduct monitoring under the provisions of paragraph (b)(ii) of
this section.
(B) In addition to
the disinfection profile generated under paragraph (3)(b)(ii) of this section,
a PWS that has existing operational data may use those data to develop a
disinfection profile for additional years. Such systems may use these
additional yearly disinfection profiles to develop a benchmark under the
provisions of paragraph (3)(c) of this section. The State must determine
whether these operational data are substantially equivalent to data collected
under the provisions of paragraph (3)(b)(ii) of this section. These data must
also be representative of inactivation through the entire treatment plant and
not just of certain treatment segments.
(iv) If the system uses only one point of
disinfectant application, the system may determine the total inactivation ratio
for the disinfection segment based on either of the methods in paragraph
(3)(b)(iv)(A) or (3)(b)(iv)(B) of this section.
(A) Determine one inactivation ratio
(CTcalc/CT99.9) before or at the first customer during
peak hourly flow.
(B) Determine
successive CTcalc/CT99.9 values, representing sequential
inactivation ratios, between the point of disinfectant application and a point
before or at the first customer during peak hourly flow. Under this
alternative, the system must calculate the total inactivation ratio by
determining (CTcalc/CT99.9) for each sequence and then
adding the (CTcalc/CT99.9) values together to determine
(508)Y (CTcalc/CT99.9)).
(v) If the system uses more than one point of
disinfectant application before the first customer, the system must determine
the CT value of each disinfection segment immediately prior to the next point
of disinfectant application, or for the final segment, before or at the first
customer, during peak hourly flow. The (CTcalc/CT99.9)
value of each segment and (508)D (CTcalc/CT99.9)) must
be calculated using the method in paragraph (3)(b)(iv) of this
section.
(vi) The system must
determine the total logs of inactivation by multiplying the value calculated in
paragraph (b)(iv)(A) or (B) of this section by 3.0.
(vii) A system that uses either chioramines
or ozone for primary disinfection must also calculate the logs of inactivation
for viruses using a method approved by the Department.
(viii) The system must retain disinfection
profile data in graphic form, as a spreadsheet, or in some other format
acceptable to the Department for review as part of the sanitary
survey.
(c) Disinfection
Benchmarking
(i) Any system required to
develop a disinfection profile under the provisions of paragraphs (3)(a) and
(3)(b) of this section and that decides to make a significant change to its
disinfection practice must consult with the Department prior to making such
change. Significant changes to disinfection practice are:
(A) Changes to the point of
disinfection;
(B) Changes to the
disinfectant(s) used in the treatment plant;
(C) Changes to the disinfection process;
and
(D) Any other modification
identified by the Department.
(ii) Any system that is modifying its
disinfection practice must calculate its disinfection benchmark using the
following procedure:
(A) For each year of
profiling data collected and calculated under paragraph (b) of this section,
the system must determine the lowest average monthly Giardia lamblia
inactivation in each year of profiling data. The system must determine the
average Giardia lamblia inactivation for each calendar month for each year of
profiling data by dividing the sum of daily Giardia lamblia of inactivation by
the number of values calculated for that month.
(B) The disinfection benchmark is the lowest
monthly average value (for systems with one year of profiling data) or average
of lowest monthly average values (for systems with more than one year of
profiling data) of the monthly logs of Giardia lamblia inactivation in each
year of profiling data.
(iii) A system that uses either chloramines
or ozone for primary disinfection must also calculate the disinfection
benchmark for viruses using a method approved by the Department.
(iv) The system must submit information in
paragraphs (3)(c)(iv)(A) through (C) of this section to the Department as part
of its consultation process.
(A) A
description of the proposed change:
(B) The disinfection profile for Giardia
lamblia (and, if necessary, viruses) under paragraph (b) of this section and
benchmark as required by paragraph (c)(2) of this section; and
(C) An analysis of how the proposed change
will affect the current levels of disinfection.