Current through Register Vol. 48, No. 9, September 27, 2024
503.1. Introduction.
The following standards describing tank designs intended to be
utilized for septic tanks, grease traps, or pump chambers for onsite wastewater
systems have been adopted in an effort to assure a quality product of
sufficient strength and resistance, capable of fulfilling its intended
purpose.
503.2. Design
Approval.
(1) No person shall manufacture
tanks intended to be utilized for septic tanks, grease traps, or pump chambers
for onsite wastewater systems without receiving approval from the Department.
All manufactured tanks must receive approval of design and reinforcement
methods prior to manufacturing.
(2)
Any person desiring to manufacture tanks shall submit a written application on
forms provided by the Department. Such application shall include the name and
address, the location of the facility, tank capacity, and design
information.
(3) Prior to approval,
the Department shall review the tank design, reinforcement, and manufacturing
methods to determine compliance.
(4) The Department shall approve plans for
manufactured tanks to ensure compliance with the South Carolina Minimum Design
Standards for Tank Construction.
(5) The Department shall approve plans for
fabricated tanks, other than those for precast reinforced concrete tanks, on an
individual basis. Fabricated tanks shall meet the requirements of precast
reinforced concrete tanks to provide equivalent effectiveness.
(6) The Department shall issue an approval to
the tank manufacturer if the tank design, reinforcement and manufacturing
method complies with the South Carolina Minimum Design Standards for Tank
Construction. Tank manufacturing approvals are not transferable. When a change
of ownership occurs, the new owner shall submit a written application on forms
provided by the Department.
(7) The
Department shall revoke approval to manufacture tanks for onsite wastewater
systems if the tank manufacturer fails to comply with the South Carolina
Minimum Design Standards for Tank Construction.
503.3. General.
(1) Septic tanks and grease traps shall be
manufactured as single compartment or partitioned tanks.
(2) If septic tanks and grease traps are
manufactured with a partition so that the tank contains two (2) compartments,
the inlet compartment of the tank shall contain two-thirds (2/3) of the overall
capacity, and the outlet compartment shall contain one-third (1/3) of the
overall capacity. The top of the partition shall terminate two (2) inches below
the bottom side of the tank top in order to leave space for air or gas passage
between compartments. The top and bottom halves of the partition shall be
constructed in such manner as to leave a four (4) inch water passage at the
vertical mid-point of the partition wall for the full width of the
tank.
(3) The minimum liquid
capacity requirements shall be met by the use of a single septic tank or two
(2) or more tanks installed in series. Septic tanks joined in series shall be
interconnected by an upper effluent pipe(s) with a minimum diameter of four (4)
inches and a lower sludge pipe(s) with a minimum diameter of twelve (12)
inches. The upper connection(s) shall be installed level from tank to tank, and
the lower sludge pipe connection(s) shall be installed level and shall be
placed twelve (12) inches above the bottoms of the tanks. The lower sludge pipe
connection(s) can be eliminated if the first tank in series contains at least
two-thirds (2/3) of the total required liquid capacity. There shall be no more
than two (2) inches of fall from the inlet invert of the first tank to the
outlet invert of the last tank in series.
(4) It is required that all pump chambers
function as a single compartment tank. If a two (2) compartment tank is used,
at least two (2) six (6) inch diameter holes or equivalent, must be provided in
the partition wall six (6) inches from the tank bottom.
(5) The septic tank and grease trap tank
length shall be at least two (2) but not more than three (3) times the
width.
(6) The liquid depth shall
not be less than four (4) feet.
(7)
A minimum of nine (9) inches of freeboard shall be provided in all tanks,
unless otherwise approved by the Department.
(8) Useable liquid capacity for septic tanks
or grease traps shall not be less than one thousand (1000) gallons.
(9) The pump tank shall have sufficient
capacity to accommodate all level control and alarm switches; to keep the
pump(s) totally submersed in liquid at all times and to provide the required
dosing volume and minimum pump run time. It is strongly recommended that pump
tank capacities be as large as possible in order to provide emergency storage
in the event of pump or power failure.
(10) There shall be a minimum of two (2)
openings in the tank wall located at the inlet and outlet ends or sides of the
inlet and outlet ends of the tank. The knockouts for the inlet and outlet
openings of pre-cast concrete tanks shall have a concrete thickness of not less
than one (1) inch in the tank wall. The openings shall allow for a minimum of
four (4) inch pipe or a maximum of six (6) inch pipe. No openings shall be
permitted below the tank liquid level.
(11) The inlet and outlet for septic tanks
and grease traps shall be a cast-in-place concrete tee, a polyvinyl chloride
(PVC) tee, an acrylonitrile butadiene styreneor (ABS), or a polyethylene (PE)
tee made of not less than Schedule 40 pipe or equivalent fittings and material.
The cast-in-place concrete tees shall have a minimum thickness of not less than
two (2) inches. The invert of the outlet shall be at least two (2) inches lower
in elevation than the invert of the inlet. The inlet and outlet tees shall
extend above liquid level a minimum of six (6) inches and to no less than one
(1) inch from the top of the tank to allow venting between tank compartments
and multiple tank configurations.
(12) The inlet tee for septic tanks and
grease traps shall extend sixteen (16) inches below the liquid level.
(13) The outlet tee for a septic tank shall
extend eighteen (18) inches below the liquid level and the outlet tee for a
grease trap shall extend between six (6) and twelve (12) inches above the tank
bottom.
(14) The inlet, outlet, and
wiring conduit openings of all tanks must utilize a resilient, watertight,
non-corrosive connective sleeve. The use of grout is prohibited.
(15) Access to each tank or compartment shall
be provided by an opening located above the inlet and outlet with an inside
dimension of at least eighteen (18) inches square (18 x 18) or in diameter,
with removable tank access lids.
(16) Concrete tank access lids shall be
equipped with steel lift rings at least three-eighths (3/8) inch diameter or by
an alternative method approved by the Department.
(17) Should risers or manholes be utilized to
allow access into septic tanks, grease traps, or pump chambers, the risers or
manhole covers, as applicable, shall be constructed to prevent the release of
odors, entry of vectors, and water. Grade level riser/manhole covers shall be
secured by bolts, locking mechanisms, fasteners that can only be removed by
tools, or have sufficient weight to prevent unauthorized access. The ground
shall slope away from any access extended to grade level.
(18) Risers/manholes shall be sealed to the
tank by using bituminous mastic, butyl rubber, or other pliable sealant that is
waterproof, corrosion-resistant, and approved for use in tank construction. The
sealant shall have a minimum size of one (1) inch diameter or equivalent. The
joint shall be smooth, intact, and free of all deleterious substances before
sealing.
(19) After curing, all
multi-piece tanks shall be joined and sealed at the joints by using a
bituminous mastic, butyl rubber, or other pliable sealant that is waterproof,
corrosion-resistant, and approved for use in tank construction. The sealant
shall have a minimum size of one (1) inch diameter or equivalent. The joint
shall be smooth, intact, and free of all deleterious substances before sealing.
The use of grout is prohibited.
(20) All concrete tanks must pass the ASTM
C-1227 Standard for watertight testing. The Department will choose tanks at
random for testing. Tanks will be approved for use in South Carolina after the
Department ascertains that the standard is met. After joining, tanks
manufactured in multiple sections shall be plastered along the section joints
with hydraulic cement or other waterproofing sealant. Other methods of
waterproofing tanks may be used as specifically approved in the plans and
specifications for the tank. Prior to backfilling, the Department shall make a
finding that multiple section tanks are watertight if a soil wetness condition
is present within five feet of the elevation of the top of the tank. Any tank
found to be improperly sealed, having cracks or holes, which will allow for
water infiltration or discharge of sewage from the tank bottom, walls, or top,
will not be approved for use.
(21)
Concrete tank manufacturers must have equipment and capabilities for portion
control to maintain constant mixture formulation ratios and provide for
systematic inspection of finished products to ensure compliance with the
minimum tank construction and design standards.
(22) The concrete mix used for concrete tank
components must be formulated to yield a minimum twenty-eight (28) day
compressive strength of four thousand (4,000) pounds per square inch
(psi).
(23) The aggregate size
utilized in the concrete mix shall not exceed one-third (1/3) of the wall
thickness. Suitable aggregates include sand particle sizes from a fine to
one-fourth (1/4) inch gravel or crushed stone. Granite dust or fine screenings
from a crusher operation may be used in lieu of sand.
(24) An identifying seal must be cast,
molded, or permanently affixed by an approved method from the Department on the
outlet tank wall within six (6) inches of the top. The identifying seal shall
identify the manufacturer and the liquid capacity of the tank. The concrete
tank's cast date shall be located on the identifying seal or imprinted on the
top of the tank within six (6) inches from outlet tank wall near the
identifying seal. The lettering on the identifying seal or date imprinted on
the top of the tank shall be no more than six (6) inches in height.
(25) The tank manufacturer shall guarantee
all tanks in writing for two (2) years against failure due to poor workmanship
and materials.
(26) Changes in
approved tank design, construction, and alternative reinforcing methods will
not be allowed without prior approval from the Department.
503.4. Pre-Cast Concrete Non-Fiber Reinforced
Septic Tanks and Grease Traps.
(1) The tank
walls and bottom shall be reinforced with six by six (6 x 6) inch ten (10)
gauge wire mesh.
(2) Tank tops
shall be reinforced with six by six (6 x 6) inch ten (10) gauge wire mesh, a
minimum of five (5) sections of three-eighths (3/8) inch diameter steel
reinforcing bars oriented perpendicular to the tank sidewalls beginning at the
center spaced twelve (12) inches apart and four (4) sections of three-eighths
(3/8) inch diameter steel reinforcing bars placed diagonally from the corners
to the center of the tank. The length of the perpendicular reinforcing bars
shall be of sufficient length to extend two (2) inches into the sidewall. The
length of the four (4) diagonal steel reinforcing bars shall be of sufficient
length to extend two (2) inches into the sidewall and six (6) inches beyond the
closest perpendicular steel reinforcing bar.
(3) If a septic tank or grease trap is
manufactured with a partition, the tank partition (both halves) shall be
reinforced with six by six (6 x 6) inch ten (10) gauge wire mesh. The
reinforcing wire shall be bent to form an angle of ninety (90) degrees on the
ends in order to form a leg not less than four (4) inches long. When the wire
is placed in the mold, the four-inch legs shall lay parallel with the sidewall
wire and adjacent to it.
(4) The
tank walls and bottom thickness shall be at least two and one-half (21/2)
inches, and top thickness shall be at least three (3) inches.
(5) All reinforcing wire and rods must be
covered by at least one-half (1/2) inch of concrete.
(6) An acceptable vibration method shall be
employed in the construction of the tank to prevent voids in the tank walls,
bottom, and top.
503.5.
Pre-Cast Concrete Fiber Reinforced Septic Tanks and Grease Traps.
(1) Tank tops shall be reinforced with a
minimum of five (5) sections of three-eighths (3/8) inch diameter steel
reinforcing bars oriented perpendicular to the tank sidewalls beginning at the
center spaced twelve (12) inches apart, and four (4) sections of three-eighths
(3/8) inch diameter steel reinforcing bars placed diagonally from the corners
to the center of the tank. The length of the perpendicular reinforcing bars
shall be of sufficient length to extend two (2) inches into the sidewall. The
length of the four (4) diagonal steel reinforcing bars shall be of sufficient
length to extend two (2) inches into the sidewall and six (6) inches beyond the
closest perpendicular steel reinforcing bar.
(2) Tank bottoms shall be reinforced with a
minimum of seven (7) sections of three-eighths (3/8) inch diameter steel
reinforcing bars oriented perpendicular to the tank sidewalls beginning at the
center spaced twelve (12) inches apart. The length of the perpendicular
reinforcing bars shall be of sufficient length to extend two (2) inches into
the sidewall.
(3) If a septic tank
or grease trap is manufactured with a partition, the tank partition (both
halves) shall be reinforced with six by six (6 x 6) inch ten (10) gauge wire
mesh. The reinforcing wire shall be bent to form an angle of ninety (90)
degrees on the ends in order to form a leg not less than four (4) inches long.
When the wire is placed in the mold, the four-inch legs shall lay parallel with
the sidewall wire and adjacent to it.
(4) The tank perimeter walls shall be
reinforced with three-eighths (3/8) inch diameter steel reinforcing bars
located one (1) inch from the tank's top and bottom section seams.
(5) The tank walls and bottom thickness shall
be at least two and one-half (21/2) inches, and top thickness shall be at least
three (3) inches.
(6) All
reinforcing wire and rods must be covered by at least one-half (1/2) inch of
concrete.
(7) Fiber products used
with this reinforcement design must be added during the mixing process in order
to achieve even distribution throughout the concrete mixture.
(8) Fiber length must range from at least one
(1) to no more than two (2) inches.
(9) The fiber must be specifically
manufactured for use as a concrete secondary reinforcement and be a
polypropylene fibrillated (two-dimensional fiber mesh network)
material.
(10) An acceptable
vibration method shall be employed in the construction of the tank to prevent
voids in the tank walls, bottom, and top.
503.6. Concrete Block Septic Tanks and Grease
Traps.
(1) The tank walls and partition
thickness shall be at least eight (8) inches and the top cover slabs thickness
shall be at least four (4) inches.
(2) The tank bottom shall be a single pour
concrete slab to a depth of at least four (4) inches within the first block
course.
(3) If a septic tank or
grease trap is manufactured with a partition, the tank walls and partition
shall be constructed of solid sixteen by eight by eight (16 x 8 x 8) inch
concrete blocks. The use of hollow blocks is prohibited.
(4) All joints between concrete blocks shall
be mortared using masonry cement mortar or equivalent. The joints shall have a
nominal thickness of three-eighths (3/8) inch.
(5) The upper partition wall may be supported
by the use of two by four by eight (2 x 4 x 8) inch bricks (or equivalent
support material) standing on edge located at the block seams of the upper
partition wall.
(6) The top cover
slabs shall be constructed such that the individual slabs will not exceed two
(2) feet in width and the length will be sufficient to extend to the outside
tank width with a minimum slab thickness of four (4) inches.
(7) The individual top cover slabs shall be
reinforced with a minimum of two (2) sections of three-eighths (3/8) inch
diameter steel reinforcing bars oriented perpendicular to the tank sidewalls
spaced twelve (12) inches apart from the center. The length of the
perpendicular reinforcing bars shall be of sufficient length to extend the full
length of the slab.
(8) The end
cover slabs shall be constructed such that the individual slabs will not exceed
three (3) feet in width and the length will be sufficient to extend to the
outside tank width with a minimum slab thickness of four (4) inches.
(9) The end cover slabs shall be cast to
allow access to each tank or compartment by providing an opening located above
the inlet and outlet tee with an inside dimension of eighteen (18) inches
square (18 x 18 inches) or in diameter with removable tank access
lids.
(10) The individual end cover
slabs shall be reinforced with two (2) sections of three-eighths (3/8) inch
diameter steel reinforcing bars oriented perpendicular to the tank sidewalls
spaced twelve (12) inches apart from the center and two (2) sections of
three-eighths (3/8) inch diameter steel reinforcing bars oriented perpendicular
to the tank sidewalls spaced sixteen (16) inches apart from the center. The
length of the perpendicular reinforcing bars shall be of sufficient length to
extend the full length of the slab.
(11) The top and end cover slab seams shall
be sealed to the tank walls and at all joints by using a bituminous mastic,
butyl rubber, or other pliable sealant that is waterproof, corrosion-resistant,
and approved for use in septic tanks. The sealant shall have a minimum size of
one (1) inch diameter or equivalent. The use of grout is prohibited.
(12) The tank top and end cover slabs shall
be equipped with steel lift handles at least one half (1/2) inch diameter, or
by an alternative method approved by the Department.
(13) All reinforcing rods must be covered by
at least one-half (1/2) inch of concrete.
(14) The interior of the tank (walls and
bottom) shall be plastered with a waterproofing cement compound.
(15) An acceptable vibration method shall be
employed in the construction of the tank to prevent voids in the tank access
lids, tank bottom, and top and end slabs.
503.7. Pre-Cast Concrete Non-Fiber Reinforced
Pump Chambers.
(1) The tank walls and bottom
shall be reinforced with six by six (6 x 6) inch ten (10) gauge wire
mesh.
(2) Tank tops shall be
reinforced with six by six (6 x 6) inch ten (10) gauge wire mesh, a minimum of
five (5) sections of three-eighths (3/8) inch diameter steel reinforcing bars
oriented perpendicular to the tank sidewalls beginning at the center spaced
twelve (12) inches apart, and four (4) sections of three-eighths (3/8) inch
diameter steel reinforcing bars placed diagonally from the corners to the
center of the tank. The length of the perpendicular reinforcing bars shall be
of sufficient length to extend two (2) inches into the sidewall. The length of
the four (4) diagonal steel reinforcing bars shall be of sufficient length to
extend two (2) inches into the sidewall and six (6) inches beyond the closest
perpendicular steel reinforcing bar.
(3) The tank walls and bottom thickness shall
be at least two and one-half (21/2) inches, and top thickness shall be at least
three (3) inches.
(4) All
reinforcing wire and rods must be covered by at least one-half (1/2) inch of
concrete.
(5) An acceptable
vibration method shall be employed in the construction of the tank to prevent
voids in the tank walls, bottom, and top.
503.8. Pre-Cast Concrete Fiber Reinforced
Pump Chambers.
(1) Tank tops shall be
reinforced with a minimum of five (5) sections of three-eighths (3/8) inch
diameter steel reinforcing bars oriented perpendicular to the tank sidewalls
beginning at the center spaced twelve (12) inches apart and four (4) sections
of three-eighths (3/8) inch diameter steel reinforcing bars placed diagonally
from the corners to the center of the tank. The length of the perpendicular
reinforcing bars shall be of sufficient length to extend two (2) inches into
the sidewall. The length of the four (4) diagonal steel reinforcing bars shall
be of sufficient length to extend two (2) inches into the sidewall and six (6)
inches beyond the closest perpendicular steel reinforcing bar.
(2) Tank bottoms shall be reinforced with a
minimum of seven (7) sections of three-eighths (3/8) inch diameter steel
reinforcing bars oriented perpendicular to the tank sidewalls beginning at the
center spaced twelve (12) inches apart. The length of the perpendicular
reinforcing bars shall be of sufficient length to extend two (2) inches into
the sidewall.
(3) The tank
perimeter walls shall be reinforced with three-eighths (3/8) inch diameter
steel reinforcing bars located one (1) inch from the tank's top and bottom
section seams.
(4) The tank walls
and bottom thickness shall be at least two and one-half (21/2) inches, and top
thickness shall be at least three (3) inches.
(5) All reinforcing wire and rods must be
covered by at least one-half (1/2) inch of concrete.
(6) Fiber products used with this
reinforcement design must be added during the mixing process in order to
achieve even distribution throughout the concrete mixture.
(7) Fiber length must range from at least one
(1) to no more than two (2) inches.
(8) The fiber must be specifically
manufactured for use as a concrete secondary reinforcement and be a
polypropylene fibrillated (two-dimensional fiber mesh network)
material.
(9) An acceptable
vibration method shall be employed in the construction of the tank to prevent
voids in the tank walls, bottom, and top.