Current through Register Vol. 48, No. 9, September 27, 2024
201.1. Septic
Tanks.
(1) All persons or firms manufacturing
septic tanks for use in South Carolina shall submit detailed plans for each
size tank to the Department and shall receive written approval for such tanks
prior to their installation in the state.
(2) The design and construction of each
septic tank shall be in accordance with minimum standards contained within this
regulation.
(3) No septic tank
shall be installed which has a net liquid capacity of less than one thousand
(1000) gallons. Such tanks shall be sufficient to serve dwellings of four (4)
bedrooms or less. Two hundred fifty (250) gallons additional capacity shall be
required for each bedroom over four (4).
(4) When multiple dwellings share a common
onsite wastewater system, each dwelling unit shall either have its own properly
sized septic tank or it must discharge to a larger tank(s) that provides the
combined total of the minimum septic tank capacities required for each
contributing unit. Exception may be granted when a public entity, or private
entity with financial assurances, is approved by the Department to provide
operation and maintenance of the system. In such cases, the formula in Section
201.1(5) may be considered.
(5)
Septic tanks serving establishments other than individual dwellings shall be
sized according to actual peak flow data, when available, or by estimates of
peak sewage flow, as set forth in standards established by the Department. For
those septic tanks receiving peak flows less than fifteen hundred (1500) gpd,
the net liquid capacity shall be calculated by multiplying 1.5 times the peak
flow expressed in (gpd). For those septic tanks receiving peak flows between
fifteen hundred (1500) and forty-five hundred (4500) gpd, the net liquid
capacity shall be calculated as follows:
Volume (V) = 1125 gal. plus (0.75 x Peak Flow(gpd)).
For those septic tanks receiving peak flows in excess of
forty-five hundred (4500) gpd, the net liquid capacity shall be at least equal
to the peak flow:
Volume (V) = Peak Flow (gpd)
(6) The minimum liquid capacity requirements
shall be met by the use of a single septic tank or two (2) or more tanks
installed in series. Septic tanks joined in series shall be interconnected by
an upper effluent pipe(s) with a minimum diameter of four (4) inches and a
lower sludge pipe(s) with a minimum diameter of twelve (12) inches. The upper
connection(s) shall be installed level from tank to tank, and the lower sludge
pipe connection(s) shall be installed level and shall be placed twelve (12)
inches above the bottoms of the tanks. The lower sludge pipe connection(s) can
be eliminated if the first tank in series contains at least two-thirds (2/3) of
the total required liquid capacity. There shall be no more than two (2) inches
of fall from the inlet invert of the first tank to the outlet invert of the
last tank in series.
201.2. Grease Traps.
(1) Any new food service facilities permitted
under R.61-25, Retail Food Establishments, and served by an onsite wastewater
system that is permitted after the effective date of this regulation shall be
required to have a properly sized grease trap. This requirement may also apply
to new facilities not requiring a food service permit under R.61-25. Exception
may be granted in cases where a permitted retail food service establishment
performs limited food preparation and/or cooking.
(2) Any existing food service establishment
that does not have a grease trap, but experiences an onsite wastewater
malfunction as a result of grease accumulation, shall be required to
immediately comply with all portions of Section 201 as if it were a new food
service facility.
(3) Any food
service facility requiring a grease trap shall provide two (2) separate
plumbing stub-outs, one serving the food preparation area and the other serving
the restrooms. The stub-out from the restrooms shall discharge directly into
the main building septic tank. The stub-out from the food preparation area
shall discharge directly into the grease trap with the effluent then directed
to the main building septic tank. In order to enhance grease separation while
the liquids are hot, the grease trap shall be placed as close as possible to
the source of wastewater. Garbage grinders shall not be allowed to discharge to
such systems.
(4) All grease traps
must be directly accessible from the surface and must be equipped with an
extended outlet sanitary tee terminating six (6) to twelve (12) inches above
the tank bottom. The minimum access opening shall be eighteen (18) inches in
diameter.
(5) All grease traps
serving facilities from which the peak sewage flow exceeds fifteen hundred
(1500) gpd shall either be dual chambered or individual tanks in series. If
dual chambered, both the dividing wall and the second chamber must be equipped
with a sanitary tee terminating six (6) to twelve (12) inches above the tank
bottom.
(6) It shall be the
responsibility of the owner/manager to ensure that the grease trap(s) is
cleaned by a licensed septage pumper at frequent intervals to prevent the
carryover of grease into other parts of the onsite wastewater system.
(7) Determination of Minimum Net Liquid
Capacity
(a) No grease trap used as part of an
onsite wastewater system shall have a net liquid capacity of less than one
thousand (1000) gallons. Commercial interior-type grease interceptors shall not
be utilized in lieu of a properly sized exterior grease trap.
(b) Minimum net liquid capacities of grease
traps shall be determined as follows:
NLC = GPD x LF x RF, where
NLC = Net Liquid Capacity of Grease Trap (gallons)
GPD = Total Maximum Estimated Sewage Flow (gpd)
LF = Loading Factor (the approximate portion of the total
maximum daily flow generated in food preparation areas)
0.3 - Schools and Other Institutions
0.4 - Restaurants
0.5 - Retail Food Stores
RF = Minimum Retention and Storage Factor of 2.5 for Onsite
Wastewater Systems
201.3. Other Primary Treatment Methods.
The Department, at its discretion, may consider other methods
of primary treatment requested by a Registered Professional Engineer where
conditions are warranted.