South Carolina Code of Regulations
Chapter 12 - SOUTH CAROLINA DEPARTMENT OF ARCHIVES AND HISTORY
Article 10 - MINIMUM STANDARDS FOR FACILITIES WHICH HOUSE SOUTH CAROLINA PUBLIC RECORDS
Section 12-1002 - Required Minimum Standards for All Records Storage Facilities

Universal Citation: SC Code Regs 12-1002

Current through Register Vol. 48, No. 3, March 22, 2024

Any facility or area thereof in which the records of a South Carolina public body are maintained shall meet the following minimum standards:

A. Construction:

(1) The building shall be of sound construction and shall be well-maintained, with a roof which is free of leaks.

(2) If the facility is located off-site (away from the building where the records are ordinarily maintained and used), and if part of the structure is used for other purposes, a fire wall shall separate the records area from any area which might present a hazard to the records.

B. Environment:

(1) It shall be kept clean to avoid accumulations of dust and dirt.

(2) If the facility is not climate-controlled, the records storage area shall be well-ventilated and shall not be subject to rapid and extreme fluctuations of temperature and humidity (more than plus or minus forty degrees or forty percent within twenty-four hours).

(3) It shall be free of vermin and shall have a pest control program to guard against insects and rodents.

(4) It shall be well-lighted, but records shall not be exposed to direct sunlight.

(5) Records shall be protected from the threat of damage caused by smoking, eating and drinking.

(6) Records shall be placed a minimum of three inches from the floor on sturdy, well-supported shelving units, file cabinets, or wooden pallets. Unbound inactive records shall be stored in file cabinets or in closed containers placed on shelves or pallets.

(7) Records shall not be placed in areas subject to flooding or excessive moisture, in areas with exposed water or steam pipes subject to leaking, or in areas that are adjacent to furnaces or boilers unless separated by a four-hour fire wall.

C. Security/Protection:

(1) It shall not be located in any area where the risk of natural and man-made disasters poses a significant threat to the facility and its contents. It shall be located sufficiently separate from external hazards to ensure a high degree of safety from such occurrences as fire and flood.

(2) It shall be located within the coverage area of a fire station and near a regularly patrolled police route.

(3) It shall be secured at all times, and, in the case of an off-site storage facility, if it is not normally open to the public, access shall be restricted to authorized persons.

(4) It shall have an operational fire detection mechanism. In an off-site, unstaffed facility, the fire detection mechanism shall have an external audible alarm.

(5) It shall contain an adequate supply (one or more) of well-distributed portable fire extinguishers with a minimum classification of IIA:10B:C suitable for extinguishing fires in all record materials stored.

Disclaimer: These regulations may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.