South Carolina Code of Regulations
Chapter 103 - PUBLIC SERVICE COMMISSION
Article 4 - GAS SYSTEMS
Subarticle 6 - INSPECTION AND TESTS
Section 103-475 - Test Procedures and Accuracies
Current through Register Vol. 48, No. 9, September 27, 2024
1. Pre-Installation Inspection.
2. Post-Removal Inspection and Tests. All meters and/or associated metering devices shall be tested when returned to the meter shop prior to being placed back in service.
3. Leak Tests. Every meter shall be leak tested prior to installation.
The tests of any unit of metering equipment shall consist of a comparison of its accuracy with the accuracy of a standard. The ORS will use the applicable provisions of the standards listed in 103-461 as criteria of accepted good practice in testing meters.
All meters and/or associated metering devices, when tested, shall be adjusted as closely as possible to the condition of zero error. All tolerances listed below are to be interpreted as maximum permissible variations from the condition of zero error.
FLOW |
ADJUSTED TO WITHIN |
Check Flow (20% of rated meter capacity) |
98.5%--100.5% |
Full Flow (Equal to or in excess of operating load requirement) |
98.5%--100.5% |
The accuracy as determined by averaging the results at the check and open rated flow.
The accuracy at a check flow and the accuracy at not less than open rated flow shall agree within one percent.
Accuracy at test points must be within one-half of one percent plus or minus.
All recording type meters or associated instruments which have a timing element that serves to record the time at which the measurement occurs must be adjusted as far as practicable so that the timing element is not in error by more than plus or minus five minutes in twenty-four hours.