Rhode Island Code of Regulations
Title 510 - Building Code Commission
Chapter 00 - N/A
Subchapter 00 - N/A
Part 4 - RISBC-4 Rhode Island Mechanical Code
Section 510-RICR-00-00-4.10 - Chapter 13
Universal Citation: 510 RI Code of Rules 00 00 4.10
Current through September 18, 2024
Add the following new section 1301.2.1:
1301.2.1 Maximum inside fuel oil storage. Where connected to a fuel-oil piping system, the maximum amount of fuel oil allowed inside any building shall be 1,320 gallons and the maximum amount of oil connected to any one (1) appliance shall be 660 gallons. Where the amount of fuel oil stored inside a building exceeds 1,320 gallons the storage area shall be in compliance with the R.I. Fire Prevention Code and the State Building Code.
Add the following new section 1305.8:
1305.8 Fuel Oil Supply and Vent Piping: Fill
and vent lines for above ground fuel storage tanks shall be permitted to be a
minimum of one and one quarter inch (1 1/4") in diameter for a single
storage tank up to 500 gallon capacity.
Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.