Rhode Island Code of Regulations
Title 510 - Building Code Commission
Chapter 00 - N/A
Subchapter 00 - N/A
Part 2 - RISBC-2 Rhode Island State One amp; Two-Family Dwelling Code
Section 510-RICR-00-00-2.28 - Appendices
Current through September 18, 2024
Add the Following
APPENDIX RP - RESIDENTIAL SPRINKLERS
Appendix RP is Informative only and is not part of this code
SECTION R-P2904 DWELLING UNIT FIRE SPRINKLER SYSTEMS
R-P2904.1 General.
Where installed, residential fire sprinkler systems, or portions thereof, shall be in accordance with NFPA 13D or Section P2904, which shall be considered equivalent to NFPA 13D. Section P2904 shall apply to stand-alone and multipurpose wet-pipe sprinkler systems that do not include the use of antifreeze. A multipurpose fire sprinkler system shall supply domestic water to both fire sprinklers and plumbing fixtures. A stand-alone sprinkler system shall be separate and independent from the water distribution system. A backflow flow preventer shall not be required to separate a stand-alone sprinkler system from the water distribution system.
Sprinklers when installed shall protect all areas of a dwelling unit.
Exceptions:
R-P2904.2 Sprinklers.
Sprinklers shall be new listed residential sprinklers and shall be installed in accordance with the sprinkler manufacturer's installation instructions.
Except as provided for in section P2904.2.2, sprinklers shall have a temperature rating of not less than one hundred thirty-five degrees Fahrenheit (135° F) (fiftyseven degrees Celsius (57° C)) and not more than one hundred seventy degrees Fahrenheit (170° F) (seventy-seven degrees Celsius (77° C)).
Sprinklers shall be separated from heat sources as required by the sprinkler manufacturer's installation instructions.
Sprinklers shall have an intermediate temperature rating not less than one hundred seventy-five degrees Fahrenheit (175° F) (seventy-nine degrees Celsius (79° C)) and not more than two hundred twenty-five degrees Fahrenheit (225° F) (one hundred seven degrees Celsius (107° C)) where installed in the following locations:
Piping shall be protected from freezing as required by section P2603.6. Where sprinklers are required in areas that are subject to freezing, dry-sidewall or drypendent sprinklers extending from a nonfreezing area into a freezing area shall be installed.
Sprinkler coverage requirements and sprinkler obstruction requirements shall be in accordance with sections P2904.2.4.1 and P2904.2.4.2.
Table P2904.2.2 - Locations Where Intermediate Temperature Sprinklers are Required
Heat Source |
Range of Distance from Heat Source within which Intermediate Temperature Sprinklers are Requireda, b (inches) |
Fireplace, side of open or recessed fireplace |
12 to 36 |
Fireplace, front of recessed fireplace |
36 to 60 |
Coal and wood burning stove |
12 to 42 |
Kitchen range top |
9 to 18 |
Oven |
9 to 18 |
Vent connector or chimney connector |
9 to 18 |
Heating duct, not insulated |
9 to 18 |
Hot water pipe, not insulated |
6 to 12 |
Side of ceiling or wall warm air register |
12 to 24 |
Front of wall mounted warm air register |
18 to 36 |
Water heater, furnace or boiler |
3 to 6 |
Luminaire up to 250 watts |
3 to 6 |
Luminaire 250 watts up to 499 watts |
6 to 12 |
For SI: 1 inch = 25.4 mm |
|
aSprinklers shall not be located at distances less than the minimum table distance unless the sprinkler listing allows a lesser distance. bDistances shall be measured in a straight line from the nearest edge of the heat source to the nearest edge of the sprinkler |
The area of coverage of a single sprinkler shall not exceed four hundred (400) square feet (37 m2) and shall be based on the sprinkler listing and the sprinkler manufacturer's installation instructions.
Sprinkler discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Sprinkler separation from obstructions shall comply with the minimum distances specified in the sprinkler manufacturer's instructions.
Pendent sprinklers within three feet (3') (915 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.
Sidewall sprinklers within five feet (5') (1524 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.
The solvent cementing of threaded adapter fittings shall be completed and threaded adapters for sprinklers shall be verified as being clear of excess cement prior to the installation of sprinklers on systems assembled with solvent cement.
Painting, caulking or modifying of sprinklers shall be prohibited. Sprinklers that have been painted, caulked, modified or damaged shall be replaced with new sprinklers.
R-P2904.3 Sprinkler piping system.
Sprinkler piping shall be supported in accordance with the requirements for cold water distribution piping. Sprinkler piping shall comply with all requirements for cold water distribution piping. For multipurpose piping systems, the sprinkler piping shall connect to and be a part of the cold-water distribution piping system.
Nonmetallic pipe and tubing, such as CPVC and PEX, shall be listed for use in residential fire sprinkler systems.
Nonmetallic pipe and tubing systems shall be protected from exposure to the living space by a layer of not less than three eighths of one inch (3/8") (9.5 mm) thick gypsum wallboard, one half of one inch (1/2") inch-thick plywood (13 mm), or other material having a fifteen (15) minute fire rating.
Exceptions:
With the exception of shutoff valves for the entire water distribution system, valves shall not be installed in any location where the valve would isolate piping serving one or more sprinklers.
Piping beyond the service valve located at the beginning of the water distribution system shall not serve more than one (1) dwelling.
A means to drain the sprinkler system shall be provided on the system side of the water distribution shutoff valve.
R-P2904.4 Determining system design flow.
The flow for sizing the sprinkler piping system shall be based on the flow rating of each sprinkler in accordance with section P2904.4.1 and the calculation in accordance with section P2904.4.2.
The minimum required flow for each sprinkler shall be determined using the sprinkler manufacturer's published data for the specific sprinkler model based on all of the following:
The design flow rate for the system shall be based on the following:
R-P2904.5 Water supply.
The water supply shall provide not less than the required design flow rate for sprinklers in accordance with section P2904.4.2 at a pressure not less than that used to comply with section P2904.6.
Where a dwelling unit water supply is from a tank system, a private well system or a combination of these, the available water supply shall be based on the minimum pressure control setting for the pump.
The water supply shall have the capacity to provide the required design flow rate for sprinklers for a period of time as follows:
R-P2904.6 Pipe sizing.
The piping to sprinklers shall be sized for the flow required by section P2904.4.2. The flow required to supply the plumbing fixtures shall not be required to be added to the sprinkler design flow.
Pipe shall be sized by determining the available pressure to offset friction loss in piping and identifying a piping material, diameter and length using the equation in section P2904.6.2.1 and the procedure in section P2904.6.2.2.
The pressure available to offset friction loss in the interior piping system (Pt) shall be determined in accordance with the Equation 29-1.
Pt = Psup-PLsvc-PLm-PLd-PLe-Psp (Equation 29-1) where: Pt = Pressure used in applying Tables P2904.6.2(4) through P2904.6.2(9).
Psup = Pressure available from the water supply source.
PLsvc = Pressure loss in the water-service pipe.
PLm = Pressure loss in the water meter.
PLd = Pressure loss from devices other than the water meter.
PLe = Pressure loss associated with changes in elevation.
Psp = Maximum pressure required by a sprinkler.
Determination of the required size for water distribution piping shall be in accordance with the following procedure:
Step 1 - Determine Psu Obtain the static supply pressure that will be available from the water main from the water purveyor, or for an individual source, the available supply pressure shall be in accordance with section P2904.5.1.
Step 2 - Determine PLsvc Use Table P2904.6.2(1) to determine the pressure loss in the water service pipe based on the selected size of the water service.
Step 3 - Determine PLm Use Table P2904.6.2(2) to determine the pressure loss from the water meter, based on the selected water meter size.
Step 4 - Determine PLd Determine the pressure loss from devices other than the water meter installed in the piping system supplying sprinklers, such as pressure-reducing valves, backflow preventers, water softeners or water filters. Device pressure losses shall be based on the device manufacturer's specifications. The flow rate used to determine pressure loss shall be the rate from section P2904.4.2, except that five (5) gpm (0.3 L/S) shall be added where the device is installed in a water-service pipe that supplies more than one (1) dwelling.
As alternative to deducting pressure loss for a device, an automatic bypass valve shall be installed to divert flow around the device when a sprinkler activates.
Step 5 - Determine PLe Use Table P2904.6.2(3) to determine the pressure loss associated with changes in elevation. The elevation used in applying the table shall be the difference between the elevation where the water source pressure was measured and the elevation of the highest sprinkler.
Step 6 - Determine Psp Determine the maximum pressure required by any individual sprinkler based on the flow rate from section P2904.4.1. The required pressure is provided in the sprinkler manufacturer's published data for the specific sprinkler model based on the selected flow rate.
Step 7 - Calculate Pt Using Equation 29-1, calculate the pressure available to offset friction loss in water-distribution piping between the service valve and the sprinklers.
Step 8 - Determine the maximum allowable pipe length Use Tables P2904.6.2(4) through P2904.6.2(9) to select a material and size for water distribution piping. The piping material and size shall be acceptable if the developed length of pipe between the service valve and the most remote sprinkler does not exceed the maximum allowable length specified by the applicable table. Interpolation of Pt between the tabular values shall be permitted. The maximum allowable length of piping in Tables P2904.6.2(4) through P2904.6.2(9) incorporates an adjustment for pipe fittings, and no additional consideration of friction losses associated with pipe fittings shall be required.
R-P2904.7 Instructions and signs.
An owner's manual for the fire sprinkler system shall be provided to the owner. A sign or valve tag shall be installed at the main shutoff valve to the water distribution system stating the following: "Warning, the water system for this home supplies fire sprinklers that require certain flows and pressures to fight a fire. Devices that restrict the flow or decrease the pressure or automatically shut off the water to the fire sprinkler system, such as water softeners, filtration systems and automatic shutoff valves, shall not be added to this system without a review of the fire sprinkler system by a fire protection specialist. Do not remove this sign."
R-P2904.8 Inspections.
The water distribution system shall be inspected in accordance with sections P2904.8.1 and P2904.8.2.
The following items shall be verified prior to the concealment of any sprinkler system piping:
The following items shall be verified upon completion of the system:
Table P2904.6.2(1) - Water Service Pressure Loss (PLsvc)a,b
Flow Ratec (gpm ) |
3/4 INCH WATER SERVICE PRESSURE LOSS (psi) |
1 INCH WATER SERVICE PRESSURE LOSS (psi) |
1 1/4 INCH WATER SERVICE PRESSURE LOSS (psi) |
|||||||||
Length of water service pipe (feet) |
Length of water service pipe (feet) |
Length of water service pipe (feet) |
||||||||||
40 or less |
41 to 75 |
76 to 100 |
101 to 150 |
40 or less |
41 to 75 |
76 to 100 |
101 to 150 |
40 or les s |
41 to 75 |
76 to 100 |
101 to 150 |
|
8 |
5.1 |
8.7 |
11.8 |
17.4 |
1.5 |
2.5 |
3.4 |
5.1 |
0.6 |
1.0 |
1.3 |
1.9 |
10 |
7.7 |
13.1 |
17.8 |
26.3 |
2.3 |
3.8 |
5.2 |
7.7 |
0.8 |
1.4 |
2.0 |
2.9 |
12 |
10.8 |
18.4 |
24.9 |
NP |
3.2 |
5.4 |
7.3 |
10.7 |
1.2 |
2.0 |
2.7 |
4.0 |
14 |
14.4 |
24.5 |
NP |
NP |
4.2 |
7.1 |
9.6 |
14.3 |
1.6 |
2.7 |
3.6 |
5.4 |
16 |
18.4 |
NP |
NP |
NP |
5.4 |
9.1 |
12.4 |
18.3 |
2.0 |
3.4 |
4.7 |
6.9 |
18 |
22.9 |
NP |
NP |
NP |
6.7 |
11.4 |
15.4 |
22.7 |
2.5 |
4.3 |
5.8 |
8.6 |
20 |
27.8 |
NP |
NP |
NP |
8.1 |
13.8 |
18.7 |
27.6 |
3.1 |
5.2 |
7.0 |
10.4 |
22 |
NP |
NP |
NP |
NP |
9.7 |
16.5 |
22.3 |
NP |
3.7 |
6.2 |
8.4 |
12.4 |
24 |
NP |
NP |
NP |
NP |
11.4 |
19.3 |
26.2 |
NP |
4.3 |
7.3 |
9.9 |
14.6 |
26 |
NP |
NP |
NP |
NP |
13.2 |
22.4 |
NP |
NP |
5.0 |
8.5 |
11.4 |
16.9 |
28 |
NP |
NP |
NP |
NP |
15.1 |
25.7 |
NP |
NP |
5.7 |
9.7 |
13.1 |
19.4 |
30 |
NP |
NP |
NP |
NP |
17.2 |
NP |
NP |
NP |
6.5 |
11.0 |
14.9 |
22.0 |
32 |
NP |
NP |
NP |
NP |
19.4 |
NP |
NP |
NP |
7.3 |
12.4 |
16.8 |
24.8 |
34 |
NP |
NP |
NP |
NP |
21.7 |
NP |
NP |
NP |
8.2 |
13.9 |
18.8 |
NP |
36 |
NP |
NP |
NP |
NP |
24.1 |
NP |
NP |
NP |
9.1 |
15.4 |
20.9 |
NP |
For SI: one inch (1") = 25.4 mm, one foot (1') = 304.8 mm, one (1) gallon per minute = 0.053 L/s, one (1) pound per square inch = 6.895 kPa.
NP - Not permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in Table P2905.4 and are based on an SDR of 11 and a Hazen Williams C Factor of one hundred fifty (150).
b. Values include the following length allowances for fittings: twenty-five percent (25%) length increase for actual lengths up to one hundred feet (100') and fifteen percent (15%) length increase for actual lengths over one hundred feet (100').
c. Flow rate from section P2904.4.2. Add five (5) gpm to the flow rate required by section P2904.4.2 where the water-service pipe supplies more than one (1) dwelling.
Table P2904.6.2(2) - Minimum Water Meter Pressure Loss (PLm)a
FLOW RATE (gallons per minute, gpm)b |
5/8-INCH METER PRESSURE LOSS (pounds per square inch, psi) |
3/4-INCH METER PRESSURE LESS (pounds per square inch, psi) |
1-INCH METER PRESSURE LOSS (pounds per square inch, psi) |
8 |
2 |
1 |
1 |
10 |
3 |
1 |
1 |
12 |
4 |
1 |
1 |
14 |
5 |
2 |
1 |
16 |
7 |
3 |
1 |
18 |
9 |
4 |
1 |
20 |
11 |
4 |
2 |
22 |
NP |
5 |
2 |
24 |
NP |
5 |
2 |
26 |
NP |
6 |
2 |
28 |
NP |
6 |
2 |
30 |
NP |
7 |
2 |
32 |
NP |
7 |
3 |
34 |
NP |
8 |
3 |
36 |
NP |
8 |
3 |
For SI: one inch (1") = 25.4 mm, one (1) pound per square inch = 6.896 kPa, one (1) gallon per minute = 0.063 L/s.
NP - Not permitted unless the actual water meter pressure loss is known.
a. Table 2904.6.2(2) establishes conservative values for water meter pressure loss or installations where the water meter loss is unknown. Where the actual water meter pressure loss is known, Pm shall be the actual loss.
b. Flow rate from section P2904.4.2. Add five (5) gpm to the flow rate required by section P2904.4.2 where the water-service pipe supplies more than one (1) dwelling.
Table P2904.6.2(3) - Elevation Loss (PLe)
ELEVATION (feet) |
PRESSURE LOSS (psi) |
5 |
2.2 |
10 |
4.4 |
15 |
6.5 |
20 |
8.7 |
25 |
10.9 |
30 |
13 |
35 |
15.2 |
40 |
17.4 |
For SI: one foot (1') = 304.8 mm, one (1) pound per square inch = 6.895 kPa.
Table P2904.6.2(4) - Allowable Pipe Length for three quarter (3/4) Inch Type M Copper
Water Tubing
SPRINKLE R FLOW RATEa (gpm) |
WATER DISTRIBUTION SIZE (inch) |
Available Pressure - Pt (psi) |
|||||||||
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
||
Allowable length of pipe from service valve to farthest sprinkler (feet) |
|||||||||||
8 |
3/4 |
217 |
289 |
361 |
434 |
506 |
578 |
65 0 |
723 |
795 |
867 |
9 |
3/4 |
174 |
232 |
291 |
349 |
407 |
465 |
523 |
581 |
639 |
697 |
10 |
3/4 |
143 |
191 |
239 |
287 |
335 |
383 |
430 |
478 |
526 |
574 |
11 |
3/4 |
120 |
160 |
220 |
241 |
281 |
321 |
361 |
401 |
441 |
481 |
12 |
3/4 |
102 |
137 |
171 |
205 |
239 |
273 |
307 |
241 |
375 |
410 |
13 |
3/4 |
88 |
118 |
147 |
177 |
206 |
235 |
265 |
294 |
324 |
353 |
14 |
3/4 |
77 |
103 |
128 |
154 |
18 0 |
205 |
231 |
257 |
282 |
308 |
15 |
3/4 |
68 |
90 |
113 |
136 |
158 |
181 |
203 |
226 |
248 |
271 |
16 |
3/4 |
60 |
80 |
100 |
120 |
14 0 |
16 0 |
18 0 |
20 0 |
220 |
241 |
17 |
3/4 |
54 |
72 |
90 |
108 |
125 |
143 |
161 |
179 |
197 |
215 |
18 |
3/4 |
48 |
64 |
81 |
97 |
113 |
129 |
145 |
161 |
177 |
193 |
19 |
3/4 |
44 |
58 |
73 |
88 |
102 |
117 |
131 |
146 |
160 |
175 |
20 |
3/4 |
40 |
53 |
66 |
80 |
93 |
106 |
119 |
133 |
146 |
159 |
21 |
3/4 |
36 |
48 |
61 |
73 |
85 |
97 |
109 |
121 |
133 |
145 |
22 |
3/4 |
33 |
44 |
56 |
67 |
78 |
89 |
10 0 |
111 |
122 |
133 |
23 |
3/4 |
31 |
41 |
51 |
61 |
72 |
82 |
92 |
102 |
113 |
123 |
24 |
3/4 |
28 |
38 |
47 |
57 |
66 |
76 |
85 |
95 |
104 |
114 |
25 |
3/4 |
26 |
35 |
44 |
53 |
61 |
70 |
79 |
88 |
97 |
105 |
26 |
3/4 |
24 |
33 |
41 |
49 |
57 |
65 |
73 |
82 |
90 |
98 |
27 |
3/4 |
23 |
30 |
38 |
46 |
53 |
61 |
69 |
76 |
84 |
91 |
28 |
3/4 |
21 |
28 |
36 |
43 |
50 |
57 |
64 |
71 |
78 |
85 |
29 |
3/4 |
20 |
27 |
33 |
40 |
47 |
53 |
60 |
67 |
73 |
80 |
30 |
3/4 |
19 |
25 |
31 |
38 |
44 |
50 |
56 |
63 |
69 |
75 |
31 |
3/4 |
18 |
24 |
29 |
35 |
41 |
47 |
53 |
59 |
65 |
71 |
32 |
3/4 |
17 |
22 |
28 |
33 |
39 |
44 |
50 |
56 |
61 |
67 |
33 |
3/4 |
16 |
21 |
26 |
32 |
37 |
42 |
47 |
53 |
58 |
63 |
34 |
3/4 |
NP |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
35 |
3/4 |
NP |
19 |
24 |
28 |
33 |
38 |
42 |
47 |
52 |
57 |
36 |
3/4 |
NP |
18 |
22 |
27 |
31 |
36 |
40 |
45 |
49 |
54 |
37 |
3/4 |
NP |
17 |
21 |
26 |
30 |
34 |
38 |
43 |
47 |
51 |
38 |
3/4 |
NP |
16 |
20 |
24 |
28 |
32 |
36 |
40 |
45 |
49 |
39 |
3/4 |
NP |
15 |
19 |
23 |
27 |
31 |
35 |
39 |
42 |
46 |
40 |
3/4 |
NP |
NP |
18 |
22 |
26 |
29 |
33 |
37 |
40 |
44 |
For SI: one inch (1") = 25.4 mm, one foot (1') = 304.8 mm, one (1) pound per square inch = 6.895 kPa, one (1) gallon per minute - 0.963 L/s.
NP - Not permitted
a. Flow rate from section P2904.4.2.
Table P2904.6.2(5) - Allowable Pipe Length for 1-inch Type M Copper Water Tubing SPRINKLER FLOW RATEa (gpm) |
WATER DISTRIBUTION SIZE (inch) |
Available Pressure - Pt (psi) |
|||||||||
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
||
Allowable length of pipe from service valve to farthest sprinkler (feet) |
|||||||||||
8 |
1 |
806 |
1075 |
1343 |
1612 |
1881 |
2149 |
2418 |
2687 |
2955 |
3224 |
9 |
1 |
648 |
864 |
1080 |
1296 |
1512 |
1728 |
1945 |
2161 |
2377 |
2593 |
10 |
1 |
533 |
711 |
889 |
1067 |
1245 |
1422 |
1600 |
1778 |
1956 |
2134 |
11 |
1 |
447 |
586 |
745 |
894 |
1043 |
1192 |
1341 |
1491 |
1640 |
1789 |
12 |
1 |
381 |
508 |
634 |
761 |
888 |
1015 |
1142 |
1269 |
1396 |
1523 |
13 |
1 |
328 |
438 |
547 |
657 |
766 |
875 |
985 |
1094 |
1204 |
1313 |
14 |
1 |
286 |
382 |
477 |
572 |
668 |
763 |
859 |
954 |
1049 |
1145 |
15 |
1 |
252 |
336 |
420 |
504 |
588 |
672 |
756 |
840 |
924 |
1008 |
16 |
1 |
224 |
298 |
373 |
447 |
522 |
596 |
671 |
745 |
820 |
894 |
17 |
1 |
200 |
266 |
333 |
400 |
466 |
533 |
600 |
666 |
733 |
799 |
18 |
1 |
180 |
240 |
300 |
360 |
420 |
479 |
539 |
599 |
659 |
719 |
19 |
1 |
163 |
217 |
271 |
325 |
380 |
434 |
488 |
542 |
597 |
651 |
20 |
1 |
148 |
197 |
247 |
296 |
345 |
395 |
444 |
493 |
543 |
592 |
21 |
1 |
135 |
180 |
225 |
270 |
315 |
360 |
406 |
451 |
496 |
541 |
22 |
1 |
124 |
165 |
207 |
248 |
289 |
331 |
372 |
413 |
455 |
496 |
23 |
1 |
114 |
152 |
190 |
228 |
267 |
305 |
343 |
381 |
419 |
457 |
24 |
1 |
106 |
141 |
176 |
211 |
246 |
282 |
317 |
352 |
387 |
422 |
25 |
1 |
98 |
131 |
163 |
196 |
228 |
261 |
294 |
326 |
359 |
392 |
26 |
1 |
91 |
121 |
152 |
182 |
212 |
243 |
273 |
304 |
334 |
364 |
27 |
1 |
85 |
113 |
142 |
170 |
198 |
226 |
255 |
283 |
311 |
340 |
28 |
1 |
79 |
106 |
132 |
159 |
185 |
212 |
238 |
265 |
291 |
318 |
29 |
1 |
74 |
99 |
124 |
149 |
174 |
198 |
223 |
248 |
273 |
298 |
30 |
1 |
70 |
92 |
116 |
140 |
163 |
186 |
210 |
233 |
256 |
280 |
31 |
1 |
66 |
88 |
110 |
132 |
153 |
175 |
197 |
219 |
241 |
263 |
32 |
1 |
62 |
83 |
103 |
124 |
145 |
165 |
186 |
207 |
227 |
248 |
33 |
1 |
59 |
78 |
98 |
117 |
137 |
156 |
176 |
195 |
215 |
234 |
34 |
1 |
55 |
74 |
92 |
111 |
129 |
148 |
166 |
185 |
203 |
222 |
35 |
1 |
53 |
70 |
88 |
105 |
123 |
140 |
158 |
175 |
193 |
210 |
36 |
1 |
50 |
66 |
83 |
100 |
116 |
133 |
150 |
166 |
183 |
199 |
37 |
1 |
47 |
63 |
79 |
95 |
111 |
126 |
142 |
158 |
174 |
190 |
38 |
1 |
45 |
60 |
75 |
90 |
105 |
120 |
135 |
150 |
165 |
181 |
39 |
1 |
43 |
57 |
72 |
86 |
100 |
115 |
129 |
143 |
158 |
172 |
40 |
1 |
41 |
55 |
68 |
82 |
96 |
109 |
123 |
137 |
150 |
164 |
For SI: one inch (1") = 25.4 mm, one foot (1') = 304.8 mm, one (1) pound per square inch = 6.895 kPa, one (1) gallon per minute - 0.963 L/s.
a. Flow rate from Section P2904.4.2.
Table P2904.6.2(6) - Allowable Pipe Length for 3/4-inch CPVC Pipe
SPRINKLER FLOW RATEa (gpm) |
WATER DISTRIBUTION SIZE (inch) |
Available Pressure - Pt (psi) |
|||||||||
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
||
Allowable length of pipe from service valve to farthest sprinkler (feet) |
|||||||||||
8 |
3/4 |
348 |
465 |
581 |
697 |
813 |
929 |
1045 |
1161 |
1278 |
1394 |
9 |
3/4 |
280 |
374 |
467 |
560 |
654 |
747 |
841 |
934 |
1027 |
1121 |
10 |
3/4 |
231 |
307 |
384 |
461 |
538 |
615 |
692 |
769 |
845 |
922 |
11 |
3/4 |
193 |
258 |
322 |
387 |
451 |
515 |
580 |
644 |
709 |
773 |
12 |
3/4 |
165 |
219 |
274 |
329 |
384 |
439 |
494 |
549 |
603 |
658 |
13 |
3/4 |
142 |
189 |
237 |
284 |
331 |
378 |
426 |
473 |
520 |
568 |
14 |
3/4 |
124 |
165 |
206 |
247 |
289 |
330 |
371 |
412 |
454 |
495 |
15 |
3/4 |
109 |
145 |
182 |
218 |
254 |
290 |
327 |
363 |
399 |
436 |
16 |
3/4 |
97 |
129 |
161 |
193 |
226 |
258 |
290 |
322 |
354 |
387 |
17 |
3/4 |
86 |
115 |
144 |
173 |
202 |
230 |
259 |
288 |
317 |
346 |
18 |
3/4 |
78 |
104 |
130 |
155 |
181 |
207 |
233 |
259 |
285 |
311 |
19 |
3/4 |
70 |
94 |
117 |
141 |
164 |
188 |
211 |
234 |
258 |
281 |
20 |
3/4 |
64 |
85 |
107 |
128 |
149 |
171 |
192 |
213 |
235 |
256 |
21 |
3/4 |
58 |
78 |
97 |
117 |
136 |
156 |
175 |
195 |
214 |
234 |
22 |
3/4 |
54 |
71 |
89 |
107 |
125 |
143 |
161 |
179 |
197 |
214 |
23 |
3/4 |
49 |
66 |
82 |
99 |
115 |
132 |
148 |
165 |
181 |
198 |
24 |
3/4 |
46 |
61 |
76 |
91 |
107 |
122 |
137 |
152 |
167 |
183 |
25 |
3/4 |
42 |
56 |
71 |
85 |
99 |
113 |
127 |
141 |
155 |
169 |
26 |
3/4 |
39 |
52 |
66 |
79 |
92 |
105 |
118 |
131 |
144 |
157 |
27 |
3/4 |
37 |
49 |
61 |
73 |
86 |
98 |
110 |
122 |
135 |
147 |
28 |
3/4 |
34 |
46 |
57 |
69 |
80 |
92 |
103 |
114 |
126 |
137 |
29 |
3/4 |
32 |
43 |
54 |
64 |
75 |
86 |
96 |
107 |
118 |
129 |
30 |
3/4 |
30 |
40 |
50 |
60 |
70 |
81 |
91 |
101 |
111 |
121 |
31 |
3/4 |
28 |
38 |
47 |
57 |
66 |
76 |
85 |
95 |
104 |
114 |
32 |
3/4 |
27 |
36 |
45 |
54 |
63 |
71 |
80 |
89 |
98 |
107 |
33 |
3/4 |
25 |
34 |
42 |
51 |
59 |
68 |
76 |
84 |
93 |
101 |
34 |
3/4 |
24 |
32 |
40 |
48 |
56 |
64 |
72 |
80 |
88 |
96 |
35 |
3/4 |
23 |
30 |
38 |
45 |
53 |
61 |
68 |
76 |
83 |
91 |
36 |
3/4 |
22 |
29 |
36 |
43 |
50 |
57 |
65 |
72 |
79 |
86 |
37 |
3/4 |
20 |
27 |
34 |
41 |
48 |
55 |
61 |
68 |
75 |
82 |
38 |
3/4 |
20 |
26 |
33 |
39 |
46 |
52 |
59 |
65 |
72 |
78 |
39 |
3/4 |
19 |
25 |
31 |
37 |
43 |
50 |
56 |
62 |
68 |
74 |
40 |
3/4 |
18 |
24 |
30 |
35 |
41 |
47 |
53 |
59 |
65 |
71 |
For SI: one inch (1") = 25.4 mm, one foot (1') - 304.8 mm, one (1) pound per square inch - 6.895 kPa, one (1) gallon per minute = 0.0963 L/s.
a. Flow rate from Section P2904.4.2.
Table P2904.6.2(7) - Allowable Pipe Length for 1-inch CPVC Pipe
SPRINKLER FLOW RATEa (gpm) |
WATER DISTRIBUTION SIZE (inch) |
Available Pressure - Pt (psi) |
|||||||||
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
||
Allowable length of pipe from service valve to farthest sprinkler (feet) |
|||||||||||
8 |
1 |
1049 |
1398 |
1748 |
2098 |
2447 |
2797 |
3146 |
3496 |
3845 |
4195 |
9 |
1 |
843 |
1125 |
1406 |
1687 |
1968 |
2249 |
2530 |
2811 |
3093 |
3374 |
10 |
1 |
694 |
925 |
1157 |
1388 |
1619 |
1851 |
2082 |
2314 |
2545 |
2776 |
11 |
1 |
582 |
776 |
970 |
1164 |
1358 |
1552 |
1746 |
1940 |
2133 |
2327 |
12 |
1 |
495 |
660 |
826 |
991 |
1156 |
1321 |
1486 |
1651 |
1816 |
1981 |
13 |
1 |
427 |
570 |
712 |
854 |
997 |
1139 |
1281 |
1424 |
1566 |
1709 |
14 |
1 |
372 |
497 |
621 |
745 |
869 |
993 |
1117 |
1241 |
1366 |
1490 |
15 |
1 |
328 |
437 |
546 |
656 |
765 |
874 |
983 |
1093 |
1202 |
1311 |
16 |
1 |
291 |
388 |
485 |
582 |
679 |
776 |
873 |
970 |
1067 |
1164 |
17 |
1 |
260 |
347 |
433 |
520 |
607 |
693 |
780 |
867 |
954 |
1040 |
18 |
1 |
234 |
312 |
390 |
468 |
546 |
624 |
702 |
780 |
858 |
936 |
19 |
1 |
212 |
282 |
353 |
423 |
494 |
565 |
635 |
706 |
776 |
847 |
20 |
1 |
193 |
247 |
321 |
385 |
449 |
513 |
578 |
642 |
706 |
770 |
21 |
1 |
176 |
235 |
293 |
352 |
410 |
469 |
528 |
586 |
645 |
704 |
22 |
1 |
1161 |
215 |
269 |
323 |
377 |
430 |
484 |
538 |
592 |
646 |
23 |
1 |
1149 |
198 |
248 |
297 |
347 |
396 |
446 |
496 |
545 |
595 |
24 |
1 |
137 |
183 |
229 |
275 |
321 |
366 |
412 |
458 |
504 |
550 |
25 |
1 |
1127 |
170 |
212 |
255 |
297 |
340 |
382 |
425 |
467 |
510 |
26 |
1 |
118 |
158 |
197 |
237 |
276 |
316 |
355 |
395 |
434 |
474 |
27 |
1 |
111 |
147 |
184 |
221 |
258 |
295 |
332 |
368 |
405 |
442 |
28 |
1 |
103 |
138 |
172 |
207 |
241 |
275 |
310 |
344 |
379 |
413 |
29 |
1 |
97 |
129 |
161 |
194 |
226 |
258 |
290 |
323 |
355 |
387 |
30 |
1 |
91 |
121 |
152 |
182 |
212 |
242 |
273 |
303 |
333 |
364 |
31 |
1 |
86 |
114 |
143 |
171 |
200 |
228 |
257 |
285 |
314 |
342 |
32 |
1 |
81 |
108 |
134 |
161 |
188 |
215 |
242 |
269 |
296 |
323 |
33 |
1 |
176 |
102 |
127 |
152 |
178 |
203 |
229 |
254 |
280 |
305 |
34 |
1 |
72 |
96 |
120 |
144 |
168 |
192 |
216 |
240 |
265 |
289 |
35 |
1 |
68 |
91 |
114 |
137 |
160 |
182 |
205 |
228 |
251 |
273 |
36 |
1 |
165 |
87 |
108 |
130 |
151 |
173 |
195 |
216 |
238 |
260 |
37 |
1 |
62 |
82 |
103 |
123 |
144 |
165 |
185 |
206 |
226 |
247 |
38 |
1 |
59 |
78 |
98 |
117 |
137 |
157 |
176 |
196 |
215 |
235 |
39 |
1 |
56 |
75 |
93 |
112 |
131 |
149 |
168 |
187 |
205 |
224 |
40 |
1 |
53 |
71 |
89 |
107 |
125 |
142 |
160 |
178 |
196 |
214 |
For SI: one inch (1") = 25.4 mm, one foot (1') = 304.8 mm, one (1) pound per square inch = 6.895 kPa, one (1) gallon per minute = 0.963 L/s.
a Flow rate from Section P2904.4.2.
Table P2904.6.2(8) - Allowable Pipe Length for 3/4-inch PEX Tubing
WATER |
Available Pressure - Pt (psi) |
||||||||||
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
||
SPRINKLER FLOW RATEa (gpm) |
DISTRIBUTION SIZE (inch) |
Allowable length of pipe from service valve to farthest sprinkler (feet) |
|||||||||
8 |
3/4 |
93 |
123 |
154 |
185 |
216 |
247 |
278 |
309 |
339 |
370 |
9 |
3/4 |
74 |
99 |
124 |
149 |
174 |
199 |
223 |
248 |
273 |
298 |
10 |
3/4 |
61 |
82 |
102 |
123 |
143 |
163 |
184 |
204 |
225 |
245 |
11 |
3/4 |
51 |
68 |
86 |
103 |
120 |
137 |
154 |
171 |
188 |
205 |
12 |
3/4 |
44 |
58 |
73 |
87 |
102 |
117 |
131 |
146 |
160 |
175 |
13 |
3/4 |
38 |
50 |
63 |
75 |
88 |
101 |
113 |
126 |
138 |
151 |
14 |
3/4 |
33 |
44 |
55 |
66 |
77 |
88 |
99 |
110 |
121 |
132 |
15 |
3/4 |
29 |
39 |
48 |
58 |
68 |
77 |
87 |
96 |
106 |
116 |
16 |
3/4 |
26 |
34 |
43 |
51 |
60 |
68 |
77 |
86 |
94 |
103 |
17 |
3/4 |
23 |
31 |
38 |
46 |
54 |
61 |
69 |
77 |
84 |
92 |
18 |
3/4 |
21 |
28 |
34 |
41 |
48 |
55 |
62 |
69 |
76 |
83 |
19 |
3/4 |
19 |
25 |
31 |
37 |
44 |
50 |
56 |
62 |
69 |
75 |
20 |
3/4 |
17 |
23 |
28 |
34 |
40 |
45 |
51 |
57 |
62 |
68 |
21 |
3/4 |
16 |
21 |
26 |
31 |
36 |
41 |
47 |
52 |
57 |
62 |
22 |
3/4 |
NP |
19 |
24 |
28 |
33 |
38 |
43 |
47 |
52 |
57 |
23 |
3/4 |
NP |
17 |
22 |
26 |
31 |
35 |
39 |
44 |
48 |
52 |
24 |
3/4 |
NP |
16 |
20 |
24 |
28 |
32 |
36 |
40 |
44 |
49 |
25 |
3/4 |
NP |
NP |
19 |
22 |
26 |
30 |
34 |
37 |
41 |
45 |
26 |
3/4 |
NP |
NP |
17 |
21 |
24 |
28 |
31 |
35 |
38 |
42 |
27 |
3/4 |
NP |
NP |
16 |
20 |
23 |
26 |
29 |
33 |
36 |
39 |
28 |
3/4 |
NP |
NP |
15 |
18 |
21 |
24 |
27 |
30 |
33 |
36 |
29 |
3/4 |
NP |
NP |
NP |
17 |
20 |
23 |
26 |
28 |
31 |
34 |
30 |
3/4 |
NP |
NP |
NP |
16 |
19 |
21 |
24 |
27 |
29 |
32 |
31 |
3/4 |
NP |
NP |
NP |
15 |
18 |
20 |
23 |
25 |
28 |
30 |
32 |
3/4 |
NP |
NP |
NP |
NP |
17 |
19 |
21 |
24 |
26 |
28 |
33 |
3/4 |
NP |
NP |
NP |
NP |
16 |
18 |
20 |
22 |
25 |
27 |
34 |
3/4 |
NP |
NP |
NP |
NP |
NP |
17 |
19 |
21 |
23 |
25 |
35 |
3/4 |
NP |
NP |
NP |
NP |
NP |
16 |
18 |
20 |
22 |
24 |
36 |
3/4 |
NP |
NP |
NP |
NP |
NP |
15 |
17 |
19 |
21 |
23 |
37 |
3/4 |
NP |
NP |
NP |
NP |
NP |
NP |
16 |
18 |
20 |
22 |
38 |
3/4 |
NP |
NP |
NP |
NP |
NP |
NP |
16 |
17 |
19 |
21 |
39 |
3/4 |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
16 |
18 |
20 |
40 |
3/4 |
NP |
NP |
NP |
NP |
NP |
NP |
NP |
16 |
17 |
19 |
For SI: one inch (1") = 25.4 mm, one foot (1') = 304.8 mm, one (1) pound per square inch = 6.895 kPa, one (1) gallon per minute = 0.963 L/s.
NP - Not permitted.
a Flow rate from Section P2904.4.2.
Table P2904.6.2(9) - Allowable Pipe Length for 1-inch PEX Tubing
SPRINKLER FLOW RATEa (gpm) |
WATER DISTRIBUTION SIZE (inch) |
Available Pressure - Pt (psi) |
|||||||||
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
||
Allowable length of pipe from service valve to farthest sprinkler (feet) |
|||||||||||
8 |
1 |
314 |
418 |
523 |
628 |
732 |
837 |
941 |
1046 |
1151 |
1255 |
9 |
1 |
252 |
336 |
421 |
505 |
589 |
673 |
757 |
841 |
925 |
1009 |
10 |
1 |
208 |
277 |
346 |
415 |
485 |
554 |
623 |
692 |
761 |
831 |
11 |
1 |
174 |
232 |
290 |
348 |
406 |
464 |
522 |
580 |
638 |
696 |
12 |
1 |
148 |
198 |
247 |
296 |
346 |
395 |
445 |
494 |
543 |
593 |
13 |
1 |
128 |
170 |
213 |
256 |
298 |
341 |
383 |
426 |
469 |
511 |
14 |
1 |
111 |
149 |
186 |
223 |
260 |
297 |
334 |
371 |
409 |
446 |
15 |
1 |
98 |
131 |
163 |
196 |
229 |
262 |
294 |
327 |
360 |
392 |
16 |
1 |
87 |
116 |
145 |
174 |
203 |
232 |
261 |
290 |
319 |
348 |
17 |
1 |
78 |
104 |
130 |
156 |
182 |
208 |
233 |
259 |
285 |
311 |
18 |
1 |
70 |
93 |
117 |
140 |
163 |
187 |
210 |
233 |
257 |
280 |
19 |
1 |
63 |
84 |
106 |
127 |
148 |
169 |
190 |
211 |
232 |
253 |
20 |
1 |
58 |
77 |
96 |
115 |
134 |
154 |
173 |
192 |
211 |
230 |
21 |
1 |
53 |
70 |
88 |
105 |
123 |
140 |
158 |
175 |
193 |
211 |
22 |
1 |
48 |
64 |
80 |
97 |
113 |
129 |
145 |
161 |
177 |
193 |
23 |
1 |
44 |
59 |
74 |
89 |
104 |
119 |
133 |
148 |
163 |
178 |
24 |
1 |
41 |
55 |
69 |
82 |
96 |
110 |
123 |
137 |
151 |
164 |
25 |
1 |
38 |
51 |
64 |
76 |
89 |
102 |
114 |
127 |
140 |
152 |
26 |
1 |
35 |
47 |
59 |
71 |
83 |
95 |
106 |
118 |
130 |
142 |
27 |
1 |
33 |
44 |
55 |
66 |
77 |
88 |
99 |
110 |
121 |
132 |
28 |
1 |
31 |
41 |
52 |
62 |
72 |
82 |
93 |
103 |
113 |
124 |
29 |
1 |
29 |
39 |
48 |
58 |
68 |
77 |
87 |
97 |
106 |
116 |
30 |
1 |
27 |
36 |
45 |
54 |
63 |
73 |
82 |
91 |
100 |
109 |
31 |
1 |
26 |
34 |
43 |
51 |
60 |
68 |
77 |
85 |
94 |
102 |
32 |
1 |
24 |
32 |
40 |
48 |
56 |
64 |
72 |
80 |
89 |
97 |
33 |
1 |
23 |
30 |
38 |
46 |
53 |
61 |
68 |
76 |
84 |
91 |
34 |
1 |
22 |
29 |
36 |
43 |
50 |
58 |
65 |
72 |
79 |
86 |
35 |
1 |
20 |
27 |
34 |
41 |
48 |
55 |
61 |
68 |
75 |
82 |
36 |
1 |
19 |
26 |
32 |
39 |
45 |
52 |
58 |
65 |
71 |
78 |
37 |
1 |
18 |
25 |
31 |
37 |
43 |
49 |
55 |
62 |
68 |
74 |
38 |
1 |
18 |
23 |
29 |
35 |
41 |
47 |
53 |
59 |
64 |
70 |
39 |
1 |
17 |
22 |
28 |
33 |
39 |
45 |
50 |
56 |
61 |
67 |
40 |
1 |
16 |
21 |
27 |
32 |
37 |
43 |
48 |
53 |
59 |
64 |
For SI: one inch (1") = 25.4 mm, one foot (1') = 304.8 mm, one (1) pound per square inch = 6.895 kPa, one (1) gallon per minute = 0.963 L/s.
a. Flow rate from Section P2904.4.2.