Rhode Island Code of Regulations
Title 510 - Building Code Commission
Chapter 00 - N/A
Subchapter 00 - N/A
Part 2 - RISBC-2 Rhode Island State One amp; Two-Family Dwelling Code
Section 510-RICR-00-00-2.13 - Chapter 11

Current through September 18, 2024

N1101.1 Delete section N1101.2 and substitute the following:

N1101.1.1 Compliance Methods

Compliance shall be demonstrated by either:

1. Meeting the requirements of the Rhode Island Energy Conservation Code SBC-8-2021 (Part 8 of this Subchapter).

2. Meeting the requirements of this Chapter using the criteria for climate zone 5 from Figure N 1102A or Table 1102.1.2.

3. Compliance submission of Res-Check for Zone 5 amp; Chapter 11 Delete Table N1101.8 without substitution

N 1101. 7 (R301.1) Climate Zones: Rhode Island shall be considered as climate zone 5 with the following design conditions.

Table N1101.7 (R301.1) Delete and substitute the following:

Table N1101.7 (R301.1)

Value

Value

Exterior Design Conditions.

Climate zone

Providence

County

All others

Winter, design dry-bulb (degree F)

0

5

Summer, design dry-bulb

87

89

Summer design wet-bulb

71

73

Degree days heating

6831

5950

Degree days cooling

371

811

Delete without substitute sections N1101.7, N1101.7.2, N1101.7.3 R301.2 and R301.3, R301.4.

Delete Table N1101.7.2 (1) (R301.3(1)) without substitute.

Delete Table N1101.7.2 (2) (R301.3(2)) without substitute.

Delete Figure N1101.7 (R301.1) and substitute the following: Figure N1101.7 (R301.1)

Click here to view image

Figure N1101.7 (R 301.1)

Delete Table N1101.14 (R401.3) and substitute the following:

Add the following to N1101.14 (R401.3), Certificate:

Figure R401.3

A certificate similar to this shall be attached to or near the electrical panel board

ENERGY CERTIFICATE

Street Address

City / Town

Predominant Values

R-Value Ceiling / Roof

R- Value Walls

R- Value Ducts (outside conditioned space)

U Factor Fenestration

SHGC Fenestration

Gas Fired Un-Vented Room Heater

Baseboard Electric Heater

Electric Furnace

U Factor Skylight / SHGC

AFUE Value Boiler / Furnace

Efficiency and type of heating equipment

Efficiency and type of cooling equipment

Efficiency and type of service water heater

Contractor or Design Professional

Address

Registration

Signature

Delete and substitute table N1102.1.2 (R402.1.2)

TABLE N 1102.1.2 (R 402.1.2)

INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT a

CLIMATE ZONE

FENESTRATION U-FACTOR b

SKYLIGHT b U-FACTOR

GLAZED FERNESTRATION SHGC b

CEILING R-VALUE i

WOOD FRAME WALL R-VALUE g

MASS WALL R-VALUE

FLOOR R-VALUE

BASEMENT C WALL R-VALUE

SLAB d R-VALUE & DEPTH

CRAWL SPACE c WALL R-VALUE

5

0.35

0.60

NR

38

20 or 13+5 f

13/17

30 e

10/13

R-10 for 2 ft.

10/13

For SI: 1 foot = 304.8 mm.

R-values are minimums U-factors and SHGC are maximums. R-19 batts compressed into a nominal two (2) by six (6) framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value.

The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.

"10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.

R-5 shall be added to the entire slab and the required slab edge R-values for heated slabs or insulation sufficient to fill the framing cavity, R-19 minimum.

"13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers twenty-five percent (25%) or less of the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more than twenty-five percent (25%) of exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.

The second R-value applies when more than half the insulation is on the interior of the mass wall.

TABLE N1102.1.4(R402.1.4) EQUIVALENT U-FACTORSa

CLIMATE ZONE

FENESTRATION U-FACTOR

SKYLIGHT U-FACTOR

CEILING U-FACTOR

FRAME WALL U-FACTOR

MASS WALL U-FACTORb

FLOOR U-FACTOR

BASEMENT WALL U-FACTOR

CRAWL SPACE U-FACTOR

5

0.32

0.55

0.026

0.057

0.082

0.033

0.050

0.055

Delete N1102.1.5 (R402.1.5) Total UA alternative and substitute the following:

N1102.1.5 (R402.1.5) Total UA alternative. If the total building thermal envelope UA (sum of U-factor times assembly area) is less than or equal to the total UA resulting from using the U-factors in Table R402.1.3 (multiplied by the same assembly area as in the proposed building), the building shall be considered in compliance with Table R402.1.1. The UA calculation shall include the thermal bridge effects of framing materials. The UA calculation shall include the thermal bridging effects of framing materials. The SHGC requirements shall be met in addition to UA compliance.

Delete section N1102.4.1.2 (R402.4.1.2) and substitute the following:

N1102.4.1.2 Testing. The building or dwelling unit shall be tested, and Testing shall be conducted with a blower door at a pressure of two tenths of one inch (0.2") w.g. (fifty (50) Pascals). Maximum air change rates per hour: In 2019 = 8, 2020 = 7, 2021 = 6, and 2022 and subsequent years = 5.

Testing shall be conducted by an approved third party, where required by the building official. A written report of the results of the test shall be signed by the party conducting the test and provided to the building official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.

During testing:

Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weather-stripping or other infiltration control measures;

Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures;

Interior doors, if installed at the time of the test, shall be open.

Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;

Heating and cooling systems, if installed at the time of the test, shall be turned off; and Supply and return registers, if installed at the time of the test, shall be fully open.

N1103.3.3 (R403.3.3) Duct Testing (Mandatory)

Delete section N1103.3.3 (R403.3.3) and substitute the following:

N1103.2.2 (R403.2.2) Sealing (Mandatory). Ducts, air handlers, and filter boxes shall be sealed. Joints and seams shall comply with section M1601.4.1 of this code.

Exceptions:

Air-impermeable spray foam products shall be permitted to be applied without additional joint seals.

Where a duct connection is made that is partially inaccessible, three (3) screws or rivets shall be equally spaced on the exposed portion of the joint so as to prevent a hinge effect.

Continuously welded and locking -type longitudinal joints and seams in ducts operating at a static pressures less than two inches (2") of water column (five hundred (500) Pascals) pressure classification shall not require additional closure systems.

Duct tightness shall be verified by either of the following:

Postconstruction test: Total leakage shall be less than or equal to eight (8) cfm (113.3 L/min) per one hundred (100) square feet (9.29 m2) of conditioned floor area.

Rough-in test: Total leakage shall be less than or equal to six (6) cfm (113.3 L/min) per one hundred (100 ft2) (9.29 m2) of conditioned floor area when tested at a pressure differential of one tenth of one inch (0.1") w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure. All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test. Total leakage shall be less than or equal to four (4) cfm (85 L/min) per one hundred (100) square feet (9.29 m2) of conditioned floor area.

Exception: The total leakage test is not required for ducts and air handlers located entirely within the building envelope.

Delete section N1103.3.5 (R403.3.5) and substitute the following:

N1103.3.5 (R403.3.5) Building cavities (Mandatory). Interior building framing cavities shall be permitted to be used as return ducts or plenums. (BP)

Delete Table N1103.6.1 without substitutions

Reference Standards

Delete without substitute

ASHRAE - 2013 ASHRAE Handbook of Fundamentals.

Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.