Rhode Island Code of Regulations
Title 510 - Building Code Commission
Chapter 00 - N/A
Subchapter 00 - N/A
Part 2 - RISBC-2 Rhode Island State One amp; Two-Family Dwelling Code
Section 510-RICR-00-00-2.12 - Chapter 10

Current through September 18, 2024

Add the following new section R1007 Room Heater

R1007.0 Room Heaters (Wood/Coal/Pellet Stoves)

R1007.1 General:

Solid-fuel-burning room heaters shall be tested in accordance with UL 1482 listed in Appendix A of this Code.

Multiple fuel-flue installations

A solid-fuel-burning room heater shall not connect to a chimney passageway venting another appliance.

R1007.3 Used or antique stoves and room heaters:

The Building Official shall permit the installation and use of non-listed or tested stoves and heaters when installed in accordance with the provisions of Table R1007.3 as follows:

Table 1007.3 CLEARANCE REDUCTION METHODS

TYPE OF PROTECTIVE ASSEMBLYa

REDUCED CLEARANCE WITH PROTECTION (inches)a

Horizontal combustible assemblies located above the heat source

Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies

Required clearance to combustibles

Required clearance to combustibles

without protection (inches)a

without protection (inches)a

36

18

9

6

36

18

9

6

Galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), mounted on 1-inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible assembly

18

9

5

3

12

6

3

3

Galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), spaced 1 inch off the combustible assembly.

18

9

5

3

12

6

3

2

Two layers of galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), having a 1-inch airspace between layers, spaced 1 inch off the combustible assembly

18

9

5

3

12

6

3

3

Two layers of galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly.

18

9

5

3

12

6

3

3

0.5-inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly.

24

12

6

4

18

9

5

3

3.5-inch brick wall, spaced 1 inch off the combustible wall

12

6

6

6

3.5-inch brick wall, against the combustible wall

24

2

6

5

For SI: 1 inch = 25.4 mm, oC = [(oF)-32]/1.8, 1 pound per cubic foot = 16.02 kg/m3, 1.0 Btu x in/ft2.h. oF=0.144 W/m 2. oK.

a Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1,500o F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu x in/ft2.h. oF) or less.

Insulation board shall be formed of noncombustible material.

Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.