Rhode Island Code of Regulations
Title 510 - Building Code Commission
Chapter 00 - N/A
Subchapter 00 - N/A
Part 2 - RISBC-2 Rhode Island State One amp; Two-Family Dwelling Code
Section 510-RICR-00-00-2.11 - Chapter 9

Current through September 18, 2024

R905.2.6 Delete section R905.2.6 and substitute the following:

R905.2.6 Attachment.

Asphalt strip shingles shall have a minimum of six (6) fasteners per shingle.

Exceptions:

1. Where the roof slope exceeds twenty (20) units vertical in twelve (12) units horizontal (20:12), special fastening details may be required by the manufacturer.

2. Fastening systems tested by the manufacturer to ASTM D3161 modified to use a wind speed of one hundred ten (110) MPH shall be permitted to be installed in any wind zone.

R905.2.8.2 #3 Delete and substitute the following:

R905.2.8.2 #3
3. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D224 Type II or Type III and at least thirty-six inches (36") (914 mm) wide or valley lining as described in Items 1 and 2 above shall be permitted. Specialty underlayment complying with ASTM D 1970 may be used in lieu of the lining material. Other valley lining systems and techniques acceptable to the shingle manufacturer shall be approved by the Building Official.

Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.