Rhode Island Code of Regulations
Title 510 - Building Code Commission
Chapter 00 - N/A
Subchapter 00 - N/A
Part 1 - RISBC-1 Rhode Island Building Code
Section 510-RICR-00-00-1.15 - Chapter 18: Soils and Foundations

Current through September 18, 2024

Delete IBC section 1801.3 and substitute the following

1809.5 Frost protection.

Except where otherwise protected from frost, foundation walls, piers and other permanent supports of buildings and structures shall be protected by one or more of the following methods:

1. See Rhode Island Frost Depth values in Table 1608.1. and Figure 1608.1

2. Construction in accordance with ASCE 32; 05

3. Erecting on solid rock

Exception: Free-standing buildings meeting all of the following conditions shall not be required to be protected:

1. Classified in Occupancy Category I, in accordance with section 1604.5;

2. Area of six hundred (600) square feet (56 M2) or less for light-frame construction or four hundred (400) square feet (37 m2) or less for other than light-frame construction; and

3. Eave height of ten feet (10') (3048 mm) or less

Footings shall not bear on frozen soil unless such frozen condition is of a permanent character.

Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.