Section 510-RICR-00-00-1.13 - Chapter 15: Roof Assemblies and Rooftop Structures
Universal Citation: 510 RI Code of Rules 00 00 1.13
Current through September 18, 2024
Delete IBC section 1507.2.6 attachment and substitute the following:
1507.2.6 Attachment.
Asphalt strip shingles shall have a minimum of six (6) fasteners per shingle strip.
Exceptions:
1.
Where the roof slope exceeds twenty (20) units vertical in twelve (12) units
horizontal (20:12), special fastening details may be required by the
manufacturer.
2. Fastening systems
tested by the manufacturer to one hundred ten (110) MPH shall be permitted to
be installed in any wind zone.
Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.