Section 510-RICR-00-00-1.13 - Chapter 15: Roof Assemblies and Rooftop Structures

Current through September 18, 2024

Delete IBC section 1507.2.6 attachment and substitute the following:

1507.2.6 Attachment.

Asphalt strip shingles shall have a minimum of six (6) fasteners per shingle strip.

Exceptions:

1. Where the roof slope exceeds twenty (20) units vertical in twelve (12) units horizontal (20:12), special fastening details may be required by the manufacturer.

2. Fastening systems tested by the manufacturer to one hundred ten (110) MPH shall be permitted to be installed in any wind zone.

Disclaimer: These regulations may not be the most recent version. Rhode Island may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.