FIRE SAFETY
Section 6400.111 - Fire extinguishers

Universal Citation: 55 PA Code ยง 6400.111

Current through Register Vol. 54, No. 44, November 2, 2024

(a) There shall be at least one operable fire extinguisher with a minimum 2-A rating for each floor, including the basement and attic.

(b) If the indoor floor area on a floor including the basement or attic is more than 3,000 square feet, there shall be an additional fire extinguisher with a minimum 2-A rating for each additional 3,000 square feet of indoor floor space.

(c) A fire extinguisher with a minimum 2A-10BC rating shall be located in each kitchen. The kitchen extinguisher meets the requirements for one floor as required in subsection (a).

(d) A fire extinguisher shall be listed by Underwriters Laboratories or approved by Factory Mutual Systems.

(e) A fire extinguisher shall be accessible to staff persons and individuals.

(f) A fire extinguisher shall be inspected and approved annually by a fire safety expert. The date of the inspection shall be on the extinguisher.

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.