(i) The provisions of
R314.4 requiring interconnected smoke alarms do not apply to one-family and
two-family dwellings undergoing alterations, repairs or additions.
Noninterconnected battery operated smoke alarms shall be installed in these
dwellings.
(ii) The following
specifications apply to residential stairway treads and risers.
(A) The maximum riser height is 8 1/4 inches.
There may be no more than a 3/8 inch variation in riser height within a flight
of stairs. The riser height is to be measured vertically between leading edges
of the adjacent treads.
(B) The
minimum tread depth is 9 inches measured from tread nosing to tread
nosing.
(C) The greatest tread
depth within any flight of stairs may not exceed the smallest by more than 3/8
inch.
(D) Treads may have a uniform
projection of not more than 1 1/2 inches when solid risers are used.
(E) Stairways may not be less than 3 feet in
clear width and clear headroom of 6 feet 8 inches shall be maintained for the
entire run of the stair.
(F)
Handrails may project from each side of a stairway a distance of 3 1/2 inches
into the required width of the stair.
(iii) The following provisions are excluded:
(A) Section R302.5.1 (relating to opening
protection).
(B) Section R322.2.1
(relating to elevation requirements for flood hazard areas).
(C) Section R322.3.2 (relating to elevation
requirements for coastal high hazard areas).
(D) Exception 2 of section R325.5 (relating
to openness).
(E) Section R703.7.1
(relating to lath).
(F) Section
R703.7.2 (relating to plaster).
(G)
Section R703.7.3 (relating to water-resistive barriers).
(H) Section R806.2 (relating to minimum vent
area).
(I) Section R1005.8
(relating to insulation shield).
(J) Section N1101.4 (relating to above code
programs).
(K) Section N1103.3.5
(relating to building cavities).
(L) Section N1105.4.2 (relating to compliance
report).
(M) Section N1106.3
(relating to energy rating index).
(N) Section N1106.6.1 (relating to compliance
software tools).
(O) Section
N1106.6.4 (relating to specific approval).
(P) Section N1106.6.5 (relating to input
values).
(Q) Section N1108.1.1.2
(relating to heating and cooling systems).
(R) Section N1109.1.2 (relating to heating
and cooling systems).
(S) Section
M1305.1.3.2 (relating to pit locations).
(T) Section M1502.3.1 (relating to exhaust
termination outlet and passageway size).
(U) Section P2503.5.1 (relating to rough
plumbing).
(V) Section P2903.5
(relating to water hammer).
(W)
Section P2906.6.1 (relating to saddle tap fittings).
(iv) The following provisions are modified:
(A) Section R311.7.4 (relating to walkline)
is amended by adding figure R311.7.4 (relating to winder tread and landing
detail).
Click to
view image
(B)
Section R325.6 (relating to habitable attic) is amended by removing subsection
4.
(C) Subsection 2.4 of section
R408.3 (relating to unvented crawl space) is amended to read as follows:
"Dehumidification sized in accordance with manufacturer's
specifications."
(D) Section
R702.7.3 (relating to minimum clear airspaces and vented openings for vented
cladding) is amended by adding a comma after the word "vinyl" in subsection
1.
(E) Section R703.7 (relating to
exterior plaster (stucco)) is amended by requiring compliance with ASTM
standards C926-2018B and C1063-2018B.
(F) The last sentence of section R806.1
(relating to ventilation required) is amended to read as follows: "Required
ventilation openings shall open directly to the outside air."
(G) The first sentence of section R806.3
(relating to vent and insulation clearance) is amended to read as follows:
"Where eave or cornice vents are installed, nothing shall block the free flow
of air."
(H) The Fenestration
U-Factor in Climate Zone 3 for Table N1102.1.2 (relating to
insulation and fenestration requirements by Component) is amended to
0.35.
(I) Section N1105.2 (relating
to mandatory requirements) is amended to require compliance with the mandatory
provisions of section N1102.4.1.2 (relating to testing).
(J) Section E3901.11 (relating to foyers) is
amended by replacing 3 feet (914 mm) with 6 feet (1829 mm) and a minimum of one
receptacle.
(v) The
following provisions of the International Residential Code of 2009 are adopted:
(A) Section R302.5.1 (relating to opening
protection).
(B) Section R322.2.1
(relating to elevation requirements for flood hazard areas).
(C) Section R322.3.2 (relating to elevation
requirements for coastal high hazard areas).
(D) Section N1101.8 (relating to above code
programs).
(E) Section N1103.2.3
(relating to building cavities).
(F) Section P2503.5.1 (relating to rough
plumbing).
(vi) The
following provisions of the "International Residential Code of 2015" are
adopted:
(A) Section R806.2 (relating to
minimum vent area).
(B) Section
N1105.4.2 (relating to compliance report).
(C) Section N1106.3 (relating to energy
rating index).
(D) Section
N1106.3.1 (relating to ERI reference design).
(E) Section N1106.6.1 (relating to compliance
software tools).
(F) Section
N1106.7 (relating to calculation software tools).
(G) Section N1106.7.1 (relating to minimum
capabilities).
(H) Section
N1106.7.2 (relating to specific approval).
(I) Section N1106.7.3 (relating to input
values).
(J) Section N1108.1.1.2
(relating to heating and cooling systems).
(K) Section N1109.1.2 (relating to heating
and cooling systems).
(L) Section
M1305.1.4.2 (relating to excavations).
(M) Section P2903.5 (relating to water
hammer).
(vii) The
following provisions of the "International Residential Code of 2021" are
adopted:
(A) Section R703.7.1 (relating to
lath).
(B) Section R703.7.1.1
(relating to furring).
(C) Section
R703.7.2 (relating to plaster).
(D)
Section R703.7.3 (relating to water-resistive barriers).
(E) Section R703.7.3.1 (relating to dry
climates).
(F) Section R703.7.3.2
(relating moist or marine climates).
(G) Section M1411.6.1 (relating to
refrigerant line insulation protection).