Section 7.323 - Capacity
Universal Citation: 34 PA Code ยง 7.323
Current through Register Vol. 54, No. 38, September 21, 2024
The maximum capacity of newly installed escalators shall be determined as follows:
(1) For escalators 24 inches or less in width, the maximum load shall equal 110 times the horizontally projected length of exposed treads in feet.
(2) For escalators over 24 inches in width, the maximum load shall equal 4.6 times the width of the escalator in inches times the horizontally projected length of exposed treads in feet.
Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.