Chapter 7 - ELEVATORS, LIFTS, ESCALATORS, DUMBWAITERS, HOISTS ANDTRAMWAYS
Subchapter G - MANLIFTS
SPECIFICATIONS
Section 7.225 - Floor opening guards

Universal Citation: 34 PA Code ยง 7.225

Current through Register Vol. 54, No. 38, September 21, 2024

(a) The floor opening at each landing shall be guarded on sides not used for entrance or exit by a standard railing and toeboard or by panels or wire mesh of not less than No. 10 U.S. gage, expanded metal of not less than No. 13 U.S. gage or sheet metal of equivalent strength or metal on a frame of angle iron not less than 1 1/4 inch by 1 1/4 inch by 1/8 inch or of 1 1/4 inch iron pipe.

(b) Such rails or guards shall be at least 42 inches in height on the up-running side and 66 inches on the down-running side. If a guardrail is used the section of the guard above the rail may be of the construction specified in subsection (a), or may consist of vertical metal bars which will reject a ball 6 inches in diameter. Rails or guards shall be located not more than one foot from the edge of the floor opening.

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.