Section 7.14 - Tests
Current through Register Vol. 54, No. 38, September 21, 2024
(a) New passengers and freight elevators shall be tested in the presence of a Department inspector to see that the car safeties, speed governors, brakes, bumpers, limit switches, and the like, perform their proper functions. The car safeties shall be tested with the elevator car carrying the maximum allowable load. In making the final test the hoisting cables shall be detached from the car, while at a height sufficient to indicate the efficiency of the car safeties. A runaway test is acceptable in lieu of the free drop test when approved safety devices are installed. For reostatic control elevators, the safeties shall be tested by tripping the governor. Broken rope safety devices shall be tested as such.
(b) Existing installations shall be tested as follows:
Maximum Speeds at which Speed Governor Trips and Governor Overspeed Switch Operates
Rated Speed (in feet per minute) | Maximum Governor Trip Speed (in feet per minute) | Maximum Speed at which Governor Overspeed Switch Operates (down feet per minute) |
0-125 | 175 | 175 |
150 | 210 | 190 |
175 | 250 | 225 |
200 | 280 | 252 |
225 | 308 | 277 |
250 | 337 | 303 |
300 | 395 | 355 |
350 | 452 | 407 |
400 | 510 | 459 |
450 | 568 | 512 |
500 | 625 | 563 |
600 | 740 | 703 |
700 | 855 | 812 |
800 | 970 | 921 |
900 | 1085 | 1031 |
1000 | 1200 | 1140 |
1100 | 1320 | 1254 |
1200 | 1440 | 1368 |
1300 | 1560 | 1482 |
1400 | 1680 | 1596 |
1500 | 1800 | 1710 |
(c) New escalators shall be tested in the presence of a Department inspector. The test shall consist of a physical examination of the escalator parts together with a running test of the escalator without load, including a test of all the safety features prescribed in § 7.324 (relating to safety equipment).
(d) On the completion of any device provided for by this chapter, the owner, builder, contractor, manufacturer, or other responsible party or parties, shall file with the Department notice in writing that such installation has been constructed and installed in accordance with the plans as approved. Upon receipt of such notice the Department may arrange for inspection of the installation by a Department inspector.
(e) New elevators, escalators, dumbwaiters, gravity elevators and hoists shall not be operated temporarily pending final completion without permission of the Department.