Chapter 55 - DIVISION C-2 HOTELS, MOTELS, APARTMENT BUILDINGS, ETC
MEANS OF EGRESS
Section 55.24 - Exit doors
Universal Citation: 34 PA Code ยง 55.24
Current through Register Vol. 54, No. 38, September 21, 2024
Exit discharge doors leading to the outside shall comply with § 50.24 (relating to exit doors and exit access doors) except that exit and exit discharge doors which serve nine or less rooms or four or less apartments shall not be required to have panic hardware or fire exit hardware, and exit discharge doors serving one apartment need not swing with exit travel.
Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.