MANUAL AND AUTOMATIC FIRE ALARM SYSTEMS
Section 55.52 - Automatic systems
Current through Register Vol. 54, No. 38, September 21, 2024
(a) An automatic fire alarm system shall be provided for C-2 occupancies, except for buildings totally protected by an automatic sprinkler system. Smoke detectors shall be located in the corridors, stairs and rooms of the building except as follows: rooms of individual apartment units, hotel or motel sleeping rooms, or dormitory rooms with sleeping accommodations for five or less persons. Heat detectors may be used in kitchens, restrooms, boiler rooms, furnace rooms and other special rooms as approved by the Department. Other detection devices may be approved by the Department for special conditions. The automatic fire alarm system shall comply with § 50.52 (relating to automatic system), except that buildings with 12 or less apartments may comply with the following:
(b) In addition to the automatic fire alarm system required in subsection (a), each apartment shall have a minimum of one smoke-detection device located in a common area between the apartment exit and the bedrooms. This device may be a single-station detection device which is not interconnected with the automatic fire alarm system. Single-station detection devices shall be listed as meeting U. L. 217, 1980 Edition.
This section cited in 34 Pa. Code § 49.2 (relating to jurisdiction and effective dates).