Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 55 - DIVISION C-2 HOTELS, MOTELS, APARTMENT BUILDINGS, ETC
EXTINGUISHERS AND SPRINKLER SYSTEMS
Section 55.71 - Fire extinguishers
Current through Register Vol. 54, No. 44, November 2, 2024
(a) Fire extinguishers with a minimum 2-A rating shall be provided as follows:
(b) There shall be a minimum of one fire extinguisher per floor including basement.
(c) Fire extinguishers shall be located so that it shall not be necessary to travel more than 100 feet in any direction to reach the nearest unit.
(d) A fire extinguisher with a minimum 10-B rating shall be provided in each kitchen.
(e) Where fire extinguishers are installed in a closet or recessed in a wall or obscured from view, there shall be provided adjacent thereto a constant blue light of not less than 25 watt capacity. Fire extinguishers in individual apartments need not comply with this subsection.