Section 51.22 - Travel distance to exits
Universal Citation: 34 PA Code ยง 51.22
Current through Register Vol. 54, No. 38, September 21, 2024
(a) Exits shall be so arranged that the total length of travel from any point to reach an exit will not exceed 150 feet. Exits shall be so arranged that one exit is not more than 200 feet from another exit. Dead ends and occupancy areas with a single path of egress travel should be eliminated where possible but in no case shall any of these occupancy areas be more than 75 feet from an exit.
(b) Travel distance may be increased to the following in buildings totally protected by an automatic sprinkler system:
(1) 200 feet from any point to an
exit.
(2) 300 feet between
exits.
(3) 100 feet for dead ends
and areas with a single path of egress.
Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.