Section 50.33 - Fire door assemblies
Current through Register Vol. 54, No. 38, September 21, 2024
Fire door assemblies in vertical openings shall be self-closing, latching, and normally kept closed. Electromagnetic hold open devices may be approved by the Department where all of the following conditions are met:
(1) Upon release, the door becomes self-closing.
(2) An approved release device is provided, so arranged that upon interruption of electric current, the door will be released.
(3) The release device is so designed that the door may be instantly released manually by some simple and readily obvious operation, and upon release the door becomes self-closing.
(4) The electric current will be positively interrupted by one or more of the following methods:
This section cited in 34 Pa. Code § 51.31 (relating to vertical openings); 34 Pa. Code§ 52.31 (relating to vertical openings); 34 Pa. Code § 53.31 (relating to vertical openings); 34 Pa. Code § 54.31 (relating to vertical openings); 34 Pa. Code § 55.31 (relating to vertical openings); 34 Pa. Code § 57.31 (relating to vertical openings); 34 Pa. Code § 58.31 (relating to vertical openings); and 34 Pa. Code § 59.31 (relating to vertical openings).