Section 50.93 - Special stage regulations
Current through Register Vol. 54, No. 38, September 21, 2024
Stages used for theatrical, musical and like performances which are equipped with a rigging loft or fly gallery shall comply with the following:
(1) Stage enclosure walls. Every stage shall be enclosed on all sides with solid walls of not less than 2-hour fire resistance rating extending continuously from foundation to at least 4 feet above the roof.
(2) Stage floor construction. The entire stage, except the portion used for the working of scenery, traps and other mechanical apparatus for the presentation of a scene, and the roof over the stage may not be less than 3-hour fire resistance rated construction. Openings through the stage floor shall be equipped with tight fitting, solid wood trap doors not less than 3 inches in thickness or other materials of equal physical and fire resistance rated properties.
(3) Stage rigging loft. The rigging loft, fly galleries and pin rails shall be constructed of noncombustible materials.
(4) Footlights and stage electrical equipment. Footlights and border lights shall be installed in troughs constructed of noncombustible materials. The switchboard shall be so located as to be readily accessible at all times, and the storage or placing of stage equipment against it is prohibited.
(5) Exterior stage doors. Required exit discharge door openings to the outer air shall be protected with approved self-closing fire doors.
(6) Proscenium wall. There may be no openings in the wall separating the stage from the auditorium except the main proscenium opening; two doorways at the stage level, one on each side thereof; and, where necessary, not more than two doorways to the musician's pit from the space below the stage floor. Each doorway may not exceed 21 square feet in area and shall be protected with 1 1/2-hour B label fire door assemblies. The distance between the top of the proscenium opening and the ceiling of the stage shall be not less than 5 feet.
(7) Proscenium curtain. The proscenium opening shall be provided with an approved curtain of noncombustible or fire-retardant material so designed and installed that it will protect against passage of flame and smoke for 5 minutes. The curtain shall be operated by an automatic heat activated device to descend instantly and safely and to completely close the proscenium opening at a rate of temperature rise of 15 to 20 F per minute (0.14 C to 0.19 C per second); and by an auxiliary operating device to permit immediate manual closing of the proscenium opening.
(8) Scenery. Combustible materials used in sets and scenery shall be rendered flame resistant.
(9) Stage ventilation. Metal or other approved noncombustible ventilators, equipped with movable shutters or sash shall be provided over the stage, constructed to open automatically and instantly by approved heat activated devices, with an aggregate clear opening of not less than 1/8 the area of the stage.
(10) Dressing and appurtenant rooms.