Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 50 - GENERAL REQUIREMENTS-BUILDINGS
MEANS OF EGRESS
Section 50.28 - Horizontal exits

Universal Citation: 34 PA Code ยง 50.28

Current through Register Vol. 54, No. 44, November 2, 2024

(a) A horizontal exit is a 2-hour fire wall with one or more openings protected by 1 1/2-hour door assemblies which permit passage from one building or structure to another or area of refuge within the same building.

(b) Horizontal exits may constitute no more than 50% of the required units of exit.

(c) Fire walls which serve as horizontal exits shall extend to exterior walls or 2-hour fire walls. They shall not be dependent on any structural members of less than 2-hour fireresistance.

(d) A horizontal exit shall have at least one door which swings with the exit travel from each building section that it serves.

This section cited in 34 Pa. Code § 51.28 (relating to horizontal exits); 34 Pa. Code § 52.28 (relating to horizontal exits); 34 Pa. Code § 53.28 (relating to horizontal exits); 34 Pa. Code § 54.28 (relating to horizontal exits); 34 Pa. Code § 55.28 (relating to horizontal exits); 34 Pa. Code § 56.28 (relating to horizontal exits); 34 Pa. Code § 58.28 (relating to horizontal exits); and 34 Pa. Code § 59.28 (relating to horizontal exits).

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.