Section 50.27 - Ramps
Current through Register Vol. 54, No. 38, September 21, 2024
(a) A ramp shall be permitted as a means of egress when it conforms to the following table:
Minimum clear width in inches | 40 inches |
Maximum slope | 1 inch per foot |
(8.33%) | |
Maximum length between landings | 30 feet |
Required handrails | Both sides |
(each handrail is allowed to project 3 inches without decreasing the minimum clear width) |
(b) Changes in direction of travel shall be made only at landings.
(c) Ramps which connect two or more floor levels shall comply with the same door, handrail and enclosure requirements as stair towers.
(d) Sloped surfaces of less than 5.0% shall not be considered ramps.
This section cited in 34 Pa. Code § 51.27 (relating to ramps); 34 Pa. Code § 52.27 (relating to ramps); 34 Pa. Code § 53.27 (relating to ramps); 34 Pa. Code § 54.27 (relating to ramps); 34 Pa. Code § 55.27 (relating to ramps); 34 Pa. Code § 56.27 (relating to ramps); 34 Pa. Code § 57.27 (relating to ramps); 34 Pa. Code § 58.27 (relating to ramps); and 34 Pa. Code § 59.27 (relating to ramps).