Current through Register Vol. 54, No. 44, November 2, 2024
(a)
Plan approval. Approval for fire alarm systems shall be
obtained at the same time as the building approval. See Chapter 49 (relating to
administration). Three sets of plans showing the location of manual stations,
automatic detection units, control or other panels, signaling devices and other
required equipment shall be submitted for approval. The location of these
devices may be incorporated on the architectural floor plans or may be on fire
alarm or electrical wiring plans. The approval issued by the Department is only
for the location of the equipment. Only equipment approved by the Department
shall be used.
(b)
Control
panels. Control panels are required for manual and automatic fire
alarm systems. A common control pannel may be installed where both are used.
(1)
Operation. The primary
function of the fire alarm control panel is to monitor alarm initiating devices
such as manual stations, automatic detectors, sprinkler flow switches or other
devices and cause upon alarm activation the operating of signaling devices to
alert building occupants of possible danger from fire. Auxiliary functions such
as fire company reporting, air handling systems start-up or shutdown, smoke
barrier door closing, elevator capture and return and remote annunciation are
secondary functions of the system and shall be given lower priority within the
control panel operations. The control panel shall be designed with sufficient
power capacity to operate all primary and secondary functions of the system
simultaneously. Wherever both a manual fire alarm system and an automatic fire
alarm system are used, all alarm indicating devices shall sound on an alarm
origination in either system.
(2)
Location. A fire alarm control panel shall be installed in a
heated room with a clean, dry environment. The control panel shall be located
in such a manner to protect it from tampering by installing it in a locked room
or with a locked control panel door that is accessible only to authorized
building personnel.
(c)
Zoning.
(1) Manual and
automatic fire alarm systems shall be designed with a minimum of one zone per
floor. Manual and automatic devices may be connected to the same zone.
Additional zones shall be provided for floor areas that exceed 20,000 square
feet or areas exceeding 200 feet in any direction.
(2) When a zone is initiated, the zone
indicator on the fire alarm control panel and any remote annunciators shall
lock-in and continuously display the alarm condition until the actuated devices
are reset and a system reset switch is activated.
(3) A maximum of 30 alarm initiating devices
may be connected within a single zone.
(d)
Annunciators.
(1)
When required.
Annunciators shall be installed in manual and automatic fire alarm systems when
more than one zone is required.
(2)
Locations. Annunciators shall be installed so that they are
readily accessible for viewing alarm conditions. Annunciators shall not be in
locked rooms, closets or other areas unless building personnel are available at
all times to provide access.
(3)
Types. Annunciators that indicate alarm zones may be one or a
combination of the following types:
(i)
Lamp illumination type. The actuation of an alarm zone
illuminates the appropriate lamp. Each zone lamp shall be identified by a label
or an adjacent zone chart describing the alarm zone.
(ii)
Graphic type. The
annunciator is represented by a panel that illustrates the building and zone
layout. Either the graphic zone or adjacent lamp shall illuminate to designate
the area of alarm.
(iii)
Window drop type. The actuation of an alarm zone shall cause a
window to mechanically or electrically drop to indicate the zone.
(iv)
Cathode Ray Tube (CRT) display.
A zone in alarm is represented by a numeric, English language or
combination display on an electronic cathode ray tube.
(v)
Hard copy print-out. The
alarm zone is represented by a numeric, English language or combination
print-out on hard copy paper. The printer shall include paper advance that
would allow multiple zones to print without overprinting.
(4)
Operation. Alarm
conditions on any of the annunciators shall lock-in or maintain their alarm
identification status until the device that initiated the alarm is reset and a
system reset switch actuated. Control panels that indicate all the zones may
serve as the annunciator if properly located for accessibility. Provisions
shall be made to test all zone indicators without actuating the alarm devices.
Trouble signals, system reset, bypass and other fire alarm system functions may
be included with annunciator panels.
(5)
Hard copy printing.
(i)
When required. Hard copy
printers shall be installed in manual and automatic detection fire alarm
systems when 50 zones or more are required. If multi-function systems are used,
fire alarm system alarms shall have priority and be readily distinguished from
all other signals. If the multi-function system is not prioritized, a separate
printer shall be used for fire alarm functions only. The order of priority
shall be as follows:
(A) Fire alarm and
process alarm.
(B) Supervisory and
fire trouble signals.
(C) Hold-up
and burglar alarms.
(D) Other
signals.
(ii)
Locations. Hard copy printers shall be installed in locations
that are generally supervised by building personnel to prevent tampering and
vandalism by unauthorized persons. If a printer is utilized for annunciation
purposes, its accessibility to fire service and building officials shall be
considered.
(iii)
Operation. Hard copy printers shall provide positive
documentation of all fire alarm conditions within the system. The documentation
shall include a printed record of date, time of day, and a method of
identifying the zone of alarm initiation. The zone identification may be by
precoded punched holes, numeric or English language print. Printers shall be
positive in operation with circuits designed to prevent confused documentation
and shall store simultaneous alarm signals so that all alarm zones will be
recorded.
(e)
Signalling devices.
(1)
Audible signalling devices shall be installed in all occupancies required to
have a manual or automatic fire alarm system.
(i)
Types. Audible
signalling devices may be any approved bell, horn, chime, buzzer, siren or
speaker. Signalling devices shall be electrically operated with wiring to the
devices supervised for opens, shorts or grounds. Trouble conditions on the
supervised circuits shall be indicated on the system fire alarm control
panel.
(ii)
Locations.
Audible signalling devices shall be installed so that they can be
heard above all other normal ambient noises in every occupied space of the
facility. Calculations shall be made when placing audible signalling devices
for a minimum of three decibels (dba) above the normal ambient noise levels.
Considerations shall be made for surrounding acoustics, ceiling heights, room
door penetrations, and ambient noise levels.
(iii)
Usage. Audible
signalling devices shall be of a distinctive sound and pitch from any other
signalling devices used in the area. No more than one type of fire alarm
signalling device may be used in an area. Audible signalling devices may be
used for other purposes, providing fire alarm signalling has priority, and the
alternate use signal is of a different sound and pitch.
(iv)
Mounting. Audible
signalling devices shall be mounted as close as practical to the ceiling in
areas with ceilings 8 feet or less. In areas with higher ceilings, the audible
signalling devices shall be installed at 8 feet. Signalling devices that
provide adequate sound levels may be installed above the 8 foot height in large
open areas.
(2) Visual
signalling devices may be required by the Department in occupancies that
shelter, employ, treat or provide entertainment for persons with known hearing
impairments.
(i)
Types.
Visual signalling shall flash on and off when activated or in a manner that
clearly signifies an alarm condition. The visual indicators shall be red or
white with "Fire" inscribed. Strobe flashing is permitted providing the flash
rate is outside the rate that affects persons with epileptic conditions. Visual
signalling devices may be installed as combination units with audible
signalling devices.
(ii)
Locations. Visual signalling devices shall be installed so
that they can be seen during alarm conditions from any point within corridors
and large open areas. If smoke barrier sections are provided, a minimum of one
visual signalling unit shall be provided in each smoke barrier section. In
addition, visual signalling devices shall be installed in classrooms,
apartments or other areas where it is known that persons with hearing
impairments will normally reside or function in without the presence of persons
with normal hearing capabilities.
(iii)
Mounting. Visual
signalling devices in corridors may be side wall or ceiling mounted within a
maximum height of 8 feet above the finished floor. Visual signalling units that
are designed for large open areas may be above the 8 foot height providing they
are visible from all points of the area they are intended to cover.
(3) Presignal systems may only be
used in special applications approved by the Department. When presignal systems
are used, a method of initiating a general alarm shall be provided at each pull
station and the control panel location.
(f)
Supervision. Fire alarm
control panels shall provide electrical supervision for all alarm initiating
circuits, signalling circuits and normal operating power supplies. Supervision
shall include wiring from the control panel terminations to the terminations of
all the devices on the circuits.
(1) Trouble
signals shall comply with the following:
(i)
An open or grounded condition in these circuits shall cause a trouble signal to
sound at the control panel.
(ii)
The trouble signal shall be distinctive in sound from alarm signals, continuous
in operation and may be common to all supervised circuits in a single
system.
(iii) A trouble signal
silence switch is permitted providing its operation transfers the trouble
indication to a lamp or other visible indicator that remains on until the
trouble condition is corrected. The trouble signal silence switch shall be
electrically arranged so that the trouble signal will sound if the switch is in
the silence position and no trouble exists in the system.
(iv) Trouble signals shall be installed at
each fire alarm control panel either mounted in the control panel or mounted
adjacent thereto. If the control panel is located in an area not regularly
frequented by building personnel, additional trouble signals shall be installed
in areas where they will be readily heard by building authorities.
(2) A single break or a single
ground fault in any of the electrically supervised alarm initiating circuits or
interruption and restoration of the main or secondary source of power to the
control panel shall not cause signalling devices to operate. Trouble signals
shall operate only on any of the conditions in this paragraph.
(3) Two wire circuits utilizing end-of-line
supervisory devices or four wire circuits allowing for McCulloh operation are
permitted for alarm initiating circuits. When end-of-line devices (E.O.L.) are
used, the alarm initiating units containing the E.O.L. devices shall be clearly
marked.
(4) In voice communication
systems where speakers are used to produce audible fire alarm signals, a
failure of a pre-amp unit, tone generator or audio amplifier shall cause a
trouble signal on the control panel except pre-amps, tone generators, or audio
amplifiers enclosed as integral parts serving only a single speaker. In these
systems, the wiring to speakers shall be electrically supervised as in other
signalling devices.
(g)
Power source. Fire alarm systems shall be powered from two
sources of electrical supply voltages.
(1) The
main source of operating voltage shall be connected to the load side of the
main service of commercial power or the main distribution service of an
isolated power plant located on the premises. The connection shall be made
through an overcurrent protective device in an approved manner with the
overcurrent protective device lockable and conspicuously identified with the
designation "Fire Alarm Supply."
(2) The second source of power may be one of
the following:
(i) A generator set approved
for emergency lighting power sized to accommodate the total load of its
intended use including the fire alarm system. The fuel supply shall be
sufficient to operate the auxiliary generator for a minimum of 12 hours with
refueling available on short notice for an additional 12 hour period.
(ii) The second source or back-up power may
be by the utilization of storage batteries located in the control panel or as
near as possible in a separate cabinet adjacent to the control panel. Batteries
used for fire alarm systems shall be designed for their intended use and shall
not supply power or be used for other purposes. The transfer from loss of
normal power to back-up battery source shall be automatic.
(A) Batteries shall be sized to operate the
entire fire alarm system under normal load for a minimum of 24 hours during
normal power outages with sufficient power to operate alarm signalling devices
a minimum of 5 minutes after the 24 hour period.
(B) Automatic charging circuits shall be
provided for recharging the batteries after use and for maintaining the
batteries at full charge under conditions of normal power applied.
(h)
Approved equipment. Detection devices, alarm indicating
devices, control panels, and connected components of the fire alarm systems
shall be listed by Underwriters' Laboratories or approved by Factory Mutual or
other accredited agency accepted by the Board. All such items shall be listed
or approved for the purpose of its intended use and shall be installed in a
manner not to exceed the maximum approved specifications.
(i)
Wiring. Wiring and
installation work shall be performed in accordance with the 1981 National
Electrical Code as adopted by the National Fire Protection Association,
Batterymarch Park, Quincy, Massachusetts 02269.
(j)
Elevator detectors in a building
that has a manual or automatic fire detection system. Elevator recall
detectors shall be interconnected to the fire alarm control panel for
monitoring alarm and trouble conditions. This monitoring shall be in addition
to the operation for elevator recall.
(k)
Automatic extinguishing systems.
Buildings required to have automatic extinguishing systems and fire
alarm systems shall comply with the following:
(1) Operation of an automatic extinguishing
system shall cause the initiation of the fire alarm system.
(2) The closing of shut off valves shall
operate the fire alarm trouble signal in a manner that does not disturb
supervision of an alarm initiating or indicating circuits.
This section cited in 34 Pa. Code §
50.51 (relating to manual system);
and 34 Pa. Code §
50.52 (relating to automatic
system).