Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 50 - GENERAL REQUIREMENTS-BUILDINGS
CONSTRUCTION TYPES
Section 50.11 - Construction tables
Current through Register Vol. 54, No. 38, September 21, 2024
(a) Fireresistive construction. Fireresistive construction shall be the type of construction in which the walls, floors, roof and structural members are steel, iron, masonry, concrete or other noncombustible materials meeting all of the requirements of this chapter and having a minimum fireresistive rating as indicated in the construction table.
CONSTRUCTION TABLE
Component Description | Minimum Fireresistive Rating |
WALLS | |
Exterior bearing walls... | 3-hour Noncombustible |
Exterior panel and curtain walls... | 1-hour Noncombustible |
PARTITIONS | |
Bearing partitions... | 2-hour Noncombustible |
(1 1/2-hour B Label door assemblies) | |
Nonbearing partitions... | 1-hour Noncombustible |
(3/4-hour C Label door assemblies) | |
Partitions enclosing stairs and other vertical openings... | 2-hour Noncombustible |
(1 1/2-hour B Label door assemblies) | |
Partitions enclosing exit access corridors... | 1-hour Noncombustible |
(3/4-hour C Label door assemblies) | |
COLUMNS | |
Supporting Masonry... | 3-hour Noncombustible |
Other... | 3-hour Noncombustible |
Supporting roofs only... | 2-hour Noncombustible |
GIRDERS AND TRUSSES | |
Supporting masonry walls... | 3-hour Noncombustible |
Other... | 3-hour Noncombustible |
Supporting roofs only... | 1-hour Noncombustible |
FLOOR PANELS-Including beams and joists... | 2-hour Noncombustible |
ROOF PANELS-Including beams and joists... | 1-hour Noncombustible |
EXCEPTIONS TO CONSTRUCTION TABLE
(b) Noncombustible construction. Noncombustible construction shall be the type of construction in which all structural members including walls, floors, roofs and their supports are steel, iron, masonry, concrete, or other noncombustible materials having a minimum fireresistive rating as indicated in the construction table.
CONSTRUCTION TABLE
Component Description | Minimum Fireresistive Rating |
WALLS | |
Exterior bearing walls... | Noncombustible |
Exterior panel and curtain walls... | Noncombustible |
Penthouse enclosure walls... | Noncombustible |
PARTITIONS | |
Bearing partitions... | Noncombustible |
Nonbearing partitions... | Noncombustible |
Partitions enclosing stairs and other vertical openings... | 1-hour Noncombustible |
(3/4-hour C Label fire door assemblies) | |
Partitions enclosing exit access corridors... | 1-hour Noncombustible |
COLUMNS | |
Supporting Masonry... | Noncombustible |
Other... | Noncombustible |
Supporting roofs only... | Noncombustible |
GIRDERS AND TRUSSES | |
Supporting masonry walls... | Noncombustible |
Other... | Noncombustible |
Supporting roofs only... | Noncombustible |
FLOOR PANELS-Including beams and joists... | Noncombustible |
ROOF PANELS-Including beams and joists... | Noncombustible |
EXCEPTIONS TO CONSTRUCTION TABLE
(c) Protected heavy timber. Protected heavy timber shall be the type of construction in which the exterior walls and fire walls are of masonry, reinforced concrete, or other approved noncombustible materials meeting the requirements of this chapter and having a fireresistive rating as indicated in the construction table. Heavy timber members of the following minimum nominal sizes may be used as an alternative to the construction table without meeting the minimum fireresistive rating.
Columns | 8" x 8" |
Trusses supporting floors | 6" x 6" |
Trusses supporting roofs only | 4" x 6" |
Girders supporting floors | 8" x 10" |
Girders supporting roofs only | 6" x 10" |
Beams supporting floors | 6" x 10" |
Beams supporting roofs only | 4" x 8" |
Floor panels | 3" |
Roof panels | 2" |
CONSTRUCTION TABLE
Component Description | Minimum Fireresistive Rating |
WALLS | |
Exterior bearing walls... | 2-hour Noncombustible |
Exterior panel and curtain walls... | 2-hour Noncombustible |
PARTITIONS | |
Bearing partitions... | 1-hour Noncombustible |
(3/4-hour C Label door assemblies) | |
Nonbearing partition... | 1-hour Noncombustible |
(3/4-hour C Label door assemblies) | |
Partitions enclosing stairs and other vertical openings... | 1-hour Noncombustible |
(3/4-hour C Label fire door assemblies) | |
Partitions enclosing exit access corridors... | 1-hour Noncombustible |
(3/4-hour C Label door assemblies) | |
COLUMNS | |
Supporting Masonry... | 2-hour Noncombustible |
Other... | 2-hour Noncombustible |
Supporting roofs only... | 1-hour Noncombustible |
GIRDERS AND TRUSSES | |
Supporting masonry walls... | 1-hour Noncombustible |
Other... | 1-hour Noncombustible |
Supporting roofs only... | 1-hour Noncombustible |
FLOOR PANELS-Including beams and joists... | 1-hour Noncombustible |
ROOF PANELS-Including beams and joists... | 1-hour Noncombustible |
EXCEPTIONS TO CONSTRUCTION TABLE
(d) Ordinary construction. Ordinary construction shall be the type of construction in which the exterior walls are of masonry, concrete or other noncombustible material meeting the requirements of this chapter and having a minimum fireresistive rating as indicated in the construction table. Interior framing may be partially or wholly of wood.
CONSTRUCTION TABLE
Component Description | Minimum Fireresistive Rating |
WALLS | |
Exterior bearing walls... | 2-hour Noncombustible |
Exterior panel and curtain walls... | Noncombustible |
Penthouse enclosure walls... | 2-hour Noncombustible |
PARTITIONS | |
Bearing partitions... | None |
Nonbearing partitions... | None |
Partitions enclosing stairs and other vertical openings... | 1-hour |
(3/4-hour C Label fire door assemblies) | |
Partitions enclosing exit access corridors... | 1-hour |
(3/4-hour C Label fire door assemblies) | |
COLUMNS | |
Supporting masonry... | None |
Other... | None |
Supporting roofs only... | None |
GIRDERS AND TRUSSES | |
Supporting masonry walls... | None |
Other... | None |
Supporting roofs only... | None |
FLOOR PANELS-Including beams and joists... | None |
ROOF PANELS-Including beams and joists... | None |
EXCEPTIONS TO CONSTRUCTION TABLE
(e) Wood frame construction. Wood frame construction shall be the type of construction in which structural members and their support are constructed of wood or are dependent upon wood for support and having a minimum fireresistive rating as indicated in the construction table.
CONSTRUCTION TABLE
Component Description | Minimum Fireresistive Rating |
WALLS | |
Exterior bearing walls... | None |
Exterior panel and curtain walls... | None |
Penthouse enclosure walls... | None |
PARTITIONS | |
Bearing partitions... | None |
Nonbearing partitions... | None |
Partitions enclosing stairs and other vertical openings... | 1-hour |
(3/4-hour C Label fire door assemblies) | |
Partitions enclosing exit access corridors... | 1-hour |
COLUMNS | |
Supporting Masonry... | None |
Supporting roofs only... | None |
General support... | None |
GIRDERS AND TRUSSES | |
Supporting masonry walls... | None |
Other... | None |
Supporting roofs only... | None |
FLOOR PANELS-Including beams and joists... | None |
ROOF PANELS-Including beams and joists... | None |
CONSTRUCTION TABLE NOTES
This section cited in 34 Pa. Code § 49.1 (relating to definitions); 34 Pa. Code § 50.25 (relating to stair towers); and 34 Pa. Code § 50.43 (relating to classification).