Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 3a - BOILER AND UNFIRED PRESSURE VESSEL REGULATIONS
Subchapter H - SPECIAL INSTALLATIONS
Section 3a.167 - Hot water/steam heat exchangers

Universal Citation: 34 PA Code ยง 3a.167

Current through Register Vol. 54, No. 38, September 21, 2024

(a) Heat exchangers must be manufactured under the ASME Code.

(b) Heat exchangers must have adequate over-pressure protection to protect both systems.

(c) Heat exchangers used for domestic hot water supply must have a high temperature limit switch designed not to exceed 210°F.

(d) Inspection of hot water/steam heat exchangers shall be performed in accordance with § 3a.111(8) (relating to field inspections).

This section cited in 34 Pa. Code § 3a.3 (relating to scope).

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.