Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 3a - BOILER AND UNFIRED PRESSURE VESSEL REGULATIONS
Subchapter B - REQUIREMENTS FOR BOILERS AND UNFIRED PRESSURE VESSELS
GENERAL REQUIREMENTS
Section 3a.27 - Different working pressures
Current through Register Vol. 54, No. 38, September 21, 2024
(a) At least one safety valve on each boiler must be set at or below the maximum allowable working pressure. All other valves may be set within a range of 3% above the maximum allowable working pressure. The range of setting of all of the saturated steam valves on the boiler may not exceed 10% of the saturated steam valve set at the highest pressure.
(b) When a boiler system is comprised of boilers with different maximum allowable working pressures having minimum safety valve settings varying more than 6% and connected so that steam flows toward the lower pressure boiler, the boiler system must meet one of the following requirements: