Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 39 - SAFETY STANDARDS-GENERAL
Subchapter B - ELECTRIC SAFETY
TELEPHONE AND OTHER SIGNAL APPARATUS ON CIRCUITS EXPOSED BY SUPPLY LINES
Section 39.304 - Grounding of arresters for signaling systems
Current through Register Vol. 54, No. 38, September 21, 2024
(a) Exemptions. The ground connections for outside installations of cable protectors employed solely to prevent electrical injury to the cable need not conform to the requirements of this section. For the provisions governing the grounding of the metal cases of outdoor apparatus as covered by this section, reference should be made to §§ 39.61-39.70 (relating to methods of protective grounding).
(b) Arresters. Arresters shall be permanently and effectively grounded in the following manner:
(c) Connecting ground conductor to pipes. Ground conductors shall be attached to pipes by means of suitable ground clamps. The entire surface of the pipe to be covered by the clamp shall be thoroughly cleaned.
(d) Connecting ground conductor to driven rod or pipe. The ground conductor shall be attached to the rod or pipe so as to give reliable connection both mechanically and electrically and in such a manner as to prevent corrosion when the joint is buried in the earth.
(e) Connecting ground conductor to buried electrode. If a buried plate or other metal electrode is employed, the ground conductor shall be securely fastened to it in such manner as to make a reliable electrical and mechanical contact.
This section cited in 34 Pa. Code § 39.192 (relating to scope).