STORAGE BATTERIES
Section 39.125 - Guarding live parts in battery room

Universal Citation: 34 PA Code ยง 39.125

Current through Register Vol. 54, No. 38, September 21, 2024

(a) The arrangement of cells and connections shall be such that no two current-carrying parts between which a voltage exceeding 150 exists, shall be closer than three feet, if the parts are so exposed that persons are liable to make accidental contact with both at the same time.

(b) No conductor above 150 volts to ground shall be placed in any passageway, unless guarded or isolated by elevation.

This section cited in 34 Pa. Code § 39.85 (relating to general requirements); 34 Pa. Code § 39.121 (relating to applicability); and 34 Pa. Code § 39.201 (relating to storage batteries, transformers, and lightning arresters).

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.