Section 39.106 - Isolating live parts by elevation
Universal Citation: 34 PA Code ยง 39.106
Current through Register Vol. 54, No. 38, September 21, 2024
Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:
Voltage of Conductors | Elevation (in feet) |
300-750 | 7 |
750-2,500 | 7 |
2,500-7,500 | 8 |
7,500-30,000 | 9 |
30,000-70,000 | 10 |
70,000-100,000 | 12 |
Over 100,000 | 14 |
This section cited in 34 Pa. Code § 39.143 (relating to isolation by elevation); 34 Pa. Code § 39.160 (relating to guarding live parts of switches and automatic cut-outs not installed on switchboards); and 34 Pa. Code § 39.199 (relating to guarding or isolating live parts).
Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.