Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 39 - SAFETY STANDARDS-GENERAL
Subchapter B - ELECTRIC SAFETY
PROTECTIVE ARRANGEMENTS OF EQUIPMENT
Section 39.106 - Isolating live parts by elevation

Universal Citation: 34 PA Code ยง 39.106
Current through Register Vol. 54, No. 38, September 21, 2024

Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:

Voltage of ConductorsElevation (in feet)
300-750 7
750-2,500 7
2,500-7,500 8
7,500-30,000 9
30,000-70,00010
70,000-100,00012
Over 100,00014

This section cited in 34 Pa. Code § 39.143 (relating to isolation by elevation); 34 Pa. Code § 39.160 (relating to guarding live parts of switches and automatic cut-outs not installed on switchboards); and 34 Pa. Code § 39.199 (relating to guarding or isolating live parts).

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.