Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 39 - SAFETY STANDARDS-GENERAL
Subchapter B - ELECTRIC SAFETY
LIGHTNING ARRESTERS
Section 39.185 - Guarding live parts

Universal Citation: 34 PA Code ยง 39.185

Current through Register Vol. 54, No. 38, September 21, 2024

(a) Current-carrying parts of arresters on circuits above 750 volts, unless effectively isolated by elevation, shall be adequately guarded to protect persons from inadvertent contact with them, or from injury by arcing.

(b) Lightning arresters, unless provided with disconnectors, which are always opened before work is done on the arresters shall be so arranged that necessary adjustments are possible, without approach to current-carrying parts, through the use of permanently grounded mechanisms or suitable insulating appliances. If it is necessary that charging or adjustments be made with arresters alive, permanently grounded mechanisms or suitable insulating appliances shall always be provided.

(c) Guarding shall comply with §§ 39.105 and 39.143 (relating to guarding live parts; isolation by elevation).

This section cited in 34 Pa. Code § 39.201 (relating to storage batteries, transformers and lightning arresters).

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.