Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 14a - STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS
Subchapter A - GENERAL PROVISIONS
OUTSIDE AND ABOVEGROUND STORAGE
Section 14a.3 - Foundations and supports
Tanks shall be supported so as to prevent excessive concentration of loads on the supporting portion of the shell. Tank foundations shall be designed to minimize the possibility of uneven settling of the tank and to minimize corrosion in any part of the tank resting on the foundation. Tanks shall rest directly on the ground or on suitable foundations or supports of concrete, masonry, piling, or steel. Exposed steel supports shall be protected by fire resistive materials to provide a fire resistance rating of not less than 2 hours, with the exception of tanks with capacities of 660 gallons or less, installed on farm or other isolated property and only used for private purposes. No combustible piling shall be permitted above ground level.
This section cited in 34 Pa. Code § 14a.111 (relating to storage and handling); 34 Pa. Code § 14a.141 (relating to scope and application); 34 Pa. Code § 14a.151 (relating to scope and application); and 34 Pa. Code § 14a.161 (relating to general provisions).