Pennsylvania Code
Title 34 - LABOR AND INDUSTRY
Part I - Department of Labor and Industry
Chapter 14a - STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS
Subchapter A - GENERAL PROVISIONS
INSIDE BUILDING STORAGE
Section 14a.33a - Tank openings other than vents for tanks inside buildings

Universal Citation: 34 PA Code ยง 14a.33a

Current through Register Vol. 54, No. 38, September 21, 2024

(a) The outlet of a vapor recovery line for which connections are made and broken shall be located outside of buildings at a location free from any source of ignition and not less than 5 feet away from any building opening. Such connections shall be closed and tight when not in use and shall be properly identified.

(b) Tank openings provided for purposes of vapor recovery shall be protected against possible vapor release by means of a spring-loaded check valve or drybreak connections, or other approved device, unless the opening is pipe-connected to a vapor processing system. Openings designed for combined fill and vapor recovery shall also be protected against vapor release unless connection of the liquid delivery line to the fill pipe simultaneously connects the vapor recovery line. All connections shall be vapor-tight.

Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.