Pennsylvania Code
Title 28 - HEALTH AND SAFETY
Part V - Department of Drug and Alcohol Programs
Chapter 705 - PHYSICAL PLANT STANDARDS
Subchapter A - RESIDENTIAL FACILITIES
Section 705.10 - Fire safety
Universal Citation: 28 PA Code ยง 705.10
Current through Register Vol. 54, No. 44, November 2, 2024
(a) Exits.
(1) The residential
facility shall:
(i) Ensure that stairways,
hallways and exits from rooms and from the residential facility are
unobstructed.
(ii) Maintain a
minimum of two exits on every floor, including the basement, that are separated
by a minimum distance of 15 feet.
(iii) Maintain each ramp, interior stairway
and outside steps exceeding two steps with a well-secured handrail and maintain
each porch that has over an 18-inch drop with a well-secured railing.
(iv) Clearly indicate exits by the use of
signs.
(v) Light interior exits and
stairs at all times.
(2)
Portable ladders and rope escapes are not considered exits, but may be used in
addition to standard exits.
(b) Smoke detectors and fire alarms. The residential facility shall:
(1) Maintain a minimum of one operable,
automatic smoke detector on each floor, including the basement and
attic.
(2) On floors with resident
bedrooms, maintain a smoke detector which shall be located within 15 feet of
each bedroom door. On floors with no resident bedrooms, the smoke detection
device shall be located in a common area or hallway. All detection devices
shall be interconnected.
(3) Repair
inoperable smoke detectors or fire alarms within 48 hours of the time the
detector or alarm is found to be inoperative.
(4) Maintain a manual fire alarm system that
is audible throughout the facility in a residential facility where four or more
residents reside.
(5) Maintain
automatic smoke detectors and fire alarms of a type approved by the Department
of Labor and Industry or by the Underwriters Laboratories.
(6) Maintain all smoke detectors and fire
alarms so that each person with a hearing impairment will be alerted in the
event of a fire, if one or more residents or staff persons are not able to hear
the smoke detector or fire alarm system.
(c) Fire extinguisher. The residential facility shall:
(1) Maintain a
portable fire extinguisher with a minimum of an ABC rating, which shall be
located on each floor. If there is more than 2,000 square feet of floor space
on a floor, the residential facility shall maintain an additional fire
extinguisher for each 2,000 square feet or fraction thereof.
(2) Maintain at least one portable fire
extinguisher with a minimum of an ABC rating in each kitchen.
(i) This fire extinguisher shall meet the
requirement of one portable fire extinguisher for a 2,000 square foot
area.
(ii) The extinguisher shall
be located near an exit and away from the cooking area.
(3) Ensure fire extinguishers are inspected
and approved annually by the local fire department or fire extinguisher
company. The date of the inspection shall be indicated on the extinguisher or
inspection tag. If a fire extinguisher is found to be inoperable, it shall be
replaced or repaired within 48 hours of the time it was found to be
inoperable.
(4) Instruct all staff
in the use of the fire extinguishers upon staff employment. This instruction
shall be documented by the facility.
(d) Fire drills. The residential facility shall:
(1) Conduct
unannounced fire drills at least once a month.
(2) Conduct fire drills during normal
staffing conditions.
(3) Ensure
that all personnel on all shifts are trained to perform assigned tasks during
emergencies.
(4) Maintain a written
fire drill record including the date, time, the amount of time it took for
evacuation, the exit route used, the number of persons in the facility at the
time of the drill, problems encountered and whether the fire alarm or smoke
detector was operative.
(5) Conduct
a fire drill during sleeping hours at least every 6 months.
(6) Prepare alternate exit routes to be used
during fire drills.
(7) Conduct
fire drills on different days of the week, at different times of the day and
night and on different staffing shifts.
(8) Set off a fire alarm or smoke detector
during each fire drill.
(9)
Prohibit the use of elevators during a fire drill or a fire.
Disclaimer: These regulations may not be the most recent version. Pennsylvania may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.