Current through Register Vol. 54, No. 44, November 2, 2024
(a)
Radon testing protocols. The certified individual shall ensure
that the requirements in this section are completed. For testing that is
required to be reported to the Department under §
240.303 (relating to reporting of
information), radon testing shall be performed in accordance with all of the
following testing protocols:
(1)
Placement of testing devices. Testing devices shall be placed
as follows:
(i) At least 3 feet from exterior
doors, windows or ventilation ducts.
(ii) Out of the direct flow of air.
(iii) At least 1 foot from ceilings and
exterior walls.
(iv) At least 20
inches but not more than 6 feet from the floor.
(v) At least 4 inches from other objects
horizontally or vertically above the detector.
(vi) At least 4 feet from heat sources
including fireplaces, furnaces and direct sunlight.
(vii) At least 7 feet from sump
pits.
(viii) Where the device will
remain undisturbed during the test period.
(2)
Improper placement of testing
devices. Testing devices may not be placed in the following locations:
(i) Bathrooms.
(ii) Kitchens.
(iii) Within 10 feet of washer/dryer
unit.
(iv) Spa rooms or other areas
of high humidity.
(v)
Closets.
(vi) Cupboards.
(vii) Sump pits.
(viii) Crawlspaces or nooks within the
foundation.
(3)
Short-term tests. Short-term tests shall be taken in the
lowest livable level of each structural zone that contacts the soil.
(4)
Conditions of testing.
Testing shall be conducted under the following conditions:
(i) Testing devices must remain undisturbed
during the testing period.
(ii) A
short-term test must range in duration from 48 hours to 90 days.
(iii) Short-term tests must be conducted
under closed-building conditions.
(iv) Closed-building conditions must begin at
least 12 hours prior to the beginning of the test period for tests lasting less
than 96 hours.
(v) Closed-building
conditions consist of all of the following criteria:
(A) All windows must be closed.
(B) All external doors must be closed except
for normal entry and exit. Structural openings due to disrepair or structural
defects shall be repaired to correct their condition prior to initiation of
testing.
(C) Normal operation of
permanently installed HVAC systems must continue during closed-building
conditions.
(D) Fireplaces, wood
stoves and coal stoves may not be operated unless they are normal sources of
heat for the building.
(E) Air
conditioning systems that recycle interior air may be operated during
closed-building conditions.
(F)
Whole-house fans may not be operated during the test period. Portable window
fans shall be removed from windows or sealed in place. Window air conditioning
units may only be operated in a recirculation mode. If the building contains an
air handling system, the air handling system may not be set for continuous
operation unless the air handling equipment is specifically used for radon
control and is labeled accordingly.
(G) In buildings with permanently installed
radon mitigation systems, the mitigation system must be functioning during the
test period. If the system is not functioning, the client must be notified
immediately.
(H) Operation of fans,
portable dehumidifiers, portable humidifiers, portable air filters and window
air conditioners may not create a direct flow of air on the radon testing
device.
(vi) All
closed-building conditions shall be inspected and documented at the time of
placement and retrieval of the detectors.
(vii) Short-term tests of fewer than 96 hours
may not be conducted during unusually severe storms or periods of high winds of
30 miles per hour or greater. Local weather forecasts shall be checked and
documented prior to placing short-term test devices when the test period is
less than 96 hours.
(viii)
Instructions describing closed-building conditions required in this section
shall be provided to the persons who control the building.
(ix) Only co-located duplicate tests may be
averaged.
(5)
Minimum requirements for short-term testing.
(i)
Simultaneous testing using
short-term passive devices.
(A)
Simultaneous testing must comprise at least two short-term indoor radon tests
conducted simultaneously with identical test devices.
(B) Simultaneous testing devices shall be:
(I) Co-located and the near edges spaced 4 to
5 inches apart.
(II) Exposed for
the same test period.
(C)
Both tests and the average of the simultaneous tests shall be reported to the
client, except as indicated in subclause (II):
(I) If the RPD is greater than 67% for
simultaneous test results that are both between 2.0 and 3.9 pCi/L, the tests
shall be reported to the client and the cause investigated, documented and
corrected.
(II) If the RPD is
greater than 36% for simultaneous test results that are both equal to or
greater than 4.0 pCi/L, the tests may not be reported to the client, and the
cause shall be investigated, documented and corrected.
(D) If one test is equal to or greater than
4.0 pCi/L and one test is less than 4.0 pCi/L, and the higher test is more than
twice the amount of the lower test, the tests may not be reported to the
client.
(ii)
CRM
testing.
(A) A CRM must have the
capability to integrate and record a new result at least hourly.
(B) The minimum test period is 48 hours, with
44 contiguous hours of usable data to produce a valid average. The first 4
hours of data from a CRM may be discarded.
(C) The contiguous results shall be averaged
to produce a result that is reported to the client.
(D) A copy of the hourly printout shall be
provided to the client as part of the test results.
(6)
Real estate
testing. Real estate testing shall be conducted using all of the
following anti-tampering procedures:
(i)
Anti-tampering devices shall be employed to indicate if a test device was moved
during the testing period.
(ii) The
buyer, seller, occupant, real estate professional or other individual in
control of the property shall sign a Conditions for Short-Term Radon Testing
Agreement, which must contain the information in Appendix B (relating to
non-interference agreement for real estate radon testing).
(iii) If the Conditions for Short-Term Radon
Testing Agreement cannot be signed by the buyer, seller, occupant, real estate
professional or other individual in control of the property, the reason shall
be documented on the completed agreement.
(iv) A Radon Testing in Progress Notice shall
be posted and in a conspicuous indoor location. The notice shall be posted upon
initiation of a radon test and include all of the following statements:
(A) "Radon Testing in Progress."
(B) "Keep all windows closed."
(C) "Keep all exterior doors closed, except
for normal entry and exit."
(D) "Do
not move or touch the radon testing device."
(7)
Multifamily building
tests. Multifamily building tests shall be performed in accordance
with ANSI/AARST MAMF-2017, "Protocol for Conducting Radon and Radon Decay
Product Measurements in Multifamily Buildings," or its equivalent as determined
by the Department.
(8)
Multifamily building mitigation. Multifamily building
mitigation shall be performed in accordance with ANSI/AARST RMS-MF 2014,"Radon
Mitigation Standards for Multifamily Buildings," or its equivalent as
determined by the Department.
(9)
School and commercial building tests. School and commercial
building tests shall be performed in accordance with Radon Measurement
in Schools (EPA 402-R-92-014) or its equivalent as determined by the
Department.
(10)
New
construction and buildings under renovation. This paragraph provides
the testing requirements for new construction and buildings under renovation. A
newly constructed building or existing building under renovation may not be
tested for radon or radon progeny unless all of the following items have been
installed:
(i) Insulation.
(ii) Exterior doors with associated
hardware.
(iii) Windows.
(iv) Fireplaces and fireplace dampers, if
they are or will be installed.
(v)
Heating, air conditioning and plumbing appliances.
(vi) Ceilings.
(vii) Interior trim and coverings for the
exterior walls.
(viii) Exterior
siding, weatherproofing and caulking.
(ix) Interior and exterior structural
components.
(x) Interior or
exterior work that may adversely affect the test validity.
(11)
Postmitigation testing.
(i) Testing conducted while temporary radon
reduction systems are in use may not be used as the postmitigation
test.
(ii) The mitigation system
must be operated continuously during the entire test period. If the system is
not functioning, the client must be notified immediately.
(iii) The postmitigation test may not be
performed sooner than 24 hours or later than 30 days following the completion
and activation of the mitigation system or an alteration to an existing system
unless unforeseen circumstances prohibit the testing being performed within
this timeframe, such as the owner or occupier refusing or ignoring requests to
complete the postmitigation test.
(iv) Postmitigation testing shall be
conducted in accordance with this subsection.
(b)
Result Report Form.
(1) A tester shall have a Department-approved
Result Report Form. Testers shall provide the client with a completed Result
Report Form within 10 business days from the completion of the test or the
receipt of the test results from the laboratory. The Result Report Form must
contain all of the following as available:
(i)
Each test result in pCi/L and rounded to one decimal place. Standard
mathematical rules for rounding shall be followed.
(ii) Notification of an invalid radon test
with an explanation and without a test result given.
(iii) The average of co-located test device
results as well as the individual results.
(iv) The exact start and stop dates and times
of the test period.
(v) The
complete street address of the test location, including, when applicable, the
apartment, suite or building number.
(vi) The test device used and its
manufacturer, model and serial number.
(vii) The complete name, street address and
telephone number of the tester.
(viii) The name and Department certification
number of each tester placing and retrieving each testing device.
(ix) The name and certification number of the
laboratory analyzing the testing device, if applicable.
(x) A statement whether a mitigation system
was observed in the building during placement or retrieval of the testing
device, including whether the mitigation system was operating.
(xi) A statement describing if tampering,
interference or deviations from the required test conditions was
observed.
(xii) A description of
the condition (open, closed or not applicable) of permanent vents that allow
outdoor air into the building, such as crawlspace vents or combustion air
supply to combustive appliances.
(xiii) A description of unusually severe
storms or periods of high winds during the test period.
(xiv) The location within the building of
each testing device.
(xv) The
Pennsylvania "Notice to Clients" statement as indicated in §
240.302 (relating to required
client information).
(xvi) If using
a CRM, a copy of the device printout.
(xvii) If using a CRM or electret reader, the
calibration expiration date.
(xviii) If using a CRM or electret reader,
the device serial number.
(xix) The
following radon health risk information:
Radon is the second leading cause of lung cancer, after
smoking. The U.S. Environmental Protection Agency (EPA) and the Surgeon General
strongly recommend taking further action when the home's radon test results are
4.0 pCi/L or greater. The National average indoor radon level is about 1.3
pCi/L. The higher the home's radon level the greater the health risk to you and
your family. Reducing your radon levels can be done easily, effectively and
fairly inexpensively. Even homes with very high radon levels can be reduced
below 4.0 pCi/L. For further information about reducing elevated radon levels,
please refer to the "Pennsylvania Consumers Guide to Radon Reduction."
(2) A laboratory shall
use a Department-approved Result Report Form. Laboratories shall provide the
client with a completed Result Report Form within 10 business days after
completion of test analysis. The Result Report Form must contain all of the
following as available:
(i) Each test result
in pCi/L and rounded to one decimal place. Standard mathematical rules for
rounding shall be followed.
(ii)
Notification of invalid radon tests with an explanation and without a test
result given.
(iii) The average of
co-located testing devices as well as the individual results.
(iv) The exact start and stop dates and times
of the test period.
(v) The
complete street address of the test location, including, when applicable, the
apartment, suite or building number, as available.
(vi) The test device used and its
manufacturer, model and serial numbers.
(vii) The name and certification number of
the laboratory analyzing the testing device.
(viii) The location within the building of
each test device, as available.
(ix) The Pennsylvania "Notice to Clients"
statement as indicated in § 240.302.
(x) If using a CRM, a copy of the device
printout.
(xi) The calibration
expiration date of the electret reader or continuous monitor.
(xii) The following radon health risk
information:
Radon is the second leading cause of lung cancer, after
smoking. The U.S. Environmental Protection Agency (EPA) and the Surgeon General
strongly recommend taking further action when the home's radon test results are
4.0 pCi/L or greater. The national average indoor radon level is about 1.3
pCi/L. The higher the home's radon level the greater the health risk to you and
your family. Reducing your radon levels can be done easily, effectively and
fairly inexpensively. Even homes with very high radon levels can be reduced
below 4.0 pCi/L. For further information about reducing elevated radon levels,
please refer to the "Pennsylvania Consumers Guide to Radon
Reduction."
The provisions of this §240.310 issued under sections 12
and 13 of the Radon Certification Act (63 P.S. §§
2012 and
2013); section 302 of the
Radiation Protection Act (35 P.S. §
7110.302); and section 1920-A of the
Administrative Code (71 P.S. § 510.20).
This section cited in 25 Pa. Code §
240.303 (relating to reporting of
information).